55
Lift the battery module from the holding rails.
Installing the battery module
Reinstall the battery module in exactly the reverse order. (See chapter: 11.14 “Battery
module assembly”, page 37.)
Clean ventilator and air filter
The air filter must be replaced at every second service. The ventilator is accessible after the hood is
opened.
Clean the grid on the air filter.
Clean the air filter with a vacuum cleaner or replace it.
Check the ventilator for soiling and clean it if necessary.
Check the bearing clearance and the free movement of the ventilator by hand.
If the ventilator needs to be replaced, please contact VARTA Storage.
Completing service and repair works
DANGER
Touching live parts.
Danger to life.
Remove all tools and/or small parts from the interior.
Create all the cable connections correctly.
Check all the cable ducts.
Check all the safety equipment.
Ensure that there are no persons in the danger zone before switching on
the energy.