TCI-W13-U, TCI-W23-U Universal Controller 

A

UX 

F

UNCTIONS 

C

ONFIGURATION

 

 

Doc: 70-00-0414C, V2.0, 20220523  

© Vector Controls GmbH, Switzerland  

Page 18-22 

Subject to alteration 

Auxiliary functions 

Summer/winter compensation 

Parameter 

Description 

Range 

Default 

Fu 00 

Select compensation input (0= function disabled):  

1= 1T,  2= 1H,  3= 1U,  4= 2T 

0

Fu 01 

Winter compensation setpoint setback 

OFF= shift toward control loop heating set point minimum  

ON=  shift toward control loop heating set point maximum 

ON/OFF 

OFF 

Fu 02 

Winter compensation lower limit value 

 end shift  

per input 

5°C (41°F) 

Fu 03 

Winter compensation upper limit value 

 start shift 

per input 

20°C (68°F) 

Fu 04 

Summer compensation setpoint setback 

OFF= shift toward control loop cooling set point minimum 

ON=  shift toward control loop cooling set point maximum 

ON/OFF 

ON 

Fu 05 

Summer compensation lower limit value 

 start shift 

per input 

35°C (95°F) 

Fu 06 

Summer compensation upper limit value 

 end shift  

per input 

40°C (104°F) 

Fu 07 

Show hot/cool symbol while compensation active 

ON/OFF 

OFF 

Occupied (comfort)/Unoccupied (economy) mode changeover 

Fu 08 

Select occupied (comfort)/unoccupied (economy) changeover input 

(0= disabled):  

1= 1T,  2= 1H,  3= 1U,  4= 2T 

0

Fu 09 

Unoccupied (economy) activation delay (seconds) 

-1275s 

300s 

Fu 10 

Input limit 1 

per input 

10 

Fu 11 

Input limit 2 

Per input 

90 

 

 

Summer/winter compensation changes the set point due to a change in an input value, typically, but not limited to, 

an outdoor temperature input. Winter compensation starts when outside temperature drops below the upper limit of 

winter compensation (FU03). At maximum winter compensation the actual set point will be equal to the control loop

’s

 

maximum heating set point (L02). Summer compensation starts when outside temperature exceeds the lower limit 

for summer compensation (FU05). At maximum summer compensation the actual set point will be equal to the 

control loop

’s

 maximum cooling set point (L04). Activate summer/winter compensation with control loop configuration 

parameter(L05). 

 

 

Use occupied (comfort)/unoccupied (economy) mode changeover with key card switches, occupancy sensors, etc. Set 
input limit 1 and 2 with possibilities below. Example: When Limit 2 is greater than Limit 1, switch comfort-to-economy 

at the lower value, economy-to-comfort at the higher value. Activate occupied (comfort)/unoccupied (economy) 

changeover with loop configuration parameter(L07).

 

 

 

 

 

1L03 

FU04-OFF 

 

Winter Compensation 

 FU01 

Summer Compensation 

 FU04 

1L02 

T [°C,°F], 

U[V,mA] 

FU02 

FU01-ON 

FU03 

1L01 

FU01-OFF 

Set point 

Min/max 

 

FU04-ON 

1L04 

FU05 

FU06 

Standby 

Mode 

Mode 

Comfort 

Input  

Limit 2 > Limit 1  

Comfort 

Standby 

Input 

Limit 1 > Limit 2  

Limit 

Limit 

Limit 

Limit 

Содержание 40-100267

Страница 1: ...loops 8 time schedules 1 internal temperature sensor 1 universal input 1 passive input 1 binary PWM output 2 analog outputs Internal temperature sensor standard Add replaceable humidity element as req...

Страница 2: ...ity Stability Capacity sensor 0 100 rH See Figure to the right 1 0 1 0 5 year Signal outputs Analog Output Output Signal Resolution Maximum Load DC 0 10 V 0 20 mA 9 76 mV 0 019 mA Voltage 1k Current 2...

Страница 3: ...outputs Potential free relays contacts see technical specification UI Universal input NTC 10k 25 C 77 F 0 10 V or 0 20 mA selectable by jumper TI Passive input NTC 10 k 25 C 77 F or open contact AO A...

