31
6 Set up with the display and adjustment module
MINITRAC 31 • 4 … 20 mA/HART - four-wire
40447-EN-130430
Additional settings
The following reset functions are available:
Basic adjustments:
Resetting of the parameter adjustmetns to
default values at the time of shipment. Order-specific settings will be
deleted.
Default settings:
Resetting of the parameter adjustment like under
"
Basic adjustment
". In addition, special parameters will be reset to
default values. Order-specific settings will not be deleted.
Peak values measured value:
Resetting of the parameter adjust-
ments in the menu item "
Setup
" to the default values of the respective
instrument. Order-specific settings remain but are not taken over into
the current parameters.
Peak values temperature:
Resetting of the measured min. and max.
temperatures to the actual measured value.
The following table shows the default values of the instrument. The
values apply for the application "
Level
". First of all you have to select
the application.
Depending on the instrument version, not all menu items may be
available or they may be differently assigned:
Menu
Menu item
Default value
Adjustment
Measurement loop name
Sensor
Isotope
Cs-137
Applications
Level
Background radiation
0 ct/s
Unit of the process value
m
Temperature unit
° C
Damping
60 s
Real value correction
0
Current output mode
4 … 20 mA, < 3.6 mA
Current output Min./Max.
Min. current 3.8 mA, max. current 20.5 mA
X-ray alarm
Modulated measuring current
Reference value - Relay
None
Block operation
Released
Display
Language
Selected language
Displayed value
Pulse rate
Display unit
ct/s
Additional settings
Temperature unit
°C
Linearization curve
Empty
HART mode
Standard
Address 0
Additional adjustments
- Reset