Dispenser Pan Sensor Installation
Installing the Dispenser Pan Sensor
14
Dispenser Pan Sensor Installation
To install any of the Dispenser Pan Sensors:
Important
☞
Do not install the dispenser pan sensor if there is any liquid in the dispenser pan.
Failure to comply can result in equipment damage or undetected potential
environmental and health hazards.
1.
Make sure no liquid exists in the dispenser pan.
Important
☞
Before removing an existing dispenser pan sensor be sure to mark field wires in the
junction box to maintain correct sensor wiring polarity during the replacement
procedure.
2.
Choose a location in the dispenser pan following these guidelines to help insure
proper operation of the sensor:
❑
The sensor should rest in the cup or lowest point of the dispenser pan.
❑
The sensor should be mounted in a true vertical position, where it can be pulled
straight out for future service or replacement.
❑
If installing the sensor into a backfilled pan, it is recommended that a screen
tube be used for ease of removal and reinstallation.
Refer to Figure 10, “Typical Dispenser Pan Sensor Installation,” on page 15, or
Figure 11, “Typical Dispenser Pan Sensor Installation in a Dispenser Sump,” on
page 15.
WARNING
This device is installed in equipment where potentially lethal voltages
may exist.
Electrical shock resulting in serious injury or death may result if
power is on during installation and the device is improperly installed.
Before installing this device, turn off power to the system.
OFF