Digital output configuration (1d, 2d)
Settings for PWM outputs (1d00 / 2d00 = OFF, 1d05 / 2d05 > 0), 1d = DO1, 2d = DO2
Parameter Description
Range
Default
1d 00
Enable digital/PWM or floating point (3-point valve) output
OFF= DO1 and DO2 are two digital/PWM outputs
ON = DO1 and DO2 are one floating point output (DO1 open, DO2 close)
ON/OFF
OFF
1d 01
Select control loop or special function (0= OFF)
1= LP1, 2= LP2
3= Dehumidify (4 pipe, max LP1 cooling, LP2 direct)
4= Manual positioning (on/off)
5= State functions
0
–
5
0
1d 02
When 1d01 = 1, configure output:
0= Stage 1 heating/reverse
1= Stage 1 cooling/direct
2= Stage 1 heating and cooling, reverse and direct
3= Stage 2 heating/reverse
4= Stage 2 cooling/direct
5= Stage 2 heating and cooling, reverse and direct
If 1d01 = 4 Manual positioning or time schedule controlled
0= Time schedule controlled only
1= Manual positioning and time schedule controlled
When 1d01 = 5, select state functions:
0= ON if controller operation state is ON
1= ON while demand on any output
2= ON while controller in heating mode and operation state ON
3= ON while controller in cooling mode and operation state ON
0
–
5
0
1d 03
Minimum PWM duty cycle limit
1)
0
–
100%
See Note
1d 04
Maximum PWM duty cycle limit
1)
0
–
100%
See Note
1d 05
Activate PWM, set cycle time, seconds (>0 activates, 0 deactivates)
0
–
1650s
0s
1d 06
Choose alarm to set output to ON (output OFF on conflicting alarms)
Alarm: 1 2 3 4 5 6 7 8
ALA1
–
ALA8
1d 07
Choose alarm to set output to OFF (output OFF on conflicting alarms)
Alarm: 1 2 3 4 5 6 7 8
ALA1
–
ALA8
1d 08
Display fan symbol while active
ON/OFF
OFF
1d 09
Not used
ON, OFF
OFF
➔
Low and high limit alarms are defined with input parameters. With output parameters assign
an alarm to an output and select output state. Each alarm
’s required output
can be
individually selected. Multiple alarms can be signed to one output. Should one alarm be
simultaneously selected to activate and deactivate the output, the one to de-activate has
precedence.
➔
With manual positioning (1d01=4) position the output directly (ON/OFF).
➔
With dehumidifying (1d01=3) the maximum value is taken of cooling and dehumidifying. When the humidity is too high,
cooling will continue to operate, even without a demand for cooling, to dehumidify the air and heating will activate to
maintain comfort.
➔
State functions (1d01=5) activate the output based on certain conditions with or without a demand for heating or cooling,
in either occupied (comfort) or unoccupied (standby) mode. In Energy Hold OFF mode (EHO) the output will be off.
➔
Pulse width modulation (PWM) mode is enabled with 1d05. In PWM mode the digital output will be switched on/off once
per cycle. The on and off times are calculated according to the PI settings of the respective control sequence (see control
loop Parameters L09
–
L15, page 13). TCI-W11-U and TCI-W22-U use relays for the digital outputs.
Important Note!
If you enable PWM function, the meaning of parameter 1d03/2d03 and 1d04/2d04 changes to duty cycle
limits!
Make sure the values of 1d03/2d03 and 1d04/2d04 are set correctly!
Recommended default: 1d03 /2d03 = 0%, 1d04/2d04 = 100%.
It is not recommended to use cycle times below 100 seconds as the lifetime of the relays will be shortened
with frequent switching. For PWM applications requiring cycle times below 100 seconds we recommend
using TCY-FT with TRIAC outputs.
1) The PWM duty cycle signal is not spanned between the min and max settings. It is just cut off. Any output percentage
below the min will be fixed at the minimum time. Any output percentage above the maximum will be fixed to the output
maximum.
Output Priority
1. Alarm level low
2. Alarm level high
3. Operation mode OFF
4. Control function