background image

 

TCI-W11-U, TCI-W22-U Universal Controller 

O

UTPUT 

C

ONFIGURATION

 

 

Doc: 70-00-0140C, V2.0-20220523  

© Vector Controls LLC, USA  

Page 17-24 

Subject to alteration 

Digital output configuration (1d, 2d) 

Settings for digital outputs (1d00 / 2d00 = OFF, 1d05 / 2d05 = 0), 1d = DO1, 2d = DO2 

 

Parameter  Description 

Range 

Default 

1d 00 

Enable digital/PWM or floating point (3-point valve) output 

OFF= DO1 and DO2 are two digital/PWM outputs 

ON = DO1 and DO2 are one floating point output (DO1 open, DO2 close) 

ON/OFF 

OFF 

1d 01 

Select control loop or special function (0= OFF) 

1= LP1, 2= LP2 

3= Dehumidify (4 pipe, max LP1 cooling, LP2 direct) 

4= Manual positioning (on/off) 

5= State functions 

0

1d 02 

When 1d01 = 1, configure output: 

0= Stage 1 heating/reverse 

1= Stage 1 cooling/direct 

2= Stage 1 heating and cooling, reverse and direct 

3= Stage 2 heating/reverse

 

4= Stage 2 cooling/direct

 

5= Stage 2 heating and cooling, reverse and direct

 

If 1d01 = 4 Manual positioning or time schedule controlled 

0= Time schedule controlled only 

1= Manual positioning and time schedule controlled 

When 1d01 = 5, select state functions:  

0= ON if controller operation state is ON 

1= ON while demand on any output 

2= ON while controller in heating mode and operation state ON 

3= ON while controller in cooling mode and operation state ON 

0

1d 03 

Switch-off delay (time output active with no more demand) 

Delay is in seconds or minutes depending on d09 

0

255 

90sec 

1d 04 

Switch-on delay(time demand active before output on) 

In state mode 1d01=5 outputs disabled during switch-on delay 

Delay is in seconds or minutes depending on d09 

0

255 

5 sec 

1d 05 

Activate PWM, set cycle time, seconds (>0 activates, 0 deactivates) 

0

1650s 

0s 

1d 06 

Choose alarm to set output to ON (output OFF on conflicting alarms) 

 

 



 

Alarm:   1 2 3 4 5 6 7 8 

ALA1

ALA8 



 

1d 07 

Choose alarm to set output to OFF (output OFF on conflicting alarms) 

 

 



 

Alarm:   1 2 3 4 5 6 7 8 

ALA1

ALA8 



 

1d 08 

Display fan symbol while active 

ON/OFF 

OFF 

1d 09 

Binary switching delays in minutes or seconds 

OFF = delays are in seconds, ON = delays are in minutes 

ON, OFF 

OFF 

 

 

Low and high limit alarms are defined with input parameters. With output parameters assign 

an alarm to an output and select output state. Each alarm

’s required output

 can be 

individually selected. Multiple alarms can be signed to one output. Should one alarm be 

simultaneously selected to activate and deactivate the output, the one to de-activate has 

precedence.  

 

With manual positioning (1d01=4) position the output directly (ON/OFF). 

 

With dehumidifying (1d01=3) the maximum value is taken of cooling and dehumidifying. When the humidity is too high, 

cooling will continue to operate, even without a demand for cooling, to dehumidify the air and heating will activate to 

maintain comfort.  

 

State functions (1d01=5) activate the output based on certain conditions with or without a demand for heating or cooling, 

in either occupied (comfort) or unoccupied (standby) mode. In Energy Hold OFF mode (EHO) the output will be off.

 

 

 

 

Output Priority  

1. Alarm level low 
2. Alarm level high 
3. Operation mode OFF 
4. Control function 

Содержание 40-10 0265

Страница 1: ...oops 8 time schedules 1 internal temperature sensor 2 universal inputs 2 binary PWM outputs 1 analog output Internal temperature sensor standard Add replaceable humidity element as required AES3 HT A2...

Страница 2: ...tability Capacity sensor 0 100 rH See Figure to the right 1 0 1 0 5 year Signal outputs Analog Output Output Signal Resolution Maximum Load DC 0 10 V 0 20 mA 9 76 mV 0 019 mA Voltage 1k Current 250 Re...

Страница 3: ...24VAC 24VDC DO Binary outputs Potential free relays contacts see technical specification UI Universal input NTC 10k 25 C 77 F 0 10 V or 0 20 mA selectable by jumper AO Analog output 0 10 V or 0 20 mA...

Страница 4: ...er heat sources e g the area above radiators and heat emitting equipment Avoid locations behind doors outside walls and below or above air discharge grills and diffusers Location of mounting is less c...

Страница 5: ...OFF displayed with current time W22 temperature W11 Parameter setting BACK to previous menu Menu navigation Back to previous home menu 6 OPTION C F Press 2 sec Enter set up CLOCK TCI W22 SCHEDULES TC...

Страница 6: ...ch for 4 seconds on the large LCD digits in a continuous cycle while OFF is displayed in the small digits To prevent this make sure that in idle mode no input values are shown on either small or large...

Страница 7: ...ayed For TCI W22 Press OPTION 2 sec SEL and current time is displayed Press UP until SEL and H C is displayed Press RIGHT to toggle H or C SEL H C Display input values For TCI W11 Press OPTION 2 sec S...

Страница 8: ...from 00 00 23 45 15 minutes steps Press RIGHT to save switching time bar appears indicating step 1 complete DAY 1 blinks Pr01 08 00 Step 2 Apply selected switching time Pr01 to DAY1 Mon DAY 7 Sun Whil...

Страница 9: ...configuration 1 analog output do1 do2 Binary output configuration 2 binary digital outputs relays FU Special functions Common to all TCI How to change parameters 1 Press UP DOWN buttons simultaneously...

Страница 10: ...UP 09 Select type of content for large digits 00 OFF 0 5 1 01 Input 02 Setpoint 03 Analog Output 04 Binary Output 05 Clock UP 10 Select content source for large digits 0 OFF 0 4 1 Input 1 1T 2 1H 3 1U...

Страница 11: ...pressure transmitter having 0 200 Pa measuring range set UO1 display minimum to 0 and U02 display maximum to 200 The allowable range value of 50 205 may be adjusted with multipliers inU03 The largest...

Страница 12: ...setpoints There are two possibilities to change the setpoint in unoccupied economy mode Shift it by L07 or switch to the minimum setpoint limit in heating mode and maximum setpoint limit in cooling Un...

Страница 13: ...hat the setpoint is normally not reached As the measured value gets closer to the setpoint the output reduces until it reaches a point a fraction above or below the setpoint where the output equals th...

Страница 14: ...ngeover when L23 OFF 0 255 min 5 min Cumulative stage action L16 0 is typically used in electric heat applications and single stage action L16 1 in fan speed applications Digital stage action L16 2 is...

Страница 15: ...define analog outputs with A02 Custom ranges can be created by setting minimum and maximum signal limits A control loop special function digital control or analog control sequence is not active until...

Страница 16: ...ing mode decreases airflow dwindles until it reaches minimum cooling output 1A05 This minimum will be based on the airflow needed at design cooling and is typically 10 to 15 of maximum cooling airflow...

Страница 17: ...demand active before output on In state mode 1d01 5 outputs disabled during switch on delay Delay is in seconds or minutes depending on d09 0 255 5 sec 1d 05 Activate PWM set cycle time seconds 0 act...

Страница 18: ...s With output parameters assign an alarm to an output and select output state Each alarm s required output can be individually selected Multiple alarms can be signed to one output Should one alarm be...

Страница 19: ...larms are defined with input parameters With output parameters assign an alarm to an output and select output state Each alarm s required output can be individually selected Multiple alarms can be sig...

Страница 20: ...275s 300s Fu 10 Input limit 1 per input 10 Fu 11 Input limit 2 Per input 90 Summer winter compensation changes the set point due to a change in an input value typically but not limited to an outdoor t...

Страница 21: ...imit 2 ON When limit 2 is greater than limit 1enable when input value is between limit 1 and limit 2 When limit 2 is less than limit 1 enable when input value below limit 2 or above limit 1 ON OFF OFF...

Страница 22: ...mperature we recommend switching to cooling at 28 C 83 F and to heating at 16 C 61 F outdoor temperature These recommendations are given as suggestions The ideal settings may be different on the actua...

Страница 23: ...TCI W11 U TCI W22 U Universal Controller Doc 70 00 0140C V2 0 20220523 Vector Controls LLC USA Page 23 24 Subject to alteration Empty page...

Страница 24: ...roller Doc 70 00 0140C V2 0 20220523 Vector Controls LLC USA Page 24 24 Subject to alteration Smart Sensors and Controls Made Easy Quality Innovation Partnership Vector Controls LLC USA infous vectorc...

Отзывы: