Technical specifications 

Power supply 

Operating voltage 

TCI2-204.202U 

24 VAC ±10%, 50/60 Hz, 12

…34 VDC

 

Safety extra-low voltage (SELV) 

HD 384, Class II 

Operating voltage 

TCI2-204.202U-L 

85…264 VAC, 50/60 Hz, 120…370 VDC

 

Power consumption 

Max. 3 VA 

Clock backup 

Min. 48 hours

 

Signal inputs 

Universal input 

Input signal 

Resolution 

Impedance 

Input jumper set for voltage or current 

0…10 VDC or 0…20 mA

 

9.76 mV or 0.019 mA (10 bit) 

Voltage: 74.8kΩ, Current: 158Ω

 

Input jumper set to temperature (RT) or digital input (DI) 

Passive input 

Type & range: 

NTC (Sxx-

Tn10) 10kΩ@25°C: 

-

40…100 °C (

-

40…212 °F)

 

PT1000 (Sxx-Tp2): -

50…205 °C (

-

58…401 °F)

 

NI1000 (Sxx-Tk5): -

50…180 °C (

-

58…356 °F)

 

Signal outputs 

Analog outputs:   Output signal 

 

 

Resolution 

 

 

Maximum load 

0...10 VDC or 0…20 mA

 

9.76 mV or 0.019 mA (10 bit)  

Voltage: ≥1kΩ

 

Current: ≤250Ω

 

Relay outputs:   AC Voltage 

(SPST NO) 

DC Voltage 

0…250 VAC, full

-load current 3A, locked-rotor 18A. 

0…30 VDC, full

-load current 3A, locked-rotor 18A. 

Insulation strength between relays contacts 

and system electronics: 

between neighboring contacts: 

 

4000 VAC to EN 60 730-1 

1250 VAC to EN 60 730-1 

Electrical 

connections 

Connector type 

Screw terminal connectors for wire 0.34…

2.5 mm2  

(AWG 22…1

2) 

Remote terminal 

RS485 in accordance with EIA/TIA 485, Shielded twisted 

pair cable 

Environment 

Operation 

Climatic conditions 

Temperature 

Humidity 

To IEC 721-3-3 

class 3K5 

0…50 °C (32…122 °F)

 

<85 % RH non-condensing 

Transport & storage 

Climatic conditions 

Temperature 

Humidity 

Mechanical conditions 

To IEC 721-3-2 and IEC 721-3-1 

class 3K3 and class 1K3 

-

25…70 °C (

-

13…158 °F)

 

<95 % RH non-condensing 

class 2M2 

Standards 

Degree of protection 

IP30 to EN 60 529 

Pollution class 

II (EN 60 730-1) 

Safety class:  

TCI2-202.202U 

 

TCI2-204.202U-L 

III (IEC 60536) if SELV is connected to DO, else II 

II (IEC 60536)  

Overvoltage category 

III (EN 60 730-1) 

General 

Material 

Fire proof ABS plastic (UL94 class V-0) 

Dimensions (H x W x D) 

57 x 93 x 115 mm (2.4 x 3.7 x 4.5) inch  

Weight (including package) 

TCI2 (24V) without display / with display 

TCI2 (230V without display / with display 

 

245g (8.6oz) / 290g (10.2oz) 

275g (9.7oz) / 320g (11.3oz) 

 

Technical specification for serial communication -MOD and -BAC types 

Network 

Hardware interface 

Max nodes per network 

Max nodes per segment 

RS485 in accordance with EIA/TIA 485 

128 

64 (Vector devices only) 

 

Conductors 
Impedance 

Nominal capacitance 

Shielded Twisted Pair (STP) cable  
100 - 130 ohm  

100 pF/m 16 pF/ft. or lower 

 

Galvanic isolation 

The communication circuitry is isolated 

 

Line termination 

 

 

Network topology 

A line termination resistance (120 ohm) shall be connected 

between the terminals (+) and (-) of the furthermost node 

of the network 

Daisy chain according EIA/TIA 485 specifications 

 

Recommended maximum length per chain 

1200 m (4000 ft.)  

Содержание TCI2 Series

Страница 1: ...et communication and the EasySet program Functions Two universally configurable control loops o Functions for dehumidifying set point shift and cascade control o Multiple auxiliary functions heat cool...

Страница 2: ...2 4 2 2 BACnet IP 100 250 VAC TCP IP WI FI TCI2 204 202UC ETB 40 110132 2 4 2 2 BACnet IP 24 V TCP IP Ethernet UI Universal input DO Digital output AO Analog output COM Communication Accessories Prod...

Страница 3: ...nal RS485 in accordance with EIA TIA 485 Shielded twisted pair cable Environment Operation Climatic conditions Temperature Humidity To IEC 721 3 3 class 3K5 0 50 C 32 122 F 85 RH non condensing Transp...

Страница 4: ...NCC 802 11 b g n 802 11n up to 150 Mbps A MPDU and A MSDU aggregation and 0 4 s guard interval support Frequency range 2 4 GHz 2 5 GHz Antenna External Ethernet Compliant with IEEE802 3 802 3u Fast E...

Страница 5: ...n input signal type of 0 10 VDC or 4 20 mA min and max signal limitations may be set with parameters 3 point actuators with constant running time are recommended Binary auxiliary devices e g pumps fan...

Страница 6: ...70 00 0893 www vectorcontrols com Status LED The TCI2 has a status LED which is located on the upper left side of the controller housing The location of the LED is described in the installation sheet...

Страница 7: ...nd installation manual OP MOD BAC TCI2 Install Sheet TCP IP 70 00 0893 Mounting and installation manual WEM WEB ETM ETB X2 Operations Manual button display 70 07 0950 Operations instructions of X2 sys...

Страница 8: ...tiple B DS WP B Data sharing Write property B DM DCC B Device management Device communication Control B DM DDB B Device management Dynamic device binding B DM DOB B Device management Dynamic object bi...

Страница 9: ...ry value Multi state Value Network Port X2 Functional Scope The controller has the following X2 functions and elements Group Modules QTY Description UP User and display parameters UI 01U to 04U 4 Univ...

Страница 10: ...20220426 Vector Controls LLC USA Page 10 10 Subjects to alteration www vectorcontrols com VECTOR Smart Sensors and Controls Made Easy Quality Innovation Partnership Vector Controls LLC USA infous vec...

Отзывы: