TCY-MT 

Configuration 

 

Doc: 70-00-0058 V1.2, 20160322 

© Vector Controls GmbH, Switzerland 

Page 7 

Subject to alteration 

www.vectorcontrols.com 

T [°C, F] 

U [V, mA] 

Heating 

Cooling 

10

 

50 

 

Y

H1

, Y

R1 

W

X

DZ

 

Y

C1, 

Y

D1

 

W

Max heating: CP14

 

Min cooling: CP15

 

Max cooling: CP16

 

Min heating: CP13

 

Output configuration 

Parameter  Description 

Range 

Default 

CP 12 

Manual Override Mode: 

Allows manual control of the analog outputs for using the 

controller as positioner or during commissioning.  

ON, OFF 

OFF 

CP 13 

Min output for AO1 (TCY-MT4 = heating output) 

0 – 100 % 

0% 

CP 14 

Max output for AO1 (TCY-MT4 = heating output) 

0 – 100 % 

100% 

CP 15 

Min output for AO2 (TCY-MT4 = cooling output) 

0 – 100 % 

0% 

CP 16 

Max output for AO2 (TCY-MT4 = cooling output) 

0 – 100 % 

100% 

CP 17 

Maximum Output in Economy (unoccupied)Mode 

Reduces the load on the system when is the space is 
unoccupied. 

0 – 100 % 

50% 

 

Limiting the output signal

 

The output signal (0–10V) may be 

limited. The lower limit for example may 

be changed to 20% for a 2–10V actuator. 

Other reasons for changing the limits are 

VAV systems. By changing the limits the 

minimum and maximum flows may be 

adjusted without the need to access the 

VAV actuator. The output limits may 

thus be set individually for heating and 

cooling mode: 

 

 

Содержание TCY-MT2-W01

Страница 1: ...es and current inputs and outputs the TCI product range is recommended The TCY MT can be configured using the standard operation terminal No special tool or software is required Name Ordering Item Nam...

Страница 2: ...122 F 95 r H non condensing Transport Storage Climatic Conditions Temperature Humidity Mechanical Conditions To IEC 721 3 2 and IEC 721 3 1 class 3 K3 and class 1 K3 25 70 C 13 158 F 95 r H non conden...

Страница 3: ...rect sunlight or other heat sources e g the area above radiators and heat emitting electrical equipment Avoid locations behind doors outside walls and below or above air discharge grills and diffusers...

Страница 4: ...connected to a power supply for at least 10 hours for the backup function to operate accordingly Error messages The TCY MT may display the following error condition Err1 The connection to the tempera...

Страница 5: ...WN buttons Select 009 in order to get access to the user parameters 241 for controls parameters Press OPTION after selecting the correct password 3 Once logged in the parameter is displayed immediatel...

Страница 6: ...Cooling mode YC1 1 TCY MT2 W02 Heating mode YH1 2 TCY MT2 Heating and Cooling 2 pipe system YH1 YC1 3 TCY MT4 Heating and Cooling 4 pipe system YH1 YC1 TCY MT2 0 2 TCY MT4 0 3 TCY MT2 W01 0 TCY MT2 W...

Страница 7: ...MT4 heating output 0 100 0 CP 14 Max output for AO1 TCY MT4 heating output 0 100 100 CP 15 Min output for AO2 TCY MT4 cooling output 0 100 0 CP 16 Max output for AO2 TCY MT4 cooling output 0 100 100...

Страница 8: ...on detectors for offices CP18 2 Switching Energy Hold OFFand Comfort modes Opening the external temperature input will force the unit into the OFF operation mode The operation mode cannot be overridde...

Отзывы: