TCI-W13-U, TCI-W23-U Universal Controller 

U

SER 

C

ONFIGURATION

 

 

Doc: 70-00-0414C, V2.0, 20220523  

© Vector Controls GmbH, Switzerland  

Page 10-22 

Subject to alteration 

User and display parameters (Password 009) 

 

Parameter  Description 

Range 

Default 

UP 00 

Enable access to operation modes 

ON/OFF 

ON 

UP 01 

Enable access to set points 

ON/OFF 

ON 

UP 02 

Enable manual control in cascade 

ON/OFF 

ON 

UP 03 

Enable change of heating/cooling mode for 2 pipe systems 

ON/OFF 

ON 

UP 04 

Enable access to time programs: 

ON/OFF 

ON 

UP 05 

State after power failure:  

0= off,  1= on,  2= state before power failure 

0, 1, 2 

UP 06 

Enable Unoccupied (economy) Mode.  

Shift the setpoint to a lower temperature in winter or higher temperature 

in summer in order to save energy. Unoccupied (economy) mode may be 

activated through the POWER button, or with the external input (typically 
for key card switches in hotel rooms or motion detectors for meeting 

rooms.) 

ON/OFF 

ON 

UP 07 

Celsius or Fahrenheit: ON= Fahrenheit,  OFF= Celsius 

ON/OFF 

OFF (Celsius) 

UP 08 

Show standard display while no key is pressed 

ON/OFF 

ON 

UP 09 

Select type of content for large digits (00= OFF): 

0

01= Input 

02= Setpoint 

03= Analog Output 

04= Binary Output 

05= Clock 

UP 10 

Select content source for large digits (0=OFF): 

0

Input: 

1= 1T 

2= 1H 

3= 1U 

4= 2T 

Set point: 

1= Lp1 

2= Lp2 

Analog or 

floating output: 

1= AO1 

2= AO1 

Binary output: 

1= DO1 

UP 11 

Select type of content for small digits(same options as UP09) 

0

TCI-W13 = 2 

TCI-W23 = 5 

UP 12 

Select content source for small digits (same options as UP10) 

0

UP 13 

Select analog output for vertical bar display (00= OFF): 

0

01= AO1 

02= AO2 

03= Output LP1 

04= Output LP2 

UP 14 

Display heating/cooling state in standard display mode 

ON/OFF 

OFF 

UP 15 

ON = Alarms blink after being active and need to be confirmed 

OFF= Alarms are only shown when they are active 

ON/OFF 

ON 

UP 16 

(TCI-W23) 

Clock display type:  OFF= 24-hr,  ON= 12-hr(AM/PM) 

ON/OFF 

OFF(24hr) 

UP 17 

(TCI-W23) 

Reset timer for manual override of PRO time schedule:  

0=  Not active  

1

255= Delay for controller to go back to the scheduled Energy Hold OFF, 

Unoccupied (ECONOMY), or Occupied (COMFORT) operation mode if the 
operation mode is changed manually. 

0

255 

Min 

60(Min) 

UP 18 

(TCI-W23) 

OFF = Backlight switch on for 30 seconds when a key is pressed. 

ON = Backlight switch on constantly when device is in ON mode 

ON/OFF 

OFF 

 

 

Содержание 40-100267

Страница 1: ...loops 8 time schedules 1 internal temperature sensor 1 universal input 1 passive input 1 binary PWM output 2 analog outputs Internal temperature sensor standard Add replaceable humidity element as req...

Страница 2: ...ity Stability Capacity sensor 0 100 rH See Figure to the right 1 0 1 0 5 year Signal outputs Analog Output Output Signal Resolution Maximum Load DC 0 10 V 0 20 mA 9 76 mV 0 019 mA Voltage 1k Current 2...

Страница 3: ...outputs Potential free relays contacts see technical specification UI Universal input NTC 10k 25 C 77 F 0 10 V or 0 20 mA selectable by jumper TI Passive input NTC 10 k 25 C 77 F or open contact AO A...

