Site Considerations
Selecting a Console Location
6
Select a mounting location on the inside of any building. The console must be protected from severe vibration,
extremes in temperature and humidity, rain, and other conditions that could harm computerized electronic
equipment.
The equipment is designed to operate safely under the following range of conditions:
•
Temperature range 0 to 40°C - ( storage temperature range of -40 to +74°C).
•
A maximum relative humidity of 95% RH (non-condensing) at temperatures up to 40°C.
•
Console may be powered by either 120 or 240 Vac. A switchmode power supply automatically detects the
input voltage (no jumpers required).
•
Main supply voltage fluctuations not exceeding ±10%.
•
Pollution Degree Category 2.
•
Installation Category II.
Important! Consoles must be installed within the interior of buildings. They are not suitable for any external
location.
Ensure that the console is located where neither the console nor its associated cabling will be damaged by doors,
furniture, barrows, etc. Consider the ease of routing wiring, ducting, and probe cables to the console. Check that
the mounting surface is strong enough to support the console’s weight of about 4 pounds.
Important! If the unit requires cleaning, do not use any liquids, wipe only with a clean, dry cloth.