43
6 Set up with the display and adjustment module
MINITRAC 31 • 4 … 20 mA/HART - four-wire
40447-EN-130430
Peak values measured value:
Resetting of the parameter adjust-
ments in the menu item "
Setup
" to the default values of the respective
instrument. Order-specific settings remain but are not taken over into
the current parameters.
Peak values temperature:
Resetting of the measured min. and max.
temperatures to the actual measured value.
The following table shows the default values of the instrument. The
values apply for the application "
Level
". First of all you have to select
the application.
Depending on the instrument version, not all menu items may be
available or they may be differently assigned:
Menu
Menu item
Default value
Adjustment
Measurement loop name
Sensor
Isotope
Cs-137
Applications
Density
Background radiation
0 ct/s
Unit of the process value
g/cm
3
Temperature unit
° C
Adjustment min. process
value
0.500 g/cm
3
Adjustment max. process
value
1.500 g/cm
3
Inner diameter
0.20 m
Linearization
90000 ct/s and 0.500 g/cm
3
Damping
60 s
Real value correction
0
Current output mode
4 … 20 mA, < 3.6 mA
Current output Min./Max.
Min. current 3.8 mA, max. current 20.5 mA
X-ray alarm
Modulated measuring current
Reference value - Relay
None
Block operation
Released
Display
Language
Selected language
Displayed value
Pulse rate
Display unit
ct/s
Additional settings
HART mode
Standard
Address 0
With this function you can select the mode.
The sensor offers the HART modes standard and multidrop.
The mode 'Standard' with the fixed address 0 (factory setting) means
output of the measured value as 4 … 20 mA signal.
This parameter is described in the operating instructions manual
"
Display and adjustment module
".
Additional adjustments/
HART mode