RS-232 Commands
Function Code: 201
29
Function Code: 201
Function Type:
In-Tank Inventory Report
Version 1
Command Format:
Display:
<SOH>I201TT
Computer:
<SOH>i201TT
Typical Response Message, Display Format:
<SOH>
I201TT
TANK
VOLUME
TC VOLUME
HEIGHT
WATER
TEMP
1
5329
5413
48.9
0.0
37.3
<ETX>
Typical Response Message, Computer Format:
<SOH>i201TT0000000000TT0ssssNNFFFFFFFF...
TTpssssNNFFFFFFFF...&&CCCC<ETX>
Notes:
1. 0000000000 -
Unused
2.
TT -
Tank Number (Decimal, 00 = all)
3.
0 -
Unused
4.
ssss -
Tank Status Bits:
Bit 1 - (LSB) Unused
Bit 2 - Unused
Bit 3 - Invalid Fuel Height Alarm (MAG Probes Only)
Bit 4-16 - Unused
5.
NN -
Number of eight character Data Fields to follow (Hex)
6.
FFFFFFFF -
ASCII Hex IEEE float:
1. Volume
2. TC Volume
3. Ullage
4. Height
5. Water
6. Temperature
7. Water Volume
7.
&& -
Data Termination Flag
8.
CCCC -
Message Checksum