background image

 

 

 

TCY-T0121 Intelligent Compact Controller

 

  

Version: 2004-07 

[email protected] 

Page 4/12 

Analog Inputs: 

The analog input signals may be configured with jumpers to 0-10V, 0-5V and 4-20 mA. The jumpers are located just 

behind the terminal connector of each input. The drawings below indicate the jumper placement for each signal type. 

The factory setting is 0-10 VDC. 

The range of the input signal can be specified in software by 

setting a minimum and a maximum limit. The limits are in 

percent of the full range 
The display value of the input signal may be specified. For 

example a pressure sensor has a 4-20 mA output and a 

pressure range of 0 – 200 Pa. It is possible to transform the 

input signal into a different dimension by setting the minimum and maximum transformation value in the input 

configuration setup. In our example the display will read 100 for a 12 mA signal.  
Averaging function: Some sensor signals (for example air flow sensors) tend to fluctuate. The controller measures 

every second the signal inputs. Select how many values should be used to calculate the averaging signal, which will 

be used as control input. (Too many samples for an averaging signal may increase the swinging te ndency, increase 

reset time on PI signals in this case) 

Output Configuration 

Analog Output 

The analog output may be configured with jumpers for 0-10 VDC or 0-20 mA control signals. The jumpers are 

located behind the terminal connector of the respective analog output. See table below for jumper placement. The 

factory setting is to 0-10 VDC. 

The signal range is specified in software by setting a 

minimum and a maximum limit.  
Each output may be assigned to a control loop, set to manual 

or serve as a temperature feedback of the internal 

temperature sensor. See parameter OP section for details:  
Enabling OP-03 changes DO1 and DO1 into a floating output for a PI loop. In this case the running time of the 

actuator needs to be specified. Running time is defined as the time required for the actuator to run from fully open to 

fully closed or vise versa. Note that it is recommended to use only actuators with a fixed running time.  
Once fully open or fully closed the running time for the actuator is extended for 5 minutes.  

If OP-03 is in the OFF position, DO1 and DO2 may be used as switching outputs for an ON/OFF control module.  

Digital Outputs 

The switching outputs DO1 and DO2 are factory assigned as floating output. They may be assigned as digital outputs 

using OP-07 to OP-08. The digital outputs may be used either as switching outputs for Temperature or Universal 

ON/OFF modules. Each output needs to be assigned to a control loop. See parameter OP section for details. 

Time schedule on digital outputs 

The digital outputs may be used with an individual schedule. Select option 7 at the OP7/8 parameter. There are two 

programs with each 4 switching times available. Program 4 and 5 applies for DO1 and Program 6 and 7 for DO2.  
Schedule for Digital outputs will only operate if floating output is disabled (OP03 = OFF). 

Switching difference on floating output 

The controller moves the actuator to the calculated position by either opening or closing the actuator. The actuator 

should not be moved for every little change in position, since this would reduce the lifetime of the actuator.  
OP-06: Switching difference: The actuator will only move, if the difference to the current actuator position is larger 

than this parameter. 

Power Failure 

All the parameters and set points are memorized and don’t need to be reentered. Depending on UP04 the unit will 

remain switched off, switch on automatically or return to the operation mode it was in before the power failure. 
Deluxe version only: Timer operation and daytime setting will be retained. (Battery factory mounted battery life is 2 

years).   

Frost Protection 

The controller will enter frost protection mode if the room temperature drops below 5°C (41°F). All heating outputs 

will be fully opened. Frost protection mode will be left once the temperature reaches 10°C  (50°F). Frost protection 

display will remain until a button is pressed. Frost protection can be enabled/disabled using user parameter UP-06. 
Note: Frost protection uses the NTC temperature input. Analog sensors set as temperature sensor with 1U11 will not 

be able to trigger frost protection 

Clock Operation (Deluxe Version) 

TLCY contains a battery backed quartz clock. Up to 16 mode changes (STANDBY, COMFORT, OFF) based on 

weekdays and time may be programmed. See chapter operation on how to program and assign switch times to the 

corresponding loops.  
A blinking clock indicates that the battery is empty and needs to be replaced. The time needs to be set in order to 

allow time programs to operate. See chapter operation, advanced settings for instructions on how to set the time. 

Signal Type 

Jumper selection 

0 – 10 VDC  

 

(1-4) 

0 –5 VDC     

 

(3-4) 

0 – 20 mA DC 

 

(2-3) 

Signal Type 

Jumper selection 

0 – 10 VDC 

(1-2) 

0 – 20 mA DC 

(2-3) 

Содержание TCY-T0121

Страница 1: ...mation system Internal or external passive temperature sensor selectable by switch Transformation of display value according to analog sensor range Password protected programmable user and control parameters Display and operation unit available in various designs and materials Applications Air Only Systems Constant or Variable Air Volume systems for single or dual duct systems with options of o up...

Страница 2: ...set time of Analog loop integral Tn is the time needed for the integral to run from 0 to 100 The range is 0 5 30 min The setting depends on the control application For temperature control of a medium sized room a setting of 5 10 minutes is appropriate For pressure control on a VAV box a value of 3 minutes is recommended depending on the speed of the actuator T Room Temperature WH Setpoint Heating ...

Страница 3: ...olved It should be at least 1 2 times the reaction time of the control cycle XU Input signal Xp1 Proportional Band reverse acting YU Output signal of universal loop Xp2 Proportional Band direct acting wR wD Reverse Direct Setpoint Tn Integral Reset Time XDZ Dead Zone Span 2 point control This control mode is enabled by parameter 1U 08 for the reverse signal and 1U 09 for the direct signal 2 point ...

Страница 4: ...ching outputs DO1 and DO2 are factory assigned as floating output They may be assigned as digital outputs using OP 07 to OP 08 The digital outputs may be used either as switching outputs for Temperature or Universal ON OFF modules Each output needs to be assigned to a control loop See parameter OP section for details Time schedule on digital outputs The digital outputs may be used with an individu...

Страница 5: ...hes the unit off UP and DOWN buttons change setpoints and parameters OPTION button used for accessing different control modes and advanced setup Acts as Enter in parameter changing menu Operation Modes Comfort The unit is in full operation mode All the control functions are operating according to their setpoints The unit displays occupied mode Standby The setpoints are shifted according to paramet...

Страница 6: ...eatedly pressing the OPTION button until DO1 or DO2 is displayed in the large LCD digits Pressing UP DOWN steps through following modes ON OFF PROG selecting ON or OFF sets the output in manual mode the manual symbol is displayed Pressing the OPTION button for more than 3 seconds starts the schedule mode The schedule operation for the DO is similar to general time scheduling see below A total of 2...

Страница 7: ... user is allowed to change operation modes OFF Disabled ON Enabled ON OFF ON UP 01 Choose if the end user is allowed to change set points OFF Disabled ON Enabled ON OFF ON UP 02 Choose if the end user is allowed to override secondary setpoint in cascade control OFF Disabled ON Enabled ON OFF ON UP 03 Heat Cool change Enable Choose if the end user is allowed to change heating cooling mode OFF Disab...

Страница 8: ...erature loop is setpoint of analog loop ON Cascade Active OFF no cascade ON OFF OFF 1U 01 Dead zone for Universal Loop range acc to input Acc Input 0 1U 02 Enable PI Reverse Loop ON OFF OFF 1U 03 Enable PI Direct Loop ON OFF OFF 1U 04 P Band or Switching Span reverse acting Range according to input Selecting 0 disables the P part Acc input 10 1U 05 P Band or Switching Span direct acting Range acco...

Страница 9: ...55 50 Mechanical Design and installation The unit consists of three parts The mounting plate the power case and the front part consisting of a module and an outside frame The outside frame may be replaced with a special design based on interior design and taste of the end user Please talk to your dealer regarding different designs materials and colors available Installation 1 Arrange the wires to ...

Страница 10: ...puts AC Voltage Insulation resistance Optical coupled TRIAC DO1 DO2 24V 220V AC 1A max AC2500 V RMS acc to EN 60 730 1 complying with UL standards File ref E81734 Display LCD Actual values and setpoint Resolution value 1000 Resolution value 1000 Digital Signals 4 digits 0 1 1 ON OFF Parameters For details of control parameters see parameter section Environment Ambient Temperature 10 to 50 C acc IE...

Страница 11: ... Analog Input Output Ground 2 Power Supply 24V AC 3 Digital Output 1 4 Digital Output 2 5 Temperature sensor NTC 6 Temperature sensor NTC 7 Analog Output 1 0 10V or 0 20mA 8 Analog Input 1 0 10V 0 5V or 0 20mA The switch for internal external temperature setting is located on the back of the operation terminal AI1 JP2 0 10V DC 0 5V DC 0 20 mA AO1 JP1 0 10V DC 0 20 mA 1 4 3 4 2 3 1 2 2 3 1 0V AC GN...

Страница 12: ...ion advice or training in how to use our products The target is to optimize your benefits The only thing you need to do is Talk to us Quality Support Partnership Our Offer Your Call Tel 86 10 6786 9251 3 Fax 86 10 6786 9256 Email info vectorcontrols com VECTOR CONTROLS LTD 23 Xi Huan Bei Road Room 208 Hua Teng Fa Zhan Building Yi Zhuang Beijing 100176 PRC VECTOR ...

Отзывы: