TCY-T0121 Intelligent Compact Controller

 

  

Version: 2004-07 

[email protected] 

Page 6/12 

Operation of the Terminal Unit 

Switching ON 

The unit is switched on by pressing the POWER button. It will start up in comfort mode. 

Changing between COMFORT and STANDBY 

Pressing the POWER button for less than 2 seconds toggles between STANDBY and COMFORT modes. Standby mode 

may be disabled with UP07.  

Switching OFF 

Pressing the POWER button for more than 2 seconds, will switch the unit off. OFF and current time will be displayed 

in the LCD for the deluxe unit. Current temperature and OFF is displayed for the basic unit. 

Standard display 

Standard display is enabled with parameter UP-17. This display mode is active if no UP/DOWN or OPTION key has 

been pressed during the previous 30 seconds.  The contents of the large and small digits may be chosen with 

parameters UP-18 to UP-20.  
Should Standard display be disabled, the selected loop setpoint will be displayed in the small digits, the associated 

input in the large digits and the output in the right hand scale.  

Changing of setpoints 

Step through the enabled control loops by repeatedly pressing the OPTION button. The large digits indicate the loop 

action (reverse/direct) for 2 seconds and afterwards the input value of the activated control loop. The output value is 

indicated in the scale. The small digits show the setpoint of this loop. Pressing directly UP/DOWN will select the first 

control loop enabled in this order: Temperature PI, Universal reverse acting, and universal direct acting.  
Select the desired control loop with the OPTION button and change the setpoint with the UP/DOWN buttons.  
Changing of setpoints may be disabled with UP-01. 

Override of secondary setpoint in cascade control 

In case cascade control is active (for example VAV control), it is possible to override the primary loop and manually 

set the setpoint of the secondary loop. While the secondary loop is displayed change the setpoint with UP/DOWN 

keys. The manual indication will show on the display. (For VAV this would mean the loop is now changed to CAV. 

This would be especially useful while tuning the VAV system) Pressing the OPTION key to move back to the 

temperature loop will cancel manual override.  
Manual override may be disabled with UP-02. 

Schedule control of digital outputs 

This feature is available if schedule control for a digital output is enabled (OP7/8). Select the digital output by 

repeatedly pressing the OPTION button until DO1 or DO2 is displayed in the large LCD digits. Pressing UP/DOWN 

steps through following modes ON, OFF, PROG, selecting ON or OFF sets the output in manual mode, the manual 

symbol is displayed. Pressing the OPTION button for more than 3 seconds starts the schedule mode. The schedule 

operation for the DO is similar to general time scheduling (see below). A total of 2 programs with each 4 switc hing 

times for each DO are available. The DO will be switched off, if the operation mode is OFF.  

Accessing advanced settings 

Pressing the option button for more than three seconds will start the advanced setup menu. The large LCD digits 

display SEL. The advanced setup menu accesses these settings: Clock setup, Time schedules, Heat / Cool change for 

2 pipe systems. The menu may be left by pressing the POWER key or by not pressing a key for more than 2 minutes.  

• 

Deluxe only: Clock Setup. The current time is displayed in the small digits. Pressing the OPTION button will 

enter the clock setup. The minutes are blinking and may be changed with the UP/DOWN keys. Pressing 

OPTION saves the minutes and steps to the hours. The hours are blinking. Pressing the OPTION key again 

will step to the weekday. DAY1-7 is displayed. Day 1 stands for the first working day (Monday) of a 5-day 

working week. (See schedule). Select the day according to current weekday. Pressing Option again saves 

the settings and moves back to the SELECT menu.  

• 

Deluxe only: Time Schedules: press the option key while Pro is displayed in the small digits. Pro1 is now 

shown in the large digits, while the number 1 is blinking. Select time program by using UP/DOWN keys. 

There is a total of 4 time programs with each 4 switching times available. Enter the time program by 

pressing the OPTION key. 
1.  Activate or deactivate the time program. Choose ON or OFF with the UP/DOWN keys 
2.  Select weekday(s) = d1-7, d1-5, d6-7, day1, day2, day3, day4, day5, day6, day7 
3.  The next steps define the switching mode and time. The bar indicator on the right side shows 

programming progress. There are four switch times for each program.  

Select desired operation mode. (no, ON, Eco, OFF), press OPTION to continue 

§ 

no = disables this time schedule 

§ 

On = sets operation mode to On and Comfort 

§ 

Eco = sets operation mode to On and Standby 

§ 

OFF = switches unit Off 

Select switching time 00:00 to 23:45 in 15-minute steps, press OPTION to continue. 

Repeat above two steps for each switching time.  

