VFL2-Ex, VTL2-Ex, VRA2-Ex

GB

1.0 General

1.1  All work is to be done by qualified and authorised personnel.

1.2  Handle the equipment carefully.

1.3  The heater is to be stored in dry conditions, relative 

  humidity <55%, temperature >15°C.

1.4  The ambient temperature for the heater when in use is 

  min. -50°C / max. +40°C.

1.5  Before installing the unit, a visual check for transport 

  damages must be made.

1.6  The heater must be secured to the ventilation duct.

1.7  If any changes are made to the product without the 

  consent of VEAB Heat Tech AB, all the certificates of 

  approval becomes invalid.

1.8  The temperature limiter capilary tub are fixed with a spring

    coil around the heating element. Monitoring heating element 

 temperature. 

  The thermostat are fixed in a tube. Monitoring outlet air   

 temperature.

1.9  This appliance can be used by children aged from 8 years and  

  above and persons with reduced physical, sensory or mental  

  capabilities or lack of experience and knowledge if they have 

    been given supervision or instruction concering use of the 

    appliance in a safe way and understand the hazards involved, 

    Childen shall not play with the appliance. Cleaning and user

    maintenance shall not be made by children without supervision.

2.0 Fitting

2.1  Min. airflow rate through the heater is stated on the 

  type lable on the lid. Outlet air temperature must not 

  exceed 40°C.

2.2  When heat is required, heating elements for power step 1  

  shall always be energized.

2.3  The heater may be mounted in a horizontal or a vertical  

  duct, the junction box is to be placed on the side or upwards.

2.4  The minimum distance from or to the nearest duct bend, 

  valve, filter, etc., should correspond with the diagonal 

  dimension of the heater i.e. the from corner to corner in the  

  duct part of the heater. If this is not the case there is a risk  

  that the air flow through the heater will be uneven, which  

  may activate the temperature limiter.

2.5  The air flow direction through the heater must go in the  

  same direction as the arrow on the cover of the heater. 

  The temperature limiter and safety thermostats shall always  

  be placed last in the air flow direction.

2.6  The settings for the surface-mounted temperature limiter  

  with manual resets must never be changed. 

  For the T3 temperature class, the temperature limiter is  

  factory set to 150°C.

2.7  The setting for the thermostat with automatically reset

    must never be higher than 60°C.

3.0 Electrical connections

3.1  Installation has to meet the requirements of any approved  

 standard. 

  1. Open the junction box 

  2. Connect the supply cable to the terminals in each step,  

  terminal earth and terminal 1-6 for thermal protection.    

  Optional:  Heater equipped with anti-condensation heater,  

  connect the supply cable to the terminals 7 and 8. 

  3. Close the junction box.

3.2  The duct heater must be installed so that there is an  

  interlock between the temperature limiters and the 

  thermostat that are fitted to the heater, as well as the fan/air  

  flow that flows through the duct heater. The power supply  

  to the elements should consequently not be switched on  

  unless the associated fan starts or if the temperature limiter  

  has tripped. See wiring example, appendix 1 page 10. 

  When heat is required, heating elements for power step 1  

  shall always be energized. The temperature limiters are  

  mounted on power step number 1. If the heater has more than  

  one power step, power step number 1 shall always be the first  

  to be energized when the heater is required for operation, and  

  the last to be switched off when the power is turned off. 

  If the duct heater has more then one power step and the first

    power step will be regulated by a thyristor, the heater must  

  also be equipped with temperature limiters on power step 2.

3.3  A multi-pole switch shall be installed in the fixed installation.

3.4  The control equipment shall have a separate sensor which  

  automatically limits the temperature of the outlet air from  

  the heater to 40°C.

3.5  The heater’s data for voltage, power and temperature limiter  

  is stated on the wiring diagram that is on the inside of the  

  cover to the duct heater as well as on the specification plate  

  on the outside of the cover.

3.6  Check the torque for all terminal blocks before using the  

  heater. The torques are specified on the wiring diagram. 

  This must also be done, at least once, after the heater has 

  been in use for 6 months. This must also be done in con- 

  nection with other periodic maintenance on the equipment.

Max cross-sectional area in terminal block

Terminal block

Max cross-sectional area

1492-J4 & JG4

4mm²

1492-J6 & JG6

6mm²

1492-J10 & JG10

10mm²

1492-J16 & JG16

16mm²

1492-J35 & JG35

35mm²

Содержание VFL2-Ex

Страница 1: ...AND MAINTENANCE INSTRUCTION ATEX approved electrical air heaters for explosive gas atmospheres IMPORTANT Read these instructions before installing and connecting the product Save these instructions f...