Страница 4: ...r other heat sources e g the area above radiators and heat emitting equipment Avoid locations behind doors outside walls and below or above air discharge grills and diffusers Location of mounting is l...

Страница 5: ...OFF displayed with current time W23 U temperature W13 U Parameter setting BACK to previous menu Menu navigation Back to previous home menu 6 OPTION C F Press 2 sec Enter set up CLOCK TCI W23 U SCHEDU...

Страница 6: ...d each for 4 seconds on the large LCD digits in a continuous cycle while OFF is displayed in the small digits To prevent this make sure that in idle mode no input values are shown on either small or l...

Страница 7: ...ec SEL and current time is displayed Press UP until SEL and H C is displayed Press RIGHT to toggle H or C SEL H C Display input values For TCI W13 Press OPTION 2 sec SEL and H C is displayed Press UP...

Страница 8: ...ime from 00 00 23 45 15 minutes steps Press RIGHT to save switching time bar appears indicating step 1 complete DAY 1 blinks Pr01 08 00 Step 2 Apply selected switching time Pr01 to DAY1 Mon DAY 7 Sun...

Страница 9: ...put configuration 1 analog output do1 do2 Binary output configuration 2 binary digital outputs relays FU Special functions Common to all TCI How to change parameters 1 Press UP DOWN buttons simultaneo...

Страница 10: ...ON UP 09 Select type of content for large digits 00 OFF 0 5 1 01 Input 02 Setpoint 03 Analog Output 04 Binary Output 05 Clock UP 10 Select content source for large digits 0 OFF 0 4 1 Input 1 1T 2 1H...

Страница 11: ...0 Match sensor range to input display With a differential pressure transmitter having 0 200 Pa measuring range set UO1 display minimum to 0 and U02 display maximum to 200 The allowable range value of...

Страница 12: ...de setpoints There are two possibilities to change the setpoint in unoccupied economy mode Shift it by L07 or switch to the minimum setpoint limit in heating mode and maximum setpoint limit in cooling...

Страница 13: ...is that the setpoint is normally not reached As the measured value gets closer to the setpoint the output reduces until it reaches a point a fraction above or below the setpoint where the output equal...

Страница 14: ...l changeover when L23 OFF 0 255 min 5 min Cumulative stage action L16 0 is typically used in electric heat applications and single stage action L16 1 in fan speed applications Digital stage action L16...

Страница 15: ...an be individually selected Multiple alarms can be signed to one output If one alarm is selected to simultaneously activate and deactivate an output the one to de activate has precedence With manual p...

Страница 16: ...1 5 outputs disabled during switch on delay Delay is in seconds or minutes depending on d09 0 255 5 sec 1d 05 Activate PWM set cycle time seconds 0activates 0 deactivates 0 1650s 0s 1d 06 Choose alarm...

Страница 17: ...larm to an output and select output state Each alarm s required output can be individually selected Multiple alarms can be signed to one output Should one alarm be simultaneously selected to activate...

Страница 18: ...delay seconds 1275s 300s Fu 10 Input limit 1 per input 10 Fu 11 Input limit 2 Per input 90 Summer winter compensation changes the set point due to a change in an input value typically but not limited...

Страница 19: ...han limit 2 ON When limit 2 is greater than limit 1enable when input value is between limit 1 and limit 2 When limit 2 is less than limit 1 enable when input value below limit 2 or above limit 1 ON OF...

Страница 20: ...or temperature we recommend switching to cooling at 28 C 83 F and to heating at 16 C 61 F outdoor temperature These recommendations are given as suggestions The ideal settings may be different on the...

Страница 21: ...TCI W13 U TCI W23 U Universal Controller Doc 70 00 0414C V2 0 20220523 Vector Controls GmbH Switzerland Page 21 22 Subject to alteration Empty page...

Страница 22: ...oc 70 00 0414C V2 0 20220523 Vector Controls GmbH Switzerland Page 22 22 Subject to alteration Smart Sensors and Controls Made Easy Quality Innovation Partnership Vector Controls GmbH Switzerland info...

Отзывы: