Manual MC3-TM  Temperature Monitor 

 

            Documentnr.: 131083  version 2.1 

 

Page 11 of 16 

 

6.6.

 

Restart application 

 

 

After restoring a backup or after changing the “Temperature Monitor config” the new configuration 

should  be  used  by  the  controller.  By  pressing  the  “Restart  the  application”  button,  the 

controlprocess on the MC3-TM is stopped and started again using the new configuration. 

6.7.

 

Modbus access 

 

 

By default no system has Modbus access to the MC3-TM. In order to give a system access to the 

Modbus registers and values, its access needs to be granted. On the “Modbus access” screen this 

access can be granted. 

Enter an IP address in the field at the top (“Enter IP number to give access:”) and press the button 

“Submit”.  The  entered  IP  address  will  be  added  to  the  list  of  permitted  systems.  If  the  newly 

entered  IP  address  is  not  shown  directly  in  the  whitelist  (list  of  permitted  systems),  press  the 

“refresh” button, to refresh the list. 

To remove a system from the whitelist, select the radio button in front of its IP address and press 

the button “remove”. 

Содержание MC3-TM

Страница 1: ...Description MC3 TM Temperature Monitor Pages 16 Doc nr 131083 Type Manual By RK Version V2 1 File Do131083 MC3 TM Manual V20 Signature Date 07 12 2015 VDH Products BV MC3 TM Manual ...

Страница 2: ...erature Monitor config 8 6 2 Config overview 9 6 3 Hardware config 9 6 4 Backup configuration 10 6 5 Restore configuration 10 6 6 Restart application 11 6 7 Modbus access 11 6 8 Date Time settings 12 7 Alarms 13 8 Diagrams of connections 14 9 Dimensions 16 The information contained in this document is assumed to be accurate However VDH Products BV accepts no liability for eventual mistakes or erro...

Страница 3: ...serial connection for service purposes Power supply 12 VC DC Power consumption Measurement range 50 0 C 50 0 C Accuracy Inputs 2x Pt1000 2 wire temperature sensors 2x Dig in potential free contact Outputs 1x Analog out for SSR Solid State Relay 7x Analog out spare Housing MC3 DIN rail mounting Dimensions 110 x 191 x 100mm lhd Operating temperature Operating RH ...

Страница 4: ...easurement range Also a delay can be configured in order to wait an amount of time before raising an alarm This delay can be set per measurement and for both the minimum and maximum temperature limit The MC3 TM will be connected to a TCP IP network and can be set to use a static IP address or to use a DHCP server to obtain one Settings can be read out and altered using a software program which con...

Страница 5: ...ess of the MC3 the IP address can be obtained Start the program and select an interface Press scan to search for available MC3 controllers All found devices will be listed Both MAC address and IP address will be shown The MAC address of the MC3 TM is printed on a sticker which is placed on the mainboard Using this MAC address the device can be selected in the list Select the device and alter the n...

Страница 6: ...12 Minimum alarm temperature hot water R W A 50 0 50 0 C 30 0 13 Maximum alarm temperature hot water R W A 50 0 50 0 C 40 0 20 Minimum alarm delay cold water R W B 0 99 Minutes 0 21 Maximum alarm delay cold water R W B 0 99 Minutes 0 22 Minimum alarm delay hot water R W B 0 99 Minutes 0 23 Maximum alarm delay hot water R W B 0 99 Minutes 0 91 Log interval R W B 1 120 Minutes 1 95 Software version ...

Страница 7: ...t water A 50 0 50 0 C 06 Maximum alarm temperature hot water A 50 0 50 0 C 07 Minimum alarm delay cold water B 0 99 Minutes 08 Maximum alarm delay cold water B 0 99 Minutes 22 Minimum alarm delay hot water B 0 99 Minutes 23 Maximum alarm delay hot water B 0 99 Minutes 91 Log interval B 1 120 Minutes 95 Software version B 96 Serial number B 97 Production date B 1 Modbus register 100 can only be wri...

Страница 8: ...can be accessed Access to the shown service interface is obtained by using the following URL http 192 168 250 245 config On the left of the screen different configurations can be selected 6 1 Temperature Monitor config This screen shows how the MC3 TM uses the available connections e g how to connect the temperature sensors and alarm output The available options are shown and every configured conn...

Страница 9: ...8 options are possible since the output board has 8 analog outputs By selecting the button Submit at the bottom the selected configuration will be saved on the MC3 TM and it is ready for use It will be used when the MC3 TM is rebooted or when the control application is restarted see 6 6 Restart application 6 2 Config overview This screen shows an overview of the same configuration used in the Temp...

Страница 10: ... they will be show in this screen and they can be downloaded to a PC Saving a backup on another system than the MC3 TM is recommended to be able to restore the backup in case of a hardware failure 6 5 Restore configuration The Restore configuration screen provides the possibility to restore a backup which was previously made Backups which are stored on the MC3 can be selected or a backup file whic...

Страница 11: ...Modbus access to the MC3 TM In order to give a system access to the Modbus registers and values its access needs to be granted On the Modbus access screen this access can be granted Enter an IP address in the field at the top Enter IP number to give access and press the button Submit The entered IP address will be added to the list of permitted systems If the newly entered IP address is not shown ...

Страница 12: ...y pressing the button Update values the displayed date and time are refreshed and by pressing the button Set time the entered values are used in the MC3 TM for date and time When a timeserver is present in the network it can be used to synchronize time In order to use the timeserver enter its name or IP address in the fields and press Test TimeServer The controller will try to reach the timeserver...

Страница 13: ...figured minimum alarm value Raise the temperature of the cold water or lower the minimum alarm temperature value Reg 10 3 Maximum alarm cold water The measured cold water temperature is above the configured maximum alarm value Lower the temperature of the cold water or raise the minimum alarm temperature value Reg 11 4 Minimum alarm hot water The measured hot water temperature is below the configu...

Страница 14: ...n 2 1 Page 14 of 16 8 Diagrams of connections The MC3 TM controller consists of two different PCB s A Processor board at the bottom and a sensor board at the top These diagrams from connection drawing 131081w2 shows how to make the connections to these boards ...

Страница 15: ...Manual MC3 TM Temperature Monitor Documentnr 131083 version 2 1 Page 15 of 16 ...

Страница 16: ...Manual MC3 TM Temperature Monitor Documentnr 131083 version 2 1 Page 16 of 16 9 Dimensions Drawing with dimension of the MC3 TM housing ...

Отзывы: