background image

 

TCI-W11-U, TCI-W22-U Universal Controller 

I

NPUT 

C

ONFIGURATION

 

 

Doc: 70-00-0140C, V2.0-20220523  

© Vector Controls LLC, USA  

Page 11-24 

Subject to alteration 

Control configuration (Password 241) 

Input configuration 

Internal inputs 1T temperature and 1H humidity (with added AES3-HT-A2, -A3 or -A5 element) 

Parameter 

Description 

Range 

Default 

1T 00 

1H 00  Enable internal sensor 

OFF/ON 

ON 

1T 01 

1H 01  Display minimum value 

-50

205 

1T 02 

1H 02  Display maximum value 

-50

205 

100 

1T 03 

1H 03  Sensor sampling rate (control speed decrease as rate increases) 

0

100 

10 

1T 04 

1H 04  Sensor calibration 

per input 

1T 05 

1H 05  Alarm 1 (1T), Alarm 3 (1H) low limit 

OFF/ON 

OFF 

1T 06 

1H 06  Alarm 1 (1T), Alarm 3 (1H) low limit values 

-40

215°C 

5°C/5% 

1T 07 

1H 07  Alarm 2 (1T), Alarm 4 (1H) high limit 

OFF/ON 

OFF 

1T 08 

1H 08  Alarm 2 (1T), Alarm 4 (1H) high limit values 

-40

215°C 

50°C / 95% 

1T 09 

1H 09  Hysteresis Alarm 1, 2, 3, 4  

0

100° 

5°C/5% 

1T 10 

1H 10  Calculate a range of inputs (0= not active):  

1= average,  2= minimum,  3= maximum,  4= differential 

0

Universal inputs 1U = UI1, 2U = UI2 (TCI-W22-U only) 

1U 00 

Signal type (0= not active): 

1= 0-10V or 0-20mA,  2= 2-10V or 4-20mA,  3= passive temperature 

0

1U 01 

Display minimum value 

-50

205 

1U 02 

Display maximum value 

-50

205 

100 

1U 03 

Analog input display range: 0= x 0.1,  1= x 1,  2= x 10,  3 = x 100 

0

1U 04 

Analog input unit of measure:  0= no unit,  1= %,  2= °C /°F,  3= Pa 

0

1U 05 

Sensor sampling rate (control speed decrease as rate increases) 

0

100 

10 

1U 06 

Sensor calibration  

Per input

 

1U 07 

Alarm 5 (1U), Alarm 7 (2U) low limit 

OFF/ON 

OFF 

1U 08 

Alarm 5 (1U), Alarm 7 (2U) low limit value 

-40

215°C 

5°C (41°F) 

1U 09 

Alarm 6 (1U), Alarm 8 (2U) high limit 

OFF/ON 

OFF 

1U 10 

Alarm 6 (1U), Alarm 8 (2U) high limit value 

-40

215°C 

50°C (122°F) 

1U 11 

Hysteresis alarm 5 and 6 (1U), alarm 7 and 8 (2U) 

0

100° 

5°C (10°F) 

1U 12 

Calculate a range of inputs (0=not active):  

1= average, 2= minimum, 3= maximum, 4= differential 

0

 

Set jumpers on the back of the controller: 0

10VDC (default), 0

20mA, or RT/DI (passive temperature or binary) 

 

Further define analog inputs with U00 

 

Match sensor range to input display. With a differential pressure transmitter having 0

200 Pa measuring range set UO1 

display minimum to 0 and U02 display maximum to 200. The allowable range value of -50

205 may be adjusted with 

multipliers inU03. The largest displayable values are -990

9999. Limiting range increases resolution. Applies to analog as 

well as passive temperature inputs. 

 

For binary input (open/close contact) set the jumper to RT/DI and parameter U00 to an analog input.  An open contact 

reads as a high value (100%), a closed contact as a low value (0%).  

 

Enable / Disable an alarm. Setting the alarm enable to OFF will prevent the alarm from being displayed on screen. It may 

never the less be used to control an output by setting the appropriate output alarm flags. This way, an alarm limit may be 

used as interlock.  

 

Specify the input value that triggers an alarm. Hysteresis is the difference between alarm level input and value required 

to turn the alarm off. An alarm is displayed as text if enabled (see table). Alarm text can be set to blink continuously until 

acknowledged by pressing the OPTION button or only while the alarm conditions are active (see user parameter UP15).  

 

Calculate mathematical functions over multiple inputs for loop control or display with xU12. In order to calculate average, 

minimum or maximum between several inputs, make sure all the inputs are of identical type and range and then activate 

the same function on xU12 on all the selected inputs. The largest input of the group selected will carry the calculated 

value. For example: When average is activated on 2U12 and 1U12 = 1, the average is carried on UI2.UI2 may now be 

used as input for control loops and it will show the average value of UI1 and UI2 combined. It is possible to use different 

functions on different inputs. For example: minimum of UI1 and UI3 and maximum of UI2 and UI4. 

 

The differential function may only be calculated on subsequent inputs. Such as UI2-UI1. The function must only be 

activated on the minuend (UI2 in this example). The displayed value of the minuend will change into the difference: UI2 

in 

 UI1 = UI2 out. It is possible to have multiple differentials on one controller. It is not possible to reverse the 

subtraction to UI1-UI2. 

