Quick setup guide

Radar sensor for continuous level 

measurement of bulk solids

VEGAPULS SR 68

Modbus and Levelmaster protocol

Document ID: 47164

Содержание PULS SR 68

Страница 1: ...Quick setup guide Radar sensor for continuous level measurement of bulk solids VEGAPULS SR 68 Modbus and Levelmaster protocol Document ID 47164...

Страница 2: ...ns Horn antenna 9 3 3 Mounting instructions 9 4 Connecting to power supply and bus system 4 1 Connection 11 4 2 Wiring plan 12 5 Set up the sensor with the display and adjustment module 5 1 Insert dis...

Страница 3: ...f the art instrument complying with all prevailing regulations and guidelines The instrument must only be operated in a technically flawless and reliable condition The operator is responsible for the...

Страница 4: ...epted as the standard in field instrumentation The device fulfills the requirements of the following NAMUR recom mendations NE 21 Electromagnetic compatibility of equipment NE 43 Signal level for malf...

Страница 5: ...ties That is why we have introduced an environment management system with the goal of continuously improving company environmental pro tection The environment management system is certified according...

Страница 6: ...ument 12 Data Matrix Code for Smartphone App 13 Symbol of the device protection class 14 ID numbers instrument documentation 15 Reminder to observe the instrument documentation 16 Notified authority f...

Страница 7: ...bus and Levelmaster protocol 47164 EN 140129 Download the smartphone app VEGA Tools from the Apple App Store or the Google Play Store Scan the Data Matrix code on the type label of the instrument or E...

Страница 8: ...41 mm in the direction of the antenna 5 Remove the parabolic antenna 4 axially 6 Mount sensor flange on the adapter flange and fasten it tightly 7 Check if the O ring seal is present on the connection...

Страница 9: ...Insert the antenna from below into the vessel socket and secure it against falling off 4 Retighten the antenna with hexagon screws to the antenna socket torque max 2 5 Nm 1 8 lbf ft Note The radar se...

Страница 10: ...r protocol 47164 EN 140129 ca 10 mm 200 mm 7 87 Fig 4 Distance of the antenna to the vessel wall vessel ceiling 2 Note min socket diameter depending on the socket length 3 Note the instructions for se...

Страница 11: ...lock you should hear it snap in Proceed as follows 1 Unscrew the housing cover 2 Loosen compression nuts of the cable glands 3 Remove approx 10 cm 4 in of the cable mantle signal output strip approx 1...

Страница 12: ...able glands The seal ring must completely encircle the cables 10 Screw the housing cover back on The electrical connection is finished Information The terminal blocks are pluggable and can be removed...

Страница 13: ...ith this double chamber housing power supply MODBUS D0 D1 IS GND USB 1 2 4 3 1 3 4 5 2 off on Fig 8 Terminal compartment 1 USB interface 2 Slide switch for integrated termination resistor 120 3 Voltag...

Страница 14: ...ions each displaced by 90 It is not necessary to interrupt the power supply Proceed as follows 1 Unscrew the housing cover 2 Place the display and adjustment module in the requested posi tion onto the...

Страница 15: ...nd to retrofit the instrument with a display and adjustment module for continuous measured value indication a higher cover with an inspection glass is required 5 2 Parameter adjustment 1 Go via the di...

Страница 16: ...nown an adjustment with distances for example of 10 and 90 is also possible Starting point for these distance specifications is always the seal surface of the thread or flange With the function Echo c...

Страница 17: ...the menu item Additional settins with and confirm with OK With you have to select the menu item False signal suppression and confirm with OK 2 Confirm again with OK 3 Confirm again with OK 4 Confirm...

Страница 18: ...o longer matches the metrological conditions in the vessel The menu item Extend is used to extend an already created false signal suppression This is useful if a false signal suppression was carried o...

Страница 19: ...mm Cable entry NPT Blind plug M20 x 1 5 NPT Closing cap M20 x 1 5 NPT Plug options Supply and signal circuit only with low voltage M12 x 1 plug Indication circuit M12 x 1 plug Wire cross section sprin...

Страница 20: ...of delivery application practical use and operat ing conditions of the sensors and processing systems correspond to the information available at the time of printing Subject to change without prior n...