15
MAG-XL Flex Probe Installation
Pre-Installation Component Setup and Functional Check
Follow the steps in the ‘Pre-Installation Component Setup and Functional Check’ section of the TLS RF Wireless 2
System (W2) Installation and Maintenance Guide (577013-964) to verify the Wireless System’s component
functionality.
Assemble the Battery Pack Mounting Bracket
PROBE INSTALLATION - MANWAY 4-INCH RISER PIPE
1.
Connect the two 4-inch conduit hangers (item 1) from the installation kit to the battery mounting bracket (item
4) as shown in Figure 6.
2.
Insert the bolt/nut pairs (items 2 and 3 in the figure) in each hanger as shown, but do not tighten.
3.
Tighten the two bolt/nut pairs (items 2 and 5 in the figure) securing the mounting bracket to the conduit hang-
ers.
4.
Get the customer supplied outdoor junction box. Get the customer supplied 3/4” x 1/2” reducing bushing.
Apply pipe thread sealant or PTFE tape to its threads and screw it into the top threaded opening of the junc-
tion box until tight.
5.
Get the 1/2” nipple from the probe installation kit. Apply pipe thread sealant or PTFE tape to its threads and
screw it in the reducing bushing until tight.
6.
Get the 1/2” brass hex adapter from the probe installation kit and after orienting the embossed arrow down,
apply pipe thread sealant or PTFE tape to its threads and screw it onto the 1/2” nipple until tight.
7.
Take the battery support assembly, the junction box/conduit assembly and the transmitter to the top of the tank
for final assembly.
PROBE INSTALLATION - TOP OF TANK 2-INCH PIPE OPENING
1.
Connect the two 2-inch conduit hangers (item 1) from the installation kit to the battery mounting bracket (item
4) as shown in Figure 6.
2.
Insert the bolt/nut pairs (items 2 and 3 in the figure) in each hanger as shown, but do not tighten.
3.
Tighten the two bolt/nut pairs (items 2 and 5 in the figure) securing the mounting bracket to the conduit hang-
ers.