Series 616
OPERATION
893179ED.DOCX
Edition 2020-01-22
25/56
5.1.1
Local operation
Local operation means that the valve is operated via the service port using a computer. When using a
computer, a USB A–B cable male-male required.
You can use our Software 'Control Performance Analyzer' 4.0 for Local operation, which is integrated in
the IC2 controller.
The software are beneficial especially for setup, testing and maintenance.
How to start:
1. Connect service cable (USB A–B cable male-male) between PC and valve controller “SERVICE”.
Refer to chapter: «Service port connection»
2. The window ‘CPA.exe’ opens.
3. Click [‘CPA.exe’]
4. The CPA 4.0 opens
5. Click [Local] for Local operation
6. Do the configuration according to your application needs.
'Control Performance
Analyzer' supports:
•
Valve setup
•
Interface setup
•
Manual control
•
Sequence control
•
Numeric and
graphical
monitoring
•
Data recording
•
Data analysis
•
Advanced
diagnostic
When communication to service port is interrupted the valve will change to remote
operation. So when service cable will be disconnected or software will be shut down,
the valve returns automatically to remote operation. This may result in an immediate
movement of the valve depending on remote control.