TCI-W13-U, TCI-W23-U Universal Controller
U
SER
C
ONFIGURATION
Doc: 70-00-0414C, V2.0, 20220523
© Vector Controls GmbH, Switzerland
Page 10-22
Subject to alteration
User and display parameters (Password 009)
Parameter Description
Range
Default
UP 00
Enable access to operation modes
ON/OFF
ON
UP 01
Enable access to set points
ON/OFF
ON
UP 02
Enable manual control in cascade
ON/OFF
ON
UP 03
Enable change of heating/cooling mode for 2 pipe systems
ON/OFF
ON
UP 04
Enable access to time programs:
ON/OFF
ON
UP 05
State after power failure:
0= off, 1= on, 2= state before power failure
0, 1, 2
2
UP 06
Enable Unoccupied (economy) Mode.
Shift the setpoint to a lower temperature in winter or higher temperature
in summer in order to save energy. Unoccupied (economy) mode may be
activated through the POWER button, or with the external input (typically
for key card switches in hotel rooms or motion detectors for meeting
rooms.)
ON/OFF
ON
UP 07
Celsius or Fahrenheit: ON= Fahrenheit, OFF= Celsius
ON/OFF
OFF (Celsius)
UP 08
Show standard display while no key is pressed
ON/OFF
ON
UP 09
Select type of content for large digits (00= OFF):
0
–
5
1
01= Input
02= Setpoint
03= Analog Output
04= Binary Output
05= Clock
UP 10
Select content source for large digits (0=OFF):
0
–
4
1
Input:
1= 1T
2= 1H
3= 1U
4= 2T
Set point:
1= Lp1
2= Lp2
Analog or
floating output:
1= AO1
2= AO1
Binary output:
1= DO1
UP 11
Select type of content for small digits(same options as UP09)
0
–
5
TCI-W13 = 2
TCI-W23 = 5
UP 12
Select content source for small digits (same options as UP10)
0
–
4
1
UP 13
Select analog output for vertical bar display (00= OFF):
0
–
4
3
01= AO1
02= AO2
03= Output LP1
04= Output LP2
UP 14
Display heating/cooling state in standard display mode
ON/OFF
OFF
UP 15
ON = Alarms blink after being active and need to be confirmed
OFF= Alarms are only shown when they are active
ON/OFF
ON
UP 16
(TCI-W23)
Clock display type: OFF= 24-hr, ON= 12-hr(AM/PM)
ON/OFF
OFF(24hr)
UP 17
(TCI-W23)
Reset timer for manual override of PRO time schedule:
0= Not active
1
–
255= Delay for controller to go back to the scheduled Energy Hold OFF,
Unoccupied (ECONOMY), or Occupied (COMFORT) operation mode if the
operation mode is changed manually.
0
–
255
Min
60(Min)
UP 18
(TCI-W23)
OFF = Backlight switch on for 30 seconds when a key is pressed.
ON = Backlight switch on constantly when device is in ON mode
ON/OFF
OFF