Technical Manual: TM80030
THERMICA WATER TO AIR COOLER
Model range: THERMICA10-VV-MMM-LLL
Revision: 1.0
Date of release: 2022-12-16
47/55
www.vareximaging.com
Figure 18: Pump curve
9.2.
Water specifications
All parameters that are not in line with the directive (EU) 2020/2184 ANNEX I, are listed below.
Parameter
Parametric max value Unit
Conductivity
1500
µS/cm at 20°C
Chloride
100
mg/l
pH value
6.0 – 8.5
pH units
Hardness
<12
°dH
0
1
2
3
4
5
6
7
8
0
1
2
3
4
5
6
7
8
9
Fl
ow
(
l/m
in)
Pressure (Bar)
PUMP CURVE