Access to time schedules may be disabled with UP-04 

• 

Heat / Cool change. Pressing UP or DOWN toggles Heating – Cooling mode. (For two pipe systems only) 

Access to Heat/Cool change may be disabled with UP-03 

Содержание TCY-T0121

Страница 1: ...mation system Internal or external passive temperature sensor selectable by switch Transformation of display value according to analog sensor range Password protected programmable user and control parameters Display and operation unit available in various designs and materials Applications Air Only Systems Constant or Variable Air Volume systems for single or dual duct systems with options of o up...

Страница 2: ...set time of Analog loop integral Tn is the time needed for the integral to run from 0 to 100 The range is 0 5 30 min The setting depends on the control application For temperature control of a medium sized room a setting of 5 10 minutes is appropriate For pressure control on a VAV box a value of 3 minutes is recommended depending on the speed of the actuator T Room Temperature WH Setpoint Heating ...

Страница 3: ...olved It should be at least 1 2 times the reaction time of the control cycle XU Input signal Xp1 Proportional Band reverse acting YU Output signal of universal loop Xp2 Proportional Band direct acting wR wD Reverse Direct Setpoint Tn Integral Reset Time XDZ Dead Zone Span 2 point control This control mode is enabled by parameter 1U 08 for the reverse signal and 1U 09 for the direct signal 2 point ...

Страница 4: ...ching outputs DO1 and DO2 are factory assigned as floating output They may be assigned as digital outputs using OP 07 to OP 08 The digital outputs may be used either as switching outputs for Temperature or Universal ON OFF modules Each output needs to be assigned to a control loop See parameter OP section for details Time schedule on digital outputs The digital outputs may be used with an individu...

Страница 5: ...hes the unit off UP and DOWN buttons change setpoints and parameters OPTION button used for accessing different control modes and advanced setup Acts as Enter in parameter changing menu Operation Modes Comfort The unit is in full operation mode All the control functions are operating according to their setpoints The unit displays occupied mode Standby The setpoints are shifted according to paramet...

Страница 6: ...eatedly pressing the OPTION button until DO1 or DO2 is displayed in the large LCD digits Pressing UP DOWN steps through following modes ON OFF PROG selecting ON or OFF sets the output in manual mode the manual symbol is displayed Pressing the OPTION button for more than 3 seconds starts the schedule mode The schedule operation for the DO is similar to general time scheduling see below A total of 2...

Страница 7: ... user is allowed to change operation modes OFF Disabled ON Enabled ON OFF ON UP 01 Choose if the end user is allowed to change set points OFF Disabled ON Enabled ON OFF ON UP 02 Choose if the end user is allowed to override secondary setpoint in cascade control OFF Disabled ON Enabled ON OFF ON UP 03 Heat Cool change Enable Choose if the end user is allowed to change heating cooling mode OFF Disab...

Страница 8: ...erature loop is setpoint of analog loop ON Cascade Active OFF no cascade ON OFF OFF 1U 01 Dead zone for Universal Loop range acc to input Acc Input 0 1U 02 Enable PI Reverse Loop ON OFF OFF 1U 03 Enable PI Direct Loop ON OFF OFF 1U 04 P Band or Switching Span reverse acting Range according to input Selecting 0 disables the P part Acc input 10 1U 05 P Band or Switching Span direct acting Range acco...

Страница 9: ...55 50 Mechanical Design and installation The unit consists of three parts The mounting plate the power case and the front part consisting of a module and an outside frame The outside frame may be replaced with a special design based on interior design and taste of the end user Please talk to your dealer regarding different designs materials and colors available Installation 1 Arrange the wires to ...

Страница 10: ...puts AC Voltage Insulation resistance Optical coupled TRIAC DO1 DO2 24V 220V AC 1A max AC2500 V RMS acc to EN 60 730 1 complying with UL standards File ref E81734 Display LCD Actual values and setpoint Resolution value 1000 Resolution value 1000 Digital Signals 4 digits 0 1 1 ON OFF Parameters For details of control parameters see parameter section Environment Ambient Temperature 10 to 50 C acc IE...

Страница 11: ... Analog Input Output Ground 2 Power Supply 24V AC 3 Digital Output 1 4 Digital Output 2 5 Temperature sensor NTC 6 Temperature sensor NTC 7 Analog Output 1 0 10V or 0 20mA 8 Analog Input 1 0 10V 0 5V or 0 20mA The switch for internal external temperature setting is located on the back of the operation terminal AI1 JP2 0 10V DC 0 5V DC 0 20 mA AO1 JP1 0 10V DC 0 20 mA 1 4 3 4 2 3 1 2 2 3 1 0V AC GN...

Страница 12: ...ion advice or training in how to use our products The target is to optimize your benefits The only thing you need to do is Talk to us Quality Support Partnership Our Offer Your Call Tel 86 10 6786 9251 3 Fax 86 10 6786 9256 Email info vectorcontrols com VECTOR CONTROLS LTD 23 Xi Huan Bei Road Room 208 Hua Teng Fa Zhan Building Yi Zhuang Beijing 100176 PRC VECTOR ...

Отзывы: