TCI2
P
RODUCT
D
ATA
S
HEET
Doc: 70-07-0703B, 20220426
© Vector Controls LLC, USA
Page 6-10
Subjects to alteration
www.vectorcontrols.com
V
ECTOR
Type: TCI2-222.200
Configuration of in- and outputs
The inputs and outputs are configured with jumpers. Jumpers are located underneath the controller.
AO: Selection of analog output type
Left position:
voltage output (0... 10 V)
factory default
Right position:
current output (0... 20 mA)
AO1
UI: Selection of universal input type
Left position:
voltage output (0... 10 V)
factory default
Middle position: current input (0... 20 mA)
Right position: RT or dry contact
UI1
0
…
1
0
V
0
…
2
0
m
A
0
…
1
0
V
0
…
2
0
m
A
R
T
/
D
I
█
█
See the TCI2 installation sheet, document no. 70-00-0688 or 70-00-0893 (
Status-LED
The TCI2 has a status-LED which is located on the upper left side of the controller housing.
The location of the LED is described in the installation sheet. The function of the LED is explained in the X2 Operations Manual.
Rest button TCP/IP (-WEM, -WEB, -ETM, -ETB only)
The TCP/IP configuration setting of the TCI2 can be reset by pressing the reset button with a 1 mm pin through the small hole
located next to the Status-LED. The function of the TCP/IP reset is explained in the X2 Wi-Fi / Ethernet Configuration Manual.
OPT1-xx
OPA2-xx
N L
Operation
Terminal
GND
UI1
UI2
Digital Output (2x)
Power
Relays 3A
NTC Input (2x)
NTC 10k
UI3
UI4
VDC Input (2x)
0...10 VDC
Status LED
GND
UI
NTC
10k
UI
GND
0…10 VDC
UI
GND
GND
V+
24V AC/DC
3 VA
GND
Vop
+
_
STP
OPXX-VC
1
2
3
4
120
Ω
JP7
OP3
OP1
OP4
OP2
24V AC/DC
L
N
N
DO1
DO1
DO2
DO2
+
REF
_
UI1/2
UI3/4