Input 

1T 

1H 

1U 

2U 

Low limit 

ALA1 

ALA3 

ALA5 

ALA7 

High limit 

ALA2 

ALA4 

ALA6 

ALA8 

Содержание 40-10 0265

Страница 1: ...oops 8 time schedules 1 internal temperature sensor 2 universal inputs 2 binary PWM outputs 1 analog output Internal temperature sensor standard Add replaceable humidity element as required AES3 HT A2...

Страница 2: ...tability Capacity sensor 0 100 rH See Figure to the right 1 0 1 0 5 year Signal outputs Analog Output Output Signal Resolution Maximum Load DC 0 10 V 0 20 mA 9 76 mV 0 019 mA Voltage 1k Current 250 Re...

Страница 3: ...24VAC 24VDC DO Binary outputs Potential free relays contacts see technical specification UI Universal input NTC 10k 25 C 77 F 0 10 V or 0 20 mA selectable by jumper AO Analog output 0 10 V or 0 20 mA...

Страница 4: ...er heat sources e g the area above radiators and heat emitting equipment Avoid locations behind doors outside walls and below or above air discharge grills and diffusers Location of mounting is less c...

Страница 5: ...OFF displayed with current time W22 temperature W11 Parameter setting BACK to previous menu Menu navigation Back to previous home menu 6 OPTION C F Press 2 sec Enter set up CLOCK TCI W22 SCHEDULES TC...

Страница 6: ...ch for 4 seconds on the large LCD digits in a continuous cycle while OFF is displayed in the small digits To prevent this make sure that in idle mode no input values are shown on either small or large...

Страница 7: ...ayed For TCI W22 Press OPTION 2 sec SEL and current time is displayed Press UP until SEL and H C is displayed Press RIGHT to toggle H or C SEL H C Display input values For TCI W11 Press OPTION 2 sec S...

Страница 8: ...from 00 00 23 45 15 minutes steps Press RIGHT to save switching time bar appears indicating step 1 complete DAY 1 blinks Pr01 08 00 Step 2 Apply selected switching time Pr01 to DAY1 Mon DAY 7 Sun Whil...

Страница 9: ...configuration 1 analog output do1 do2 Binary output configuration 2 binary digital outputs relays FU Special functions Common to all TCI How to change parameters 1 Press UP DOWN buttons simultaneously...

Страница 10: ...UP 09 Select type of content for large digits 00 OFF 0 5 1 01 Input 02 Setpoint 03 Analog Output 04 Binary Output 05 Clock UP 10 Select content source for large digits 0 OFF 0 4 1 Input 1 1T 2 1H 3 1U...

Страница 11: ...pressure transmitter having 0 200 Pa measuring range set UO1 display minimum to 0 and U02 display maximum to 200 The allowable range value of 50 205 may be adjusted with multipliers inU03 The largest...

Страница 12: ...setpoints There are two possibilities to change the setpoint in unoccupied economy mode Shift it by L07 or switch to the minimum setpoint limit in heating mode and maximum setpoint limit in cooling Un...

Страница 13: ...hat the setpoint is normally not reached As the measured value gets closer to the setpoint the output reduces until it reaches a point a fraction above or below the setpoint where the output equals th...

Страница 14: ...ngeover when L23 OFF 0 255 min 5 min Cumulative stage action L16 0 is typically used in electric heat applications and single stage action L16 1 in fan speed applications Digital stage action L16 2 is...

Страница 15: ...define analog outputs with A02 Custom ranges can be created by setting minimum and maximum signal limits A control loop special function digital control or analog control sequence is not active until...

Страница 16: ...ing mode decreases airflow dwindles until it reaches minimum cooling output 1A05 This minimum will be based on the airflow needed at design cooling and is typically 10 to 15 of maximum cooling airflow...

Страница 17: ...demand active before output on In state mode 1d01 5 outputs disabled during switch on delay Delay is in seconds or minutes depending on d09 0 255 5 sec 1d 05 Activate PWM set cycle time seconds 0 act...

Страница 18: ...s With output parameters assign an alarm to an output and select output state Each alarm s required output can be individually selected Multiple alarms can be signed to one output Should one alarm be...

Страница 19: ...larms are defined with input parameters With output parameters assign an alarm to an output and select output state Each alarm s required output can be individually selected Multiple alarms can be sig...

Страница 20: ...275s 300s Fu 10 Input limit 1 per input 10 Fu 11 Input limit 2 Per input 90 Summer winter compensation changes the set point due to a change in an input value typically but not limited to an outdoor t...

Страница 21: ...imit 2 ON When limit 2 is greater than limit 1enable when input value is between limit 1 and limit 2 When limit 2 is less than limit 1 enable when input value below limit 2 or above limit 1 ON OFF OFF...

Страница 22: ...mperature we recommend switching to cooling at 28 C 83 F and to heating at 16 C 61 F outdoor temperature These recommendations are given as suggestions The ideal settings may be different on the actua...

Страница 23: ...TCI W11 U TCI W22 U Universal Controller Doc 70 00 0140C V2 0 20220523 Vector Controls LLC USA Page 23 24 Subject to alteration Empty page...

Страница 24: ...roller Doc 70 00 0140C V2 0 20220523 Vector Controls LLC USA Page 24 24 Subject to alteration Smart Sensors and Controls Made Easy Quality Innovation Partnership Vector Controls LLC USA infous vectorc...

Отзывы: