Installing the Dispenser Pan Sensor
Dispenser Control Interface Wiring
7
Figure 2.
Dispenser Control Interface WARNING Label
7.
Route and secure protective Dispenser Control Interface cable with plastic wire
ties, supplied in the wiring kit. The cable may be tied to the plumbing and
structural members of the pump frame.
Cable must not be tied to sharp edges or
moving parts.
Any remaining slack may be looped and tied at a convenient point.
8.
Use wire nuts or other approved connectors for junction box connections to red,
black, and white wires of the Dispenser Control Interface. See Figure 3 on page 8.
Dispenser Control Interface Wiring
1.
Wire Dispenser Control Interface to dispenser according to the appropriate Dis-
penser Control Interface wiring diagram (Figure 3 on page 8, Figure 4 on page 8,
Figure 5 on page 9, Figure 6 on page 10, Figure 7 on page 11, Figure 8 on page 12,
or Figure 9 on page 13).
WARNING
To maintain intrinsic safety, route cable in accordance with Article 504
of the National Electrical Code.
TO MAINTAIN INTRINSIC SAFETY,
DO NOT INSTALL THESE WIRES
NEAR WIRING FOR ANY OTHER
CIRCUIT
PT. NO.326429-001
WARNING
WARNING
Be sure no unplugged openings exist in the junction box. Close or
plug any openings before proceeding. Failure to comply with this
warning may result in personal injury, property loss, and equipment
damage.