AW 13s-63s, 13a-63a
20
Cleaning
For optimum performance, the fan heater must be cleaned on a regular basis.
Dust on the water battery’s aluminium fins reduces the air flow and its heat exchanging performance.
The battery must therefore be kept clean, which can be done in any of the following ways:
1. Blowing with compressed air.
2. Steam cleaning.
3. Spraying or rinsing with water. If the fins are greasy, add a suitable detergent.
For options 2 and 3, the fan motors must be protected against the ingress of water. When cleaning, disconnect the
fan heater from the power supply, and remove the air deflector and cleaning cover.
Also clean the fan’s protective grille and blades using a soft brush.
The interval between each cleaning depends on the environment in which the fan heater is used.
Control board LED
A red LED above the terminal indicates the mode of operation and any fault conditions as follows:
Normal operation – master
Steady light
Normal operation – slave
Slow flashing light
Sensor fault NTC input, terminal 1-2
Intermittent fast flashing light
Internal error control board self-monitoring
Two fast intermittent flashes
GB
Appendix A
Product Range Overview
Type
AW13
AW23
AW43
AW63
Voltage/Frequency
230 VAC 50/60 Hz
230 VAC 50/60 Hz
230 VAC 50/60 Hz
230 VAC 50 Hz
Power consumption 50/60 Hz
A
0.4 / 0.45
0.6 / 0.75
0.9 / 1.25
2.2
Air volume (low/medium/high speed)
m³/h
600 / 900 / 1250
900 / 1250 / 2200
1900 / 2500 / 3700
2200 / 3400 / 5200
Sound pressure level
1)
(low/medium/
high speed)
dB(A)
39 / 44 / 51
41 / 45 / 58
43 / 53 / 61
45 / 54 / 68
Horizontal range
2)
(high speed)
m
4.5
7.0
9.0
14.0
Horizontal range with AWLA
2)
(high speed)
m
6.5
10.0
12.5
19.0
Connection pipe
∅
mm
22
22
28
28
Max. operating temp. water, AW-a
°C
100
100
100
100
Max. operating temp. water AW-s
°C
150
150
150
150
Max. operating pressure (of water)
bar
10
10
10
10
Max. ambient temperature
°C
30
30
30
30
Can be ordered for version -a
X
X
X
X
Can be ordered for version -s
X
X
X
X
Weight
kg
17
23
32
46
Degree of protection
IP44
IP44
IP44
IP44
1)
Measured 5 metres in front of AW unit.
2)
The shown horizontal range applies for inlet air temperature of +40 °C and room temperature of +18 °C. The horizontal range is defined as the distance from the fan air
heater to the point where air velocity is 0.2 m/s.
Содержание AW 13a-63s
Страница 33: ...AW 13s 63s 13a 63a 33 Bilaga D Appendix D Anlage D...
Страница 34: ...AW 13s 63s 13a 63a 34 Bilaga E Appendix E Anlage E...
Страница 35: ...AW 13s 63s 13a 63a 35 Bilaga F Appendix F Anlage F...
Страница 36: ...AW 13s 63s 13a 63a 36 Bilaga G Appendix G Anlage G...
Страница 37: ...AW 13s 63s 13a 63a 37 Bilaga H Appendix H Anlage H...
Страница 38: ...AW 13s 63s 13a 63a 38 Bilaga I Appendix I Anlage I...
Страница 39: ...AW 13s 63s 13a 63a 39 Bilaga J Appendix J Anlage J...
Страница 40: ...AW 13s 63s 13a 63a 40 Bilaga K Appendix K Anlage K...
Страница 41: ...AW 13s 63s 13a 63a 41 Bilaga L Appendix L Anlage L...
Страница 42: ...AW 13s 63s 13a 63a 42 Bilaga M Appendix M Anlage M...
Страница 43: ...AW 13s 63s 13a 63a 43 Bilaga N Appendix N Anlage N...
Страница 45: ...AW 13s 63s 13a 63a 45...
Страница 46: ...AW 13s 63s 13a 63a 46...
Страница 47: ...AW 13s 63s 13a 63a 47...