background image

                                                                                                                 

Page 37  

CHAPTER 3 - USER GUIDE 

 
 
 
 

FAN 1 DIFFERENTIAL 

 
 
The Fan 1 differential setting establishes the 
temperature at which Fan 1 reaches maximum 
speed. The value is a temperature 

difference 

from the main set point. 
 
The Fan 1 differential is adjusted in 0.5 degree 
increments from a minimum setting of 2.0°F 
(1.0°C) to a maximum setting of 18.0°F (10.0°
C). 
 
 

Adjusting the Fan 1 differential:

 

rotate the Selector dial to position (12), 

rapidly rotate the Adjustor dial back and 
forth to enter secondary function mode, 

rotate the Selector dial to position (3), 

rotate the Adjustor dial counterclockwise to 
decrease the period, clockwise to increase 
it. 

 
The Fan 1 Differential setting is displayed on 
the ECS. 

 

Example: 

 

 

 

 

A main set point 

temperature of 70°F along with a 
Fan 1 differential setting of 5°F is 
set. When the temperature of the 
room reaches 75°F, Fan 1 
operates at its maximum speed. 

       Diff 

Содержание ECS 5M

Страница 1: ... computer compatible 1 2 3 4 5 MIN SPEED TIMER on off M O T O R MIN SPEED F A N 5 FAN 4 FAN 3 ADJUST A L A R M A L ARM F A N 1 rel reduc per day LO HI L IM I T D IF F F A N 2 D IFF TIMER rel H E AT 5 5 Varifan ECS 5M 6 5 1 2 3 4 10 11 7 8 9 12 ECS 5M USER S MANUAL ...

Страница 2: ... equipment For added security against line voltage surges it is recommended that surge and noise suppression devices be installed at the electrical distribution panel Use of shielded cable for probes is recommended for protection against lightning These devices are available from most electrical supply distributors RECOMMENDATIONS The manufacturer recommends that all installation procedures descri...

Страница 3: ... 1 115 VAC 11 2 4 1 2 230 VAC 12 2 4 2 Fan 1 12 2 4 3 Fan 2 12 2 4 4 Fan 3 12 2 4 5 Fan 4 Drip Cool 12 2 4 6 Fan 5 Heater 12 2 5 Temperature Humidity Probes 13 2 5 1 Single Temperature Probe 13 2 5 2 Averaging 13 2 5 3 Humidity Probe 13 2 6 Alarm 13 2 7 Powering Up 14 CHAPTER 3 USER GUIDE LED Status Window 21 Control Dials 21 PRIMARY FUNCTIONS Main Set Point Temperature 23 Fan 1 Minimum Speed 24 F...

Страница 4: ...re 33 Ambient Room Display 34 SECONDARY FUNCTIONS Relative Humidity Set Point 35 Fan 1 Motor 36 Fan 1 Differential 37 Fan 2 Differential 38 Fan 2 Motor 39 Drip Cool duty cycle 40 Heater Fan 5 Differential 41 Minimum Ramping 42 Low Temperature Alarm 43 High Temperature Alarm 44 Relative Humidity Display 45 APPENDIX Motor Compatibility Table 47 Troubleshooting 48 Specification 49 Record Form 50 ...

Страница 5: ...e with IPM 1 and DIP 1 Hi Lo temperature indication Automatic temperature reduction ramping Adaptable variable speed outputs for a wide selection of fan model types Humidity probe Full torque fan start preventing motor damage The ECS 5M provides microprocessor control over a five stage output The first stage controls a variable speed fan which can operate at a continuous low speed to ensure good q...

Страница 6: ...ly informed by displaying the status of all of its outputs as well as the ambient temperature With an optional humidity probe the ECS 5M displays current humidity levels Safety of livestock is ensured by the continuous control of climate and timely alarm notification should environmental conditions exceed alarm set points Further security may be obtained by connecting all ECS series controls in a ...

Страница 7: ...INIMUM FAN SPEED The desired minimum speed for variable speed fans RAMPING An automatic daily reduction in the main set point and all temperature settings relative to this DIFFERENTIAL ON OFF relay Range of temperature where two conditions are possible The output depends on whether the temperature was increasing or decreasing when it enters that range VARIABLE Bandwidth Temperature range where a v...

Страница 8: ...Page 8 ECS 5M ...

Страница 9: ...erature probe model number 2004 1K 5 cable fasteners or fuses 1 User s manual The following optional items may be included 3 additional temperature probes for temperature averaging 1 humidity probe The ECS 5M requires the RHT 1 humidity probe for maximum accuracy of monitoring and control of humidity levels The manufacturer recommends that the installation instructions which follow be adhered to a...

Страница 10: ... as follows 2 3 1 Line Voltage Selector Switch This switch is located on the surface of the main bottom board and adapts the control panel for 115 VAC or 230 VAC line voltage To limit the unit s exposure to noxious gases install the unit in a hallway Make certain that the unit is mounted right side up with the cable entry holes facing down The ECS 5M will operate in a temperature range of 32 F 120...

Страница 11: ...witch 4 must be at ON 2 4 CONNECTION PROCEDURE For the connection procedures which follow refer to Figures 1 through 3 2 4 1 Input power Use a screwdriver to remove cable knock outs for the installation of cabling to the ECS 2 4 1 1 115 VAC Make certain that the line voltage selector switch is set to 115 VAC Connect the power cable to terminals 11 and 12 on the main bottom board connect the ground...

Страница 12: ...nnect the second wire of the fan to N neutral For a 230V fan connect the second wire of the fan to L2 2 4 5 Fan 4 Drip Cool Stage 4 provides a dry contact closure which controls the operation of a fourth single speed fan or a drip cool unit This contact closure is voltage rated to 230 VAC The current rating of the dry contact is 6 Amps conductive for a fan Make connections as follow Connect L1 to ...

Страница 13: ...he temperature probe to the ECS terminals labelled Probe as indicated in Figure 4 2 5 2 Averaging optional Four temperature probes are required if temperature averaging is desired in larger rooms Place the probes in appropriate locations to best average the ambient temperature Refer to Figure 5 2 5 3 Humidity Probe optional Install one humidity probe in an area that best reflects the overall humid...

Страница 14: ...of it s LED Make certain that all segments light Following the LED display test the unit displays the ambient temperature of the room If the temperature is not displayed refer to the Trouble Shooting section in the appendix of this document Fig 1 Four Fans 115V and One Heating Unit 115V Momentary power interruptions may trigger false alarms To avoid false alarming when the ECS is connected to an a...

Страница 15: ...Page 15 Fig 2 Five Fans 230V Fig 3 Four Fans 230V and One Heating Unit 115V CHAPTER 2 INSTALLATION ...

Страница 16: ...fans that have thermal protection devices Terminals 8 10 and 11 are internally connected Connect the grounding wire to the ground terminal 13 IMPORTANT Must be on a 15A separate circuit of the ECS Make sure to disconnect power of the source and all loads before wiring 1 2 4 3 Fig 4 Probes and Alarm Wiring 5 ...

Страница 17: ... 17 Fig 5 Temperature Averaging Probe Connection Fig 6 Main Board Terminal Blocks Switches Fuses and Ground PROBES AUX ALARM 10A Slo Blo Fan 2 10A Slo Blo Fan 1 1047 Ground Connection CHAPTER 2 INSTALLATION ...

Страница 18: ...reach the T15 WD set value Therefore the T15 WD should be accessible for its adjustment and it should be set at the same temperature as the alarm i e approximately 5ºF above the fan relative set point BACKUP POWER SOURCE The DPDT relay connects to the source 1 in normal operation but will switch to the source 2 if source 1 is off The relay shall be chosen to support the load connect to it ALARM CI...

Страница 19: ...Page 19 Fig 7 Recommended control backup CHAPTER 2 INSTALLATION L1 L2 L1 L2 5 5 5 5 IMPORTANT Must be on a 15A independant circuit ...

Страница 20: ...Page 20 ECS 5M ...

Страница 21: ... lights to indicate a low or high temperature alarm condition CONTROL DIALS The center dial is the Selector dial and is used to select one of the control panel s 12 primary or 11 secondary functions The dial located to the right of the Selector dial is the Adjustor dial and is used to enter secondary function mode and to adjust the setting of each function NOTE M O T O R D I F F RH RH F2 ENVIRONME...

Страница 22: ...nking value Function 12 displays ambient temperature The 11 secondary functions are 1 Relative humidity setting 2 Fan 1 motor compatibility 3 Fan 1 differential temperature 4 Fan 2 differential temperature 5 Fan 2 motor compatibility 7 Drip Cool duty cycle timer 8 Fan 5 Heater differential 9 Ramping minimum temperature limit 10 Low temperature alarm 11 High temperature alarm 12 Relative humidity d...

Страница 23: ...crements from a minimum setting of 13 5 F 9 5 C to a maximum setting of 105 0 F 41 0 C Adjusting the main set point temperature rotate the Selector dial to position 1 rotate the Adjustor dial counterclockwise to decrease the temperature setting clockwise to increase it The main set point temperature is displayed on the ECS 1 Note The ramping feature primary function 9 must be OFF to adjust the mai...

Страница 24: ... in 2 increments from a minimum setting of 12 to a maximum setting of 100 Adjusting the minimum speed of Fan 1 rotate the Selector dial to position 2 rotate the Adjustor dial counterclockwise to decrease fan speed clockwise to increase it The minimum fan speed is displayed on the ECS NOTE Upon start up Fan 1 will run at its maximum speed for 4 seconds This feature aids Fan 1 in attaining its set s...

Страница 25: ...uty cycle is adjusted in 5 increments from a minimum setting of OFF 5 10 etc up to a maximum setting of ON corresponding to continuous operation Adjusting the duty cycle of Fan 1 rotate the Selector dial to position 3 rotate the Adjustor dial counterclockwise to decrease the duty cycle clockwise to increase it The duty cycle is displayed on the ECS Example The duty cycle is set to 30 As long as th...

Страница 26: ...crements from a minimum setting of 0 0 F 0 0 C to a maximum setting of 18 0 F 10 0 C Adjusting the relative set point of Fan 2 rotate the Selector dial to position 4 rotate the Adjustor dial counterclockwise to decrease the relative set point clockwise to increase it The Fan 2 relative set point is displayed on the ECS Example A main set point of 70 F along with a Fan 2 relative set point of 5 F i...

Страница 27: ...ncrements from a minimum setting of 12 to a maximum setting of 100 Adjusting the minimum speed of Fan 2 rotate the Selector dial to position 5 rotate the Adjustor dial counterclockwise to decrease fan speed clockwise to increase it The minimum fan speed is displayed on the ECS NOTE Upon start up Fan 2 will run at its maximum speed for 4 seconds This feature aids Fan 2 in attaining its set speed as...

Страница 28: ...0 C to a maximum setting of 30 0 F 16 0 C Note The differential on fan 3 is not adjustable and the default value is set at 2 F 1 C Adjusting the relative set point of Fan 3 rotate The Selector dial to position 6 rotate the Adjustor dial counterclockwise to decrease the relative set point clockwise to increase it The Fan 3 relative set point is displayed on the ECS Example A main set point of 70 F ...

Страница 29: ...ting of 30 0 F 16 0 C Note The differential on fan 4 is not adjustable and the default value is set at 2 F 1 C Adjusting the relative set point of Fan 4 Drip Cool rotate the Selector dial to position 7 rotate the Adjustor dial counterclockwise to decrease the relative set point clockwise to increase it The Fan 4 Drip Cool relative set point is displayed on the ECS Example A main set point of 70 F ...

Страница 30: ...ee increments from a minimum setting of 9 0 F 5 0 C to a maximum setting of 30 0 F 16 0 C Adjusting the Heater Fan 5 relative temperature rotate the Selector dial to position 8 rotate the Adjustor dial counterclockwise to decrease the temperature setting clockwise to increase it The relative temperature setting is displayed ECS Example The main set point temperature is adjusted to 70 F A heater is...

Страница 31: ...ase the ramping rate clockwise to decrease it The ramping setting is displayed on the ECS NOTE When ramping is activated or enabled the main set point temperature cannot be manually adjusted Ramping automatically turns OFF when the minimum temperature limit is reached Example The main set point temperature is set to 70 F and ramping is adjusted to 0 05 F The following day the main set point temper...

Страница 32: ...degree from a minimum display of 13 5 F 10 0 C to a maximum display of 105 0 F 40 5 C If a temperature lower than 13 5 F is recorded Lo is displayed Viewing the lowest temperature recorded rotate the Selector dial to position 10 Clearing the low temperature value quickly rotate the Adjustor dial counterclockwise then clockwise CLr will be briefly displayed on the ECS LO ...

Страница 33: ...nimum display of 13 5 F 10 0 C to a maximum display of 105 0 F 40 5 C If a temperature higher than 105 0 F is recorded Hi is displayed Displaying the highest temperature recorded rotate the Selector dial to position 11 Clearing the high temperature value quickly rotate the Adjustor dial counterclockwise then clockwise CLr will be briefly displayed on the ECS HI CHAPTER 3 USER GUIDE ...

Страница 34: ...nt temperature is displayed to the nearest 0 5 degree from a minimum display of 13 5 F 10 0 C to a maximum display of 105 0 F 41 0 C If the temperature is lower than 13 5 F Lo is displayed If the tem perature is higher than 105 0 F Hi is displayed Viewing the ambient temperature rotate the Selector dial to position 12 The ambient temperature is displayed on the ECS 12 ...

Страница 35: ...he fan operates at this increased speed for as long as the ambient room temperature is below the main set point When the temperature of the room is greater than the main set point temperature the fan speed increases until the maximum speed as been reached The humidity level is adjustable in 1 increments from a minimum setting of 30 to a maximum setting of 80 Adjusting the relative humidity level r...

Страница 36: ...ce with your fan Settings 2 8 are the optimized settings for fan models listed in the compatibility table Using the compatibility table find the model number of your fan motor and take note of the fan motor compatibility number Setting the Fan 1 motor compatibility rotate the Selector dial to position 12 rapidly rotate the Adjustor dial back and forth to enter secondary function mode rotate the Se...

Страница 37: ... F 10 0 C Adjusting the Fan 1 differential rotate the Selector dial to position 12 rapidly rotate the Adjustor dial back and forth to enter secondary function mode rotate the Selector dial to position 3 rotate the Adjustor dial counterclockwise to decrease the period clockwise to increase it The Fan 1 Differential setting is displayed on the ECS Example A main set point temperature of 70 F along w...

Страница 38: ...e Fan 2 differential rotate the Selector dial to position 12 rapidly rotate the Adjustor dial back and forth to enter secondary function mode rotate the Selector dial to position 4 rotate the Adjustor dial counterclockwise to decrease the differential setting clockwise to increase it The Fan 2 differential setting is displayed on the ECS Example The main set point temperature of the room is 70 F A...

Страница 39: ...an Settings 2 8 are the optimized settings for fan models listed in the compatibility table Using the compatibility table find the model number of your fan and take note of the fan motor compatibility number Setting the Fan 2 motor compatibility rotate the Selector dial to position 12 rapidly rotate the Adjustor dial back and forth to enter secondary function mode rotate the Selector dial to posit...

Страница 40: ...N time is entered as a percentage of a 12 minutes period If a fan is used set this value at 100 Adjusting the duty cycle setting rotate the Selector dial to position 12 rapidly rotate the Adjustor dial back and forth to enter secondary function mode rotate the Selector dial to position 7 rotate the Adjustor dial counterclockwise to decrease the duty cycle setting clockwise to increase it The duty ...

Страница 41: ... of 6 F 3 C degrees Adjusting the differential setting rotate the Selector dial to position 12 rapidly rotate the Adjustor dial back and forth to enter secondary function mode rotate the Selector dial to position 8 rotate the Adjustor dial counterclockwise to decrease the differential setting clockwise to increase it The differential setting is displayed on the ECS Diff Example The heater Fan 5 re...

Страница 42: ...sting the minimum ramping setting rotate the Selector dial to position 12 rapidly rotate the Adjustor dial back and forth to enter secondary function mode rotate the Selector dial to position 9 rotate the Adjustor dial counterclockwise to decrease the minimum ramping setting clockwise to increase it The minimum ramping setting is displayed on the ECS Limit NOTE When the main set point temperature ...

Страница 43: ...alarm is adjusted in 0 5 degree increments from a minimum setting of 32 0 F 18 0 C to a maximum setting of 0 0 F 0 0 C Adjusting the low temperature alarm setting rotate the Selector dial to position 12 rapidly rotate the Adjustor dial back and forth to enter secondary function mode rotate the Selector dial to position 10 rotate the Adjustor dial counterclockwise to decrease the setting clockwise ...

Страница 44: ...The high temperature alarm is adjusted in 0 5 degree increments from a minimum setting of 0 F 0 C to a maximum setting of 32 0 F 18 0 C Adjusting the high temperature alarm rotate the Selector dial to position 12 rapidly rotate the Adjustor dial back and forth to enter secondary function mode rotate the Selector dial to position 11 rotate the Adjustor dial counterclockwise to decrease the setting ...

Страница 45: ...maximum display of 90 If a humidity level lower than 30 is sensed F2 is displayed Conversely if a humidity level higher than 90 is sensed 90 stay displayed Displaying the humidity level rotate the Selector dial to position 12 rapidly rotate the Adjustor dial back and forth to enter secondary function mode The humidity level is displayed on the ECS RH CHAPTER 3 USER GUIDE ...

Страница 46: ...Page 46 ECS 5M ...

Страница 47: ... 18 3 Multifan 6E56 230 v 22 3 Multifan AF AF36M 230 v 36 3 Leeson 1 2H PAF20L 115 v 20 3 Leeson 1 2HP AF24L 115 v 24 3 Aerotech F AT242 230 v 24 4 Multifan 2E25 230 v 10 4 Leeson 1 4HP AF14L 115 v 14 4 Leeson 1 4HP AF16L 115 v 16 4 Marathon 1 4HP 230 v 16 4 Marathon 1 3HP 230 v 18 4 Leeson 1 3HP AF18L 115 v 18 5 GE Motor 5KCP39 230 v 12 5 Leeson 1 4HP AF12L 230 v 12 5 GE Motor 5KCP39 230 v 14 5 E...

Страница 48: ... Figure 6 for fuse location If fuse is blown replace with fuse of same type Stage 5 Fan or Heater is operating erratically Verify that the software setting switch located at the rear of the faceplate is properly set Verify the minimum rating 10mA at 230V or 20mA at 230V Display is blank Verify that the line voltage selector switch is properly set Verify that the 10 pin flat cable between the main ...

Страница 49: ... Fused 10 AMP 115V 230V 1 2 HP 115V 1 HP 230V Min Rating 10mA at 115V 20mA at 230V STAGE 4 dry relay contact Not Fused 10 AMP 115V 230V 1 2 HP 115V 1 HP 230V Min Rating 10mA at 115V 20mA at 230V STAGE 5 dry relay contact Not Fused 10 AMP 115V 230V 1 2 HP 115V 1 HP 230V Min Rating 10mA at 115V 20mA at 230V ALARM dry relay contact 2 AMP 30V AC DC SPECIFICATIONS APPENDIX Relay will not function prope...

Страница 50: ...e Differential 2 F 1 C 9 Minimum Ramping Limit 65 F 18 C 10 Low Temperature Limit 9 F 5 C 11 High Temperature Alarm 20 F 12 C RECORD FORM 2nd Function 1 Main Set Point Temperature 77 F 25 C 2 Fan 1 Minimum Speed 24 24 3 Fan 1 Duty Cycle Timer ON ON 4 Fan 2 Relative Set Point 4 F 2 C 5 Fan 2 Minimum Speed 24 24 6 Fan 3 Relative Set Point 8 F 4 C 7 Fan 4 Drip Cool Relative Set Point 10 F 5 C 8 Heate...

Страница 51: ...ood fire hail lightning or any other natural disaster Any unauthorized work modification or repair on this product automatically voids the warranty and disclaims the manufacturer from all responsibility The manufacturer assumes only those obligations set forth herein excluding all other warranties or obligations This warranty stipulates that in all cases the manufacturer shall be liable only for t...

Страница 52: ...MAV ECS 5M Ver 03 June 2001 ...

Отзывы: