38
6 Set up with the display and adjustment module
MINITRAC 31 • 4 … 20 mA/HART - four-wire
40447-EN-130430
You can also delete individual linearization points. Enter the number
of the point you want to delete.
•
Linearization - Modify
You can also modify individual linearization points.
After editing, you have to activate the complete value pair so that the
linearization point will be effective.
You recognize active linearization points by a small square with a
cross next to the number of the linearization point.
In this menu item you can adjust the damping of the sensor. With
it you can suppress fluctuations in the measured value indication,
caused e.g. by an agitated product surface. This time can be between
1 and 1200 seconds. Keep in mind that also the reaction time in-
creases and the instrument reacts to quick level changes with a delay.
Generally a time of approximately 60 seconds is sufficient to smooth
the measured value indication.
With the setting "Automatic", the instrument itself calculates a suitable
damping on the basis of the adjustment and the measured value
changes. This setting is particularly suitable for application where fast
and slow level changes occur.
Setup/Damping