Страница 2: ...rbegr nsare fabriksinst llda p 150 C 2 7 Inst llt v rde p termostat med automatisk terg ende terst llning f r inte st llas in ver 60 C 3 0 Elinstallation 3 1 Installationen m ste uppfylla kraven f r g...

Страница 3: ...stad med temperaturbegr nsare som r egens kra dvs vid ett eventuellt kapill rr rsbrott s kommer skydden automatiskt att bryta s kerhetskretsen Denna s kerhetsfunktion g r ocks att verhettnings skydden...

Страница 4: ...ts must never be changed For the T3 temperature class the temperature limiter is factory set to 150 C 2 7 The setting for the thermostat with automatically reset must never be higher than 60 C 3 0 Ele...

Страница 5: ...uipped with temperature limiters and thermostat that is fail safe i e if the capillary tube should rupture the safety circuits are automatically tripped This safety function also means that the temper...

Страница 6: ...mperaturbegrenzers mit manueller R ckstellung d rfen nicht ver ndert werden F r die Temperaturklasse T3 ist der Temperaturbegrenzer ab Werk auf 150 C eingestellt 2 7 Die Einstellung des Thermostaten m...

Страница 7: ...1 Der Erhitzer ist mit Temperaturbegrenzern und einem ausfallsicheren Thermostat ausger stet d h falls das Kapillarrohr platzt werden die Sicherheitskreise automatisch ausgel st Diese Sicherheitsfunkt...

Страница 8: ...15 C 1 4 50 C 40 C 1 5 1 6 1 7 VEAB Heat Tech AB 1 8 1 9 8 2 0 2 1 40 C 2 2 1 2 3 2 4 2 5 2 6 T3 150 C 2 7 60 C 3 0 3 1 1 2 1 6 7 8 3 3 2 1 10 1 1 1 2 3 3 3 4 40 C 3 5 1492 J4 JG4 4 1492 J6 JG6 6 149...

Страница 9: ...eset arm push to reset 1 5 0 5 1 1 1 2 3 9 10 1 6 0 6 1 VFL2 Ex VTL2 Ex VRA2 Ex 6 2 6 3 Intertek 0359 ITS10ATEX36956X 7 0 1 10 3 6 6 3 7 3 8 IP66 Ex e Ex d 3 9 4 0 4 1 4 2 4 3 VEAB Heat Tech AB 4 4 VF...

Страница 10: ...on step 1 B Thermostat with automatic reset limiting ourlet air temperature C Load D Interlocking E Contactor F Multi pole switch G Output control H Sensor I Safety contactor J Thermostat K High outl...

Страница 11: ...2 Grupp 2 Group 3 Grupp 3 Heater v rmare PE PE PE C C C A A V rmare Heater Heizung V rmare Heater Heizung V rmare Heater Heizung V rmare Heater Heizung V rmare Heater Heizung Steg 3 Step 3 Stufe 3 3...

Страница 12: ...N 60079 7 The duct heaters are also tested and approved by Intertek according to LVD directive IEC EN 60335 1 IEC EN 60335 2 30 and SS4364000 EMC directive IEC EN 61000 3 3 IEC EN 61000 3 11 IEC EN 55...

Страница 13: ...13 VFL2 Ex VTL2 Ex VRA2 Ex...

Страница 14: ...14 VFL2 Ex VTL2 Ex VRA2 Ex...

Страница 15: ...15 VFL2 Ex VTL2 Ex VRA2 Ex...

Страница 16: ...16 VFL2 Ex VTL2 Ex VRA2 Ex...

Страница 17: ...17 VFL2 Ex VTL2 Ex VRA2 Ex...

Страница 18: ...18 VFL2 Ex VTL2 Ex VRA2 Ex...

Страница 19: ...19 VFL2 Ex VTL2 Ex VRA2 Ex...

Страница 20: ...1 Postal Cheque Service 48 51 08 5 Bank Transfer 926 0365 Fax Int 46 451 410 80 E mail veab veab com Phone Int 46 451 485 00 Website www veab com VFL2 Ex VTL2 Ex VRA2 Ex 20 Originalspr k svenska Origi...

Отзывы: