background image

 

TCY-MT 

Operation Instructions 

 

Doc: 70-00-0058 V1.2, 20160322 

© Vector Controls GmbH, Switzerland 

Page 4 

Subject to alteration 

www.vectorcontrols.com 

Display and Operation 

 

Operation mode 

 

Comfort (occupied) 

All control functions operating per set points. 

 

Economy (unoccupied): 

Set points shifted according to 

Parameters CP04.

 

Economy mode and set point shift may be disabled with UP07 

OFF 

Energy Hold Off 

Outputs are off, inputs monitored for alarm condition 

 

Heating 

Output activates if temperature lower than set point 

 

Cooling 

Output activates if temperature higher than set point 

Power Failure 

All the parameters and set points are memorized and do not need to be reentered. Depending on 

UP05

 the unit will 

remain switched off, switch on automatically or return to the operation mode it was in before the power failure. 

Deluxe version only

: Timer operation and daytime setting will be retained for 24h. The controller has to be connected to a 

power supply for at least 10 hours for the backup function to operate accordingly.  

Error messages 

The TCY-MT may display the following error condition:  

 

Err1:

 

The connection to the temperature sensor may be interrupted or the temperature sensor is damaged.  

The output is switched off. Verify parameter settings and wiring.  

 

Left (POWER) 

Press < 2 sec.: Toggle STANDBY-

COMFORT mode or switch from OFF 
to ON 
Press > 2 sec.: Turn unit OFF. Text 
OFF displayed with current time 
(deluxe) temperature (standard) 
(Parameter setting: ENTER to 
select menu option, accept 
parameter change) 
 

Up  

Increment SET POINT  

(Parameter setting: 
SCROLL menu options 
and parameters) 
 

Down  

Decrement SET POINT  

(Parameter setting: SCROLL menu 
options and parameters) 
 

Mode 

Display of operation 

mode 

 
 

Large Digits 

Display of input or parameter 
value. 

Indicators 

1 Remote 

temperature sensor 

2 Dew point sensor 

Vertical Bar 

(scrolls up/down, 10% resolution) 

Small Digits 

Display of set point, clock or 
parameter number. 
 

Right (OPTION)  

Press < 2 sec.: Select Control Loop 

Press > 2 sec.: Manual H/C change 

(Parameter setting: ENTER to 
select menu option, accept 
parameter change) 
 

Содержание TCY-MT2-W01

Страница 1: ...es and current inputs and outputs the TCI product range is recommended The TCY MT can be configured using the standard operation terminal No special tool or software is required Name Ordering Item Nam...

Страница 2: ...122 F 95 r H non condensing Transport Storage Climatic Conditions Temperature Humidity Mechanical Conditions To IEC 721 3 2 and IEC 721 3 1 class 3 K3 and class 1 K3 25 70 C 13 158 F 95 r H non conden...

Страница 3: ...rect sunlight or other heat sources e g the area above radiators and heat emitting electrical equipment Avoid locations behind doors outside walls and below or above air discharge grills and diffusers...

Страница 4: ...connected to a power supply for at least 10 hours for the backup function to operate accordingly Error messages The TCY MT may display the following error condition Err1 The connection to the tempera...

Страница 5: ...WN buttons Select 009 in order to get access to the user parameters 241 for controls parameters Press OPTION after selecting the correct password 3 Once logged in the parameter is displayed immediatel...

Страница 6: ...Cooling mode YC1 1 TCY MT2 W02 Heating mode YH1 2 TCY MT2 Heating and Cooling 2 pipe system YH1 YC1 3 TCY MT4 Heating and Cooling 4 pipe system YH1 YC1 TCY MT2 0 2 TCY MT4 0 3 TCY MT2 W01 0 TCY MT2 W...

Страница 7: ...MT4 heating output 0 100 0 CP 14 Max output for AO1 TCY MT4 heating output 0 100 100 CP 15 Min output for AO2 TCY MT4 cooling output 0 100 0 CP 16 Max output for AO2 TCY MT4 cooling output 0 100 100...

Страница 8: ...on detectors for offices CP18 2 Switching Energy Hold OFFand Comfort modes Opening the external temperature input will force the unit into the OFF operation mode The operation mode cannot be overridde...

Отзывы: