6 Set up with the display and adjustment module PLICSCOM
VEGACAL 69 • Two-wire 4 … 20 mA/HART
31178-EN-200929
Function
Reset value
Current output - failure
< 3.6 mA
Special parameters
All special parameters are reset to delivery status.
Peak value indicator
The min. and max. values are reset to the actual value.
The sensor is already set to the ordered national language. In this
menu item you can change the language. The following languages are
available as of software version 3.50:
•
Deutsch
•
English
•
Français
•
Espanõl
•
Pycckuu
•
Italiano
•
Netherlands
•
Japanese
•
Chinese
Language
German
HART offers standard and multidrop mode.
The mode "standard" with the fixed address 0 means outputting the
measured value as a 4 … 20 mA signal.
In Multidrop mode, up to 15 sensors can be operated on one two-wire
cable. An address between 1 and 15 must be assigned to each sen-
sor.
4)
In this menu item you determine the HART mode and enter the ad-
dress for multidrop.
HART mode
Standard
Address 0
The default setting is standard with address 0.
With this function
•
Load parameter adjustment data from the sensor into the display
and adjustment module
•
Write parameter adjustment data from the display and adjustment
module into the sensor
Service - Language
Service - HART mode
Copy sensor data
4)
The 4 … 20 mA signal of the sensor is switched off. The sensor uses a
constant current of 4 mA. The measuring signal is transmitted exclusively as
a digital HART signal.
Содержание VEGACAL 69
Страница 14: ...14 4 Mounting VEGACAL 69 Two wire 4 20 mA HART 31178 EN 200929 Fig 6 Inflowing medium...
Страница 57: ...57 Notes VEGACAL 69 Two wire 4 20 mA HART 31178 EN 200929...
Страница 58: ...58 Notes VEGACAL 69 Two wire 4 20 mA HART 31178 EN 200929...
Страница 59: ...59 Notes VEGACAL 69 Two wire 4 20 mA HART 31178 EN 200929...