TCY-T0121 Intelligent Compact Controller
Version: 2004-07
Page 10/12
Configuration of controller
Proceed in the following steps in order to adapt the controller to its application:
1. Set jumpers for inputs and outputs
2. Connect power supply
3. Program input parameters (IP)
4. Program control parameters (HC or 1U)
5. Program output parameters (OP)
6. Set user settings (UP)
7. Connect inputs and outputs.
8. Test function of unit
Technical Specification
Power Supply
Operating Voltage
24 V AC 50/60 Hz ± 10%
Power Consumption
Max 4 VA
Electrical Connection
Terminal Connectors
Battery (deluxe version)
Lithium CR1220 3V
Signal Inputs
Analog Inputs
Input Signal
Resolution
Accuracy
AI1
DC 0-10V, DC 0-5V or 0…20mA
39 mV, 0.078 mA
±
2%
Temperature Inputs
Range
Resolution
Accuracy
Type
RT
-40…140 °C
0.1 K
0.5 K
NTC 10KO, 25 °C, B25/50:3950 Acc: 1%
Signal Outputs
Analog Outputs
Output Signal
Resolution
Accuracy
Maximum Load
AO1
DC 0-10V or 0…20mA
39 mV, 0.078 mA
±
2%
20 mA, 500
V
Digital Switching Outputs
AC Voltage
Insulation resistance
Optical coupled TRIAC
DO1, DO2
24V – 220V AC 1A max.
AC2500 V RMS acc. to EN 60 730-1,
complying with UL standards File ref E81734
Display (LCD)
Actual values and setpoint
Resolution value < 1000
Resolution value > 1000
Digital Signals
4 digits
0.1
1
ON, OFF
Parameters
For details of control parameters see parameter section
Environment
Ambient Temperature
-10 to 50°C acc IEC 721-3-3 (14 to 122 °F)
Operation
Climatic Conditions
Temperature
Humidity
To IEC 721-3-3
class 3 K5
0…50°C
<95% r.h.
Transport & Storage
Climatic Conditions
Temperature
Humidity
Mechanical Conditions
To IEC 721-3-2 and IEC 721-3-1
class 3 K3 and class 1 K3
-25…70°C
<95% r.h.
class 2M2
Standards
conform according to
EMC Standard
EMEI Standard
89/336/EEC
73/23/EEC
Product standards
Automatic electrical controls for
household and similar use
Special requirement on
temperature dependent controls
EN 60 730 –1
EN 60 730 – 2 - 9
Electromagnetic compatibility
Emissions
Immunity
EN 50 081-1
EN 50 082-1
Pollution Class
Normal acc. to EN 60 730
Degree of Protection
IP30 to EN 60 529
Safety Class
III
General
Dimensions
Front part: 21 x 88 x 88 (H x W x D)
Power case: 30 x 50 x 60
Weight (including package)
80 g