Страница 4: ...r other heat sources e g the area above radiators and heat emitting equipment Avoid locations behind doors outside walls and below or above air discharge grills and diffusers Location of mounting is l...

Страница 5: ...OFF displayed with current time W23 U temperature W13 U Parameter setting BACK to previous menu Menu navigation Back to previous home menu 6 OPTION C F Press 2 sec Enter set up CLOCK TCI W23 U SCHEDU...

Страница 6: ...d each for 4 seconds on the large LCD digits in a continuous cycle while OFF is displayed in the small digits To prevent this make sure that in idle mode no input values are shown on either small or l...

Страница 7: ...ec SEL and current time is displayed Press UP until SEL and H C is displayed Press RIGHT to toggle H or C SEL H C Display input values For TCI W13 Press OPTION 2 sec SEL and H C is displayed Press UP...

Страница 8: ...ime from 00 00 23 45 15 minutes steps Press RIGHT to save switching time bar appears indicating step 1 complete DAY 1 blinks Pr01 08 00 Step 2 Apply selected switching time Pr01 to DAY1 Mon DAY 7 Sun...

Страница 9: ...put configuration 1 analog output do1 do2 Binary output configuration 2 binary digital outputs relays FU Special functions Common to all TCI How to change parameters 1 Press UP DOWN buttons simultaneo...

Страница 10: ...ON UP 09 Select type of content for large digits 00 OFF 0 5 1 01 Input 02 Setpoint 03 Analog Output 04 Binary Output 05 Clock UP 10 Select content source for large digits 0 OFF 0 4 1 Input 1 1T 2 1H...

Страница 11: ...0 Match sensor range to input display With a differential pressure transmitter having 0 200 Pa measuring range set UO1 display minimum to 0 and U02 display maximum to 200 The allowable range value of...

Страница 12: ...de setpoints There are two possibilities to change the setpoint in unoccupied economy mode Shift it by L07 or switch to the minimum setpoint limit in heating mode and maximum setpoint limit in cooling...

Страница 13: ...is that the setpoint is normally not reached As the measured value gets closer to the setpoint the output reduces until it reaches a point a fraction above or below the setpoint where the output equal...

Страница 14: ...l changeover when L23 OFF 0 255 min 5 min Cumulative stage action L16 0 is typically used in electric heat applications and single stage action L16 1 in fan speed applications Digital stage action L16...

Страница 15: ...an be individually selected Multiple alarms can be signed to one output If one alarm is selected to simultaneously activate and deactivate an output the one to de activate has precedence With manual p...

Страница 16: ...1 5 outputs disabled during switch on delay Delay is in seconds or minutes depending on d09 0 255 5 sec 1d 05 Activate PWM set cycle time seconds 0activates 0 deactivates 0 1650s 0s 1d 06 Choose alarm...

Страница 17: ...larm to an output and select output state Each alarm s required output can be individually selected Multiple alarms can be signed to one output Should one alarm be simultaneously selected to activate...

Страница 18: ...delay seconds 1275s 300s Fu 10 Input limit 1 per input 10 Fu 11 Input limit 2 Per input 90 Summer winter compensation changes the set point due to a change in an input value typically but not limited...

Страница 19: ...han limit 2 ON When limit 2 is greater than limit 1enable when input value is between limit 1 and limit 2 When limit 2 is less than limit 1 enable when input value below limit 2 or above limit 1 ON OF...

Страница 20: ...or temperature we recommend switching to cooling at 28 C 83 F and to heating at 16 C 61 F outdoor temperature These recommendations are given as suggestions The ideal settings may be different on the...

Страница 21: ...TCI W13 U TCI W23 U Universal Controller Doc 70 00 0414C V2 0 20220523 Vector Controls GmbH Switzerland Page 21 22 Subject to alteration Empty page...

Страница 22: ...oc 70 00 0414C V2 0 20220523 Vector Controls GmbH Switzerland Page 22 22 Subject to alteration Smart Sensors and Controls Made Easy Quality Innovation Partnership Vector Controls GmbH Switzerland info...

Отзывы: