Setup
Automatic Events: (Pump Mode = External Pump Control)
ii. Select LINE OUT for the appropriate Line as a Trigger
Figure 52. Example Device Task – External Pump Control - LINE OUT (No Dispenser Relay(s))
4. Dispenser Relay Shutdown option: For each Dispenser Relay:
a. Via: Setup > Devices > Relay:
i. Configure/Enable Relay
ii. Set the Type to Standard
b. Via: Setup > Automatic Events > Device Tasks:
Add a task for each Dispenser Relay:
i. Set the Device to the Relay
ii. Select each required Hose Alarm for the appropriate Gasoline Hose(s) as a Trigger
Figure 53. Example Device Tasks – External Pump Control (With Dispenser Relay(s))