IQ Control Box Installation and Owner’s Manual
IQ Manifold Control Information
5
becomes a point where the power drawn by the motor reaches its threshold. At this point the IQ box sends a
request for the next device in line to turn on in conjunction with itself. So, in this case Unit 2 will always turn on
next. Then when Unit 2 is running and more flow is needed it, Unit 3 will be the next to turn on. Lastly Unit 4 will
turn on. All pumps once turned on continue to stay on until the active hook signal is disabled. Once the hook signal
is disabled, they will all turn off. On the next hook signal the next unit in line will turn on. So, if 1 turned on first, 2
will be the first to accept the hook request on the next cycle. On the next cycle Unit 3 will be the first to turn on
and so forth. If it is the last Unit in the setup, it will pass the token back to Unit 1.