TCY-FT 

PI-Temperature controller 

 

Doc: 70-00-0129B, V1.2, 2012-11-09 

© Vector Controls GmbH, Switzerland 

Page 1 

Subject to alteration 

www.vectorcontrols.com 

TCY-FT Series PI-temperature controller 

 

Features 

 

Temperature PI control for HVAC systems.  

 

Up to two 3-point outputs for 24VAC actuators.  

 

1 internal temperature sensor and up to 2 external sensor inputs 

 

Multiple remote control functions on external input 

 

Password protected programmable user and control parameters 

 

Blue backlight 

Applications 

 

Various temperature control applications 

 

Water Only Systems: Radiator, floor heating or chilled ceilings 

 

Individual room control for offices, residential, hotel rooms, 

meeting rooms, etc.  

General description 

The TCY-FT is a stand-alone electronic temperature controller. It may use up to 2 PI sequences. The TCY-FT features 1 

internal NTC temperature sensor, up to two external sensors inputs and up to four binary outputs. The configuration has 
been reduced to a minimum to allow for a simple and off the shelf usage. For more advanced features the TCI product 

range may be used. The TCY-FT can be configured using the standard operation terminal. No special tool or software is 

required.  

 

Name  

 

Ordering 

Item Name 

Item code 

Control Type 

Key-data 

TCY-FT2-W01 

40-10 0067-1 

Cooling only 

Compact PI controller with: 
2 TI, 1 3-point output 

TCY-FT2-W02 

40-10 0067-2 

Heating only 

TCY-FT2 

40-10 0067 

2-Pipe system 

TCY-FT4 

40-10 0071 

4-Pipe system 

1 TI, 2 3-point outputs 

 

Accessories

 

S-Tn10-2 

SD-Tn10-12-2 

SD-Tn10-20-2 

SDB-Tn10-12 

SDB-Tn10-20 
SRA-Tn10 

40-20 0001 
40-20 0002 

40-20 0003 

40-20 0051 

40-20 0004 

40-20 0005 

Flying lead sensor with 2 m cable 

Flying lead duct sensor 12cm immersion depth, 2m cable 

Flying lead duct sensor 20cm immersion depth, 2m cable 

Duct sensor with housing, 12cm immersion depth 

Duct sensor with housing, 20cm immersion depth 
Room sensor 

Selection of actuators and sensors 

Temperature Sensors:  

Use only our approved NTC sensors to achieve maximum accuracy.  Recommended is SDB-Tn10-20 as Duct sensor, SRA-

Tn10 as Room sensor and SDB-Tn10-20 with AMI-S10 as immersion sensor.  

3-point actuators:  

Actuators with constant running time are recommended. Observe power limits. Do not use actuators with power 

consumption > 6VA. Adjust running time in SW. Default running time is 90s for fully open / close running time.  

 

Housing:  

U  = Vertical (2x4”) housing, Standard is square housing 

Function: 

2  = 2 = 2-Pipe, 4 = 4-Pipe

 

Input: 

T  = Temperature, H = Humidity 

Output:  

F  = 3-point, M = Modulating, B = Binary 

Series: 

TCY

 

T  C  Y 

-  F 

-   U 

(   )  

Содержание TCY-FT Series

Страница 1: ...l tool or software is required Name Ordering Item Name Item code Control Type Key data TCY FT2 W01 40 10 0067 1 Cooling only Compact PI controller with 2 TI 1 3 point output TCY FT2 W02 40 10 0067 2 H...

Страница 2: ...F 95 r H non condensing Transport Storage Climatic Conditions Temperature Humidity Mechanical Conditions To IEC 721 3 2 and IEC 721 3 1 class 3 K3 and class 1 K3 25 70 C 13 158 F 95 r H non condensing...

Страница 3: ...4 5 above the floor in an area of average temperature Avoid exposure to direct sunlight or other heat sources e g the area above radiators and heat emitting electrical equipment Avoid locations behind...

Страница 4: ...e connected to a power supply for at least 10 hours for the backup function to operate accordingly Error messages The TCY FT may display the following error condition Err1 The connection to the temper...

Страница 5: ...t a password using UP or DOWN buttons Select 009 in order to get access to the user parameters 241 for controls parameters Press OPTION after selecting the correct password 3 Once logged in the parame...

Страница 6: ...FT2 W1 Cooling mode YC1 1 TCY FT2 W2 Heating mode YH1 2 TCY FT2 Heating and Cooling 2 pipe system YH1 YC1 3 TCY FT4 Heating and Cooling 4 pipe system YH1 YC1 TCY FT2 0 2 TCY FT4 0 3 TCY FT2 W1 0 TCY...

Страница 7: ...sed to fully open 0 255s 90s CP 14 Minimum running time FO1 TCY FT4 heating output The minimum time the output runs once it starts This setting prevents frequent switches with very short running times...

Страница 8: ...ion detectors for offices CP18 2 Switching Energy Hold OFF and Comfort modes Opening the external temperature input will force the unit into the OFF operation mode The operation mode cannot be overrid...

Отзывы: