TCY-T0121 Intelligent Compact Controller
Version: 2004-07
Page 7/12
Error messages
The TCY may display the following error condition:
Err1:
Temperature sensor faulty. The connection to the temperature sensor may be interrupted, the DIP switch
settings may be incorrect or the temperature sensor is damaged. As a consequence all the outputs tied to
this sensor are switched off.
Setting of parameters
The TCY is an
intelligent
controller and can be adapted to fit perfect into your application. The control operation is
defined by parameters. The parameters are set during operation by using the standard operation terminal.
The parameters are password protected. There are two levels of parameters: User operation parameters for access
control settings and Expert parameters for control functions and unit setup. The passwords for user levels and expert
levels are different. Only control experts should be given the control parameter password.
The parameters can be changed as follows:
1. Press UP and DOWN button simultaneously for three seconds. The display will indicate CODE.
2. Select a password using UP or DOWN buttons. Dial
09
in order to get access to the user parameters,
241
for EXPERT mode. Press OPTION after selecting the correct password.
3. Once logged in, the parameter is displayed immediately
4. Select the parameters with the UP/DOWN keys. Change a parameter by pressing the OPTION key. The MIN
and MAX symbols show up and indicate that the parameter may be modified now. Use UP and DOWN key to
adjust the value.
5. After you are done, press OPTION or POWER in order to return to the parameter selection level.
6. Press the POWER key again so as to leave the menu. The unit will return to normal operation if no key is
pressed for more than 5 minutes.
User Parameters
Parameter
Description
Setting Range
Factory Setting
UP 00
Choose if end user is allowed to change operation modes,
OFF = Disabled, ON = Enabled
ON, OFF
ON
UP 01
Choose if the end user is allowed to change set points
OFF = Disabled, ON = Enabled
ON, OFF
ON
UP 02
Choose if the end user is allowed to override secondary setpoint in
cascade control OFF = Disabled, ON = Enabled
ON, OFF
ON
UP 03
Heat/Cool change Enable, Choose if the end user is allowed to change
heating/cooling mode. OFF = Disabled, ON Enabled
ON, OFF
ON
UP 04
Access Time programs, Choose if the end user can change time
programs. OFF = Disabled, ON = Enabled
ON, OFF
ON
UP 05
State after power failure:
0 = Switched off, 1 = Switched on, 2 = state before power failure
0, 1, 2
2
UP 06
Frost protection enable/disable
ON, OFF
ON
UP 07
Enable standby functionality
ON, OFF
ON
UP 08
Standby temperature shift
0…10.0K
5.0 K
UP 09
Limit output while unit is in Standby mode
0…100%
100%
UP 10
Define a minimum temperature limit, if you do not want the end user to
select 10C/50F as a set point.
-40…214
10C, 50F
UP 11
Define a maximum temperature limit, if you do not want the end user to
select 34C/98F as a set point.
-39…215
34C, 98F
UP 12
Calibration value of temperature sensor.
-10.0…10.0
~
UP 13
Celsius or Fahrenheit, Select ON for Fahrenheit, OFF for Celsius
ON, OFF
OFF (Celsius)
UP 14
Standby shift for Universal Setpoint
Range is according to input selection
Acc. Input range
0
UP 15
Calibration value for analog input. Range is in % of input signal.
-10…10%
0
UP 16
User Display: Indicate a designated value on LCD display while no key
is pressed
ON, OFF
ON
Select contents of Large LCD display in standard mode:
UP 17
00 = OFF
01 = Setpoint Temperature HC
02 = Setpoint Universal 1
03 = Temperature sensor
04 = Analog Input
05 = Output Temperature Pi
06 = Output Universal PI Reverse
07 = Output Universal PI Direct
08 = Floating Output Position
09 = Clock
0…13
05
UP 18
Select contents of small LCD display in standard mode
0…13
01
Select contents of vertical LCD display in standard mode
UP 19
00 = OFF
01 = Analog Input
02 = Output temperature PI
03 = Output universal PI reverse
04 = Output universal PI direct
05 = Floating Output Position
0…6
03