Appendix A
Diagnostics
A-15
Diagnostics
STP Status
You can view the status of each STP by navigating to
Diagnostics > Pump Controller > Communications
(see
Figure A-13. IQ Control Box Communications Status Screen
The normal operating voltage range for Red Jacket pumps is 200 to 250 Vac.
Alarms
Table A-4 lists the IQ Control Box Diagnostic alarms. Reference “Description of Fault Conditions” on page 17.
Table A-4. IQ Control Box Diagnostic Alarms
TLS Alarm
Pump Controller
Comm Screen
PC Status
IQ Control Box
Red LED Indicator
Cause
1
UNCALIBRATED
Uncalibrated
DEVICE IS UNCALIBRATED (1 Flash)
Uncalibrated IQ Control Box
OVERLOAD
Overload
OVERCURRENT FAULT (2 Flashes)
Over-Current Condition, e.g., Locked Rotor
– Pump Shutoff
DRY RUN
Dry Run
DRY RUN FAULT (3 Flashes)
Dry Run Detected – Pump Shutoff
UNDERLOAD
Underload
LOW AC CURRENT (4 Flashes)
Low AC Current
NETWORK
ERROR
Network Error
SETUP/COMMUNICATION ERROR
(5 Flashes)
Setup/Communication Error
UNDER VOLTAGE
Under Voltage
LOW LINE VOLTAGE (6 Flashes)
Low Line Voltage < 200Vac
BYPASSED
Bypassed
BYPASS MODE (7 Flashes)
IQ Control Box Normal/Bypass jumper left
in Bypass position
EXTENDED RUN
Extended Run
EXTENDED RUN (8 Flashes)
Extended Run Condition