16
Install Transmitter
A Transmitter/Battery Pack pair is required for each device that will be monitored by the ATG. Follow the
steps below to install the Transmitter system within a sump. Refer to the 577014–482 TLS–RF Series 4
Wireless System Site Prep and Installation Manual for the steps to install the Transmitter system within a
dispenser pan.
When replacing the Transmitter cover onto the housing verify the following to ensure a watertight seal:
• Retaining washers are assembled to the screws.
• Gaps don’t exist between the cover, washers, and enclosure.
• Gasket is properly seated within the cover.
• Screws are tightened to between 14 and 18 inch–pounds.
1.
Attach the two 12.7 mm [1/2”] conduit clamps to the two riser hangers from the installation
hardware kit (330020–528 or 330020–835) (50.8 mm [2”] or 101.6 mm [4”], as required) as
shown in Figure 13. Orient riser hangers so holes for 12.7mm (1/2”) clamps (Item 4) are vertically
aligned.
Figure 13. Attaching 12.7 mm [1/2”] Conduit Clamps to Riser Hangers
LEGEND FOR NUMBERED
BOXES IN Figure 13
1. 50.8 mm or 101.6 mm riser
hanger [as required]– 2 places
2. 6.35mm–20 (1/4”–20) hex nut –
2 places
3. Bolt provided with riser hanger –
2 places
4. 12.7mm (1/2”) metal conduit
clamp (bolt not shown) – 2
places
5. 6.35mm–20 x 12.7mm (1/4”–20
x 1/2”) hex head bolt – 2 places
6. Nut provided with riser hanger –
2 places
6
2
3
5
4
1