5
Introduction
Gasoline Pump and Line Requirements
Gasoline Pump and Line Requirements
All gasoline STPs (Pumps) have the following setup requirements via Setup> Pump and Lines. Each gasoline tank
must be assigned to a pump via Setup> Pump and Lines> Pumps. The created pump must then be assigned to a
line via Setup> Pump and Lines> Lines. These pump/line assignments are required to properly setup the ISD shut
down requirements.
ISD Shutdown Requirements
For ISD on the TLS-450PLUS, the gasoline lines must be able to be shutdown for required ISD Site/Hose alarms.
Dispenser relays may be used to shut down gasoline dispensers for Hose alarms.
The TLS 450 setup requires at least one Line to shutdown for required ISD alarms, otherwise the ‘Missing Relay’
warning will post. Ensure that all gasoline Lines/Hoses are configured to shutdown on required ISD Site/Hose
alarms. Hoses may also be shutdown using dispenser relays. ISD shutdown requirements is accomplished using
Automatic Events Setup. Refer to Table 3 for required ISD Shutdown alarms.
Table 3: ISD Shutdown Alarms
Alarm
Days to Failure
Shutdown Required
ISD DEGRD PRES WARN
30
Optional
ISD DEGRD PRES FAIL
-
Yes
ISD GROSS PRES WARN
7
Optional
ISD GROSS PRES FAIL
-
Yes
ISD VAPOR LEAK WARN
7
Optional
ISD VAPOR LEAK FAIL
-
Yes
ISD SENSOR OUT WARN
7
Optional
ISD SENSOR OUT FAIL
-
Optional
1
ISD SETUP WARN
7
Optional
ISD SETUP FAIL
-
Optional
1
hnn: DEGRD COLLECT WARN
7
Optional
hnn: DEGRD COLLECT FAIL
-
Yes
hnn: GROSS COLLECT WARN
1
Optional
hnn: GROSS COLLECT FAIL
-
Yes
hnn: FLOW COLLECT WARN
1
Optional
hnn: FLOW COLLECT FAIL
-
Yes
ISD VP STATUS WARN
1
Optional
ISD VP STATUS FAIL
-
Yes
ISD VP PRES WARN
1
Optional
ISD VP PRES FAIL
-
Yes
Assist EVR Systems Only
Balance EVR Systems Only
Vapor Processor Required
1
Shutdown is optional for these alarm conditions and it is recommended that they be enabled.
Содержание TLS-450PLUS
Страница 46: ...38 Setup Single CARB EVR ISD Setup Printout Figure 55 Example EVR ISD Setup Printout...
Страница 98: ......