STAGE 1 DUTY CYCLE PERIOD
The Stage 1 duty cycle period is adjusted in
conjunction with the Stage 1 duty cycle timer
(primary function 3). The Stage 1 duty cycle
period is the total time in ON-OFF fan cycle.
The period is adjusted in 1 minute increments
from a setting of 1 minute to a maximum setting
of 10 minutes.
Adjusting the Stage 1 duty cycle period:
•
rotate the Selector dial to position (12),
•
rapidly rotate the Adjustor dial back and
forth to enter secondary function mode,
•
rotate the Selector dial to position (3),
•
rotate the Adjustor dial counterclockwise to
decrease the period, clockwise to increase
it.
The Stage 1 period setting is displayed on the
MST-1.
Period
CHAPTER 3 - USER’S GUIDE