TCI-W13-U, TCI-W23-U Universal Controller 

C

ONTROL LOOP 

C

ONFIGURATION

 

 

Doc: 70-00-0414C, V2.0, 20220523  

© Vector Controls GmbH, Switzerland  

Page 14-22 

Subject to alteration 

Digital control sequence 

Parameter  Description 

Range 

Default 

1L 16 

Action of stages: 

0= cumulative: stage 1 stays on when 2 on comes on 

1= single: stage 1 turns off when 2 on comes on 

2= digital: stage 1 only, stage 2 only, then stage 1 plus 2 

0

1L 17 

Offset for heating/reverse binary sequences 

per input 

0.0°C (0.0°F) 

1L 18 

Offset for cooling/direct binary sequences 

per input 

0.0°C (0.0°F) 

1L 19 

Switching span heating 

per input 

1.0°C (2.0°F) 

1L 20 

Switching span cooling 

per input 

1.0°C (2.0°F) 

1L 21 

Switching hysteresis 

per input 

0.5°C (1.0°F) 

1L 22 

Switching delay  

0

255s 

10s 

1L 23 

Activation of reverse/direct (heat/cool) sequence 

OFF=   activates based on demand 
ON  =  follows heat/cool state of controller: Set manually or by 

auxiliary function (FU20-FU23) 

ON/OFF 

OFF 

1L 24 

Delay for heat /cool changeover when L23=OFF 

0

255 min 

5 min 

 

 

Cumulative stage action (L16=0) is typically used in electric heat applications, and single stage action (L16=1) in fan 

speed applications. Digital stage action (L16=2) is especially useful in electric heat applications to generate three 

steps with just two outputs. For example: Step 1=100W, step 2=200W, step 3=300W.  

 

 

 

 

 

 

 

 

Switching hysteresis (L21) is the difference between switching on and switching off. A small hysteresis will increase 

the number of switching cycles and thus the wear on associated equipment.  

 

With switching delay (L22) cumulative stages will not switch on simultaneously. With a sudden demand or initial 

power stage 2 will not start earlier than 10 seconds (default value) after stage 1 has been initiated.  

 

 

 

Cumulative  

Single  

Digital  

Stage 1 

Q

1

 

Q

1

 

Q

1

 

Stage 2 

Q

1

+Q

2

 

Q

2

 

Q

2

 

Stage 3 

 

 

Q

1

+Q

2

 

ON 

OFF 

T [°C, °F] 
U [V, mA] 
 

Q

C2, 

Q

D2

 

O

SH

 

W

O

SC

 

X

DZ

 

W

X

H

 

Q

C1, 

Q

D1

 

Q

H2, 

Q

R2

 

 

Legend 

T, U

 

Input signal 

O

SH

 

Offset heating/direct

 

O

SC

 

Offset cooling/reverse

 

X

DZ

 

Dead zone 

X

SBY

 

Economy set point shift

 

W

H

 

Set point heating/reverse

 

W

C

 

Set point cooling/direct

 

Q

C

, Q

Binary sequences cooling/direct 

Q

H

, Q

Binary sequences heating/reverse 

Содержание 40-100267

Страница 1: ...loops 8 time schedules 1 internal temperature sensor 1 universal input 1 passive input 1 binary PWM output 2 analog outputs Internal temperature sensor standard Add replaceable humidity element as req...

Страница 2: ...ity Stability Capacity sensor 0 100 rH See Figure to the right 1 0 1 0 5 year Signal outputs Analog Output Output Signal Resolution Maximum Load DC 0 10 V 0 20 mA 9 76 mV 0 019 mA Voltage 1k Current 2...

Страница 3: ...outputs Potential free relays contacts see technical specification UI Universal input NTC 10k 25 C 77 F 0 10 V or 0 20 mA selectable by jumper TI Passive input NTC 10 k 25 C 77 F or open contact AO A...

Страница 4: ...r other heat sources e g the area above radiators and heat emitting equipment Avoid locations behind doors outside walls and below or above air discharge grills and diffusers Location of mounting is l...

Страница 5: ...OFF displayed with current time W23 U temperature W13 U Parameter setting BACK to previous menu Menu navigation Back to previous home menu 6 OPTION C F Press 2 sec Enter set up CLOCK TCI W23 U SCHEDU...

Страница 6: ...d each for 4 seconds on the large LCD digits in a continuous cycle while OFF is displayed in the small digits To prevent this make sure that in idle mode no input values are shown on either small or l...

Страница 7: ...ec SEL and current time is displayed Press UP until SEL and H C is displayed Press RIGHT to toggle H or C SEL H C Display input values For TCI W13 Press OPTION 2 sec SEL and H C is displayed Press UP...

Страница 8: ...ime from 00 00 23 45 15 minutes steps Press RIGHT to save switching time bar appears indicating step 1 complete DAY 1 blinks Pr01 08 00 Step 2 Apply selected switching time Pr01 to DAY1 Mon DAY 7 Sun...

Страница 9: ...put configuration 1 analog output do1 do2 Binary output configuration 2 binary digital outputs relays FU Special functions Common to all TCI How to change parameters 1 Press UP DOWN buttons simultaneo...

Страница 10: ...ON UP 09 Select type of content for large digits 00 OFF 0 5 1 01 Input 02 Setpoint 03 Analog Output 04 Binary Output 05 Clock UP 10 Select content source for large digits 0 OFF 0 4 1 Input 1 1T 2 1H...

Страница 11: ...0 Match sensor range to input display With a differential pressure transmitter having 0 200 Pa measuring range set UO1 display minimum to 0 and U02 display maximum to 200 The allowable range value of...

Страница 12: ...de setpoints There are two possibilities to change the setpoint in unoccupied economy mode Shift it by L07 or switch to the minimum setpoint limit in heating mode and maximum setpoint limit in cooling...

Страница 13: ...is that the setpoint is normally not reached As the measured value gets closer to the setpoint the output reduces until it reaches a point a fraction above or below the setpoint where the output equal...

Страница 14: ...l changeover when L23 OFF 0 255 min 5 min Cumulative stage action L16 0 is typically used in electric heat applications and single stage action L16 1 in fan speed applications Digital stage action L16...

Страница 15: ...an be individually selected Multiple alarms can be signed to one output If one alarm is selected to simultaneously activate and deactivate an output the one to de activate has precedence With manual p...

Страница 16: ...1 5 outputs disabled during switch on delay Delay is in seconds or minutes depending on d09 0 255 5 sec 1d 05 Activate PWM set cycle time seconds 0activates 0 deactivates 0 1650s 0s 1d 06 Choose alarm...

Страница 17: ...larm to an output and select output state Each alarm s required output can be individually selected Multiple alarms can be signed to one output Should one alarm be simultaneously selected to activate...

Страница 18: ...delay seconds 1275s 300s Fu 10 Input limit 1 per input 10 Fu 11 Input limit 2 Per input 90 Summer winter compensation changes the set point due to a change in an input value typically but not limited...

Страница 19: ...han limit 2 ON When limit 2 is greater than limit 1enable when input value is between limit 1 and limit 2 When limit 2 is less than limit 1 enable when input value below limit 2 or above limit 1 ON OF...

Страница 20: ...or temperature we recommend switching to cooling at 28 C 83 F and to heating at 16 C 61 F outdoor temperature These recommendations are given as suggestions The ideal settings may be different on the...

Страница 21: ...TCI W13 U TCI W23 U Universal Controller Doc 70 00 0414C V2 0 20220523 Vector Controls GmbH Switzerland Page 21 22 Subject to alteration Empty page...

Страница 22: ...oc 70 00 0414C V2 0 20220523 Vector Controls GmbH Switzerland Page 22 22 Subject to alteration Smart Sensors and Controls Made Easy Quality Innovation Partnership Vector Controls GmbH Switzerland info...

Отзывы: