MAG-XL Flex Probe Installation
Connecting MAG-XL Flex Probe Wiring
23
Figure 14. Installing TLS XL-Transmitter - tank 2-inch pipe fitting
Connecting MAG-XL Flex Probe Wiring
1.
Strip back the probe cable jacket and wires as shown in Figure 16.
2.
Attach the three MAG-XL Flex Probe cable wires to the PROBE terminal block (red to P, white to D and black
to G) (see item 1 in Figure 16).
3.
Making sure the battery cable is not connected to the battery pack, attach the battery pack/dc power cable to
the BATTERY terminal block (white to +IN and black to -IN) as shown in Figure 16.
Hand tighten the battery cable entry cord grip nut to prevent water entry!
LEGEND FOR NUMBERED BOXES IN Figure 13
1.
2” - 3/4” Adapter/Reducer
2.
Single-gang box from BELL outdoor, P/N 5321-0, or equivalent
with 3/4” x 1/2” NPT reducing bushing (customer supplied)
3.
Battery pack
4.
1/2” conduit, min. 6” length (customer supplied)
5.
1/2” brass hex adapter
6.
TLS XL-Transmitter
7.
Probe cable
8.
3/4” NPT probe threaded fitting
6
3
4
1
2
7
8
972-11.eps
5
CAUTION! TIGHTEN
CORD GRIPS TO PREVENT
WATER INGRESS!