INSTALLATION
Series 616
18/56
Edition 2020-01-22
893179ED.DOCX
4.5
Electrical connection
NOTICE
Wrong connection
Wrong connection may result in damage of controller or power supply.
Connect all cables exactly as shown in the following descriptions and schematics.
NOTICE
Burned connector pins (spark)
Connector pins or electronic parts could damage, if plugged and unplugged under
power.
Do not plug or unplug connectors under power.
4.5.1
Ground connection
Recommendation for ground connection between controller and system chassis.
Recommendation for ground connection cable: AWG 12 (4 mm
2
)
The connection point at chassis (FE) must be blank metal (not coated).
Controller bottom side
Recommended torque: 1,3…1,7Nm
Chassis (FE)
(Functional Earth)