Technical Manual: TM80030
THERMICA WATER TO AIR COOLER
Model range: THERMICA10-VV-MMM-LLL
Revision: 1.0
Date of release: 2022-12-16
34/55
www.vareximaging.com
5.6.
Parameter settings
Parameter
Factory
setting
Description
Setting range
A0
1
Assignment of alarm sensors, detailed description of
sensors in parameters H11 through H53.
0: none, 1: Sensor F1, 2: Sensor
F2, 3: Sensor F3, 4: Sensor F4,
5: weighted mean value from F1
and F2
A3
1
Switching mode of alarm relay
0: on if alarm present (normal)
1: off if alarm present (inverse)
A4
1
Switching hysteresis for alarm
0.1 … 15 °C
A6
35 °C
Upper absolute alarm limit
A7 … +999°C
A7
5 °C
Lower absolute alarm limit
-99°C … A6
A14
0
Behavior if temperature alarm disappears again
0: without buzzer, delete
automatically
1: with buzzer, delete
automatically
2: without buzzer, with
acknowledgment
3: with buzzer, with
acknowledgment
A15
1
Function buzzer and/or display in the case of alarm
(temperature alarm)
0: no display, no buzzer
1: display flashing only
2: buzzer active only
3: display flashing, buzzer active
4: like 2., can be acknowledged
5: like 3., buzzer can be
acknowledged
A35
129 bin
Alarms for alarm "Notify 1"
Binary mask:
+1: Sensor error E1x
+2: Sensor error E2x
+4: Sensor error E3x
+8: Sensor error E4x
+16: Sensor error E5 Door
+32: Sensor error E6 High
Pressure
+64: Sensor error E7 Low
pressure
+128: Temperature alarm
A36
0 bin
Alarms for alarm "Notify 2"
Same as A35
A37
0 bin
Alarms for alarm "Notify 3"
Same as A35
C0
1
Assignment of cold store sensors
See setting range A0
C1
33 °C
Setpoint for Set 1
C8…C7
C4
1
Switching mode
0: heating, 1: refrigerating
C5
1 °C
Hysteresis
0.1 … 15 °C
C6
0
Hysteresis mode
0: symmetrical, 1: one-sided
C7
50 °C
Upper setpoint limit
C8 … +999°C
C8
20 °C
Lower setpoint limit
-99°C … C7
F50
1
Assignment of condenser sensor.
0-5
F55
1
Mode on sensor error
0: normal switched with
compressor 1: Fan speed in F56