Technical Manual: TM80030
THERMICA WATER TO AIR COOLER
Model range: THERMICA10-VV-MMM-LLL
Revision: 1.0
Date of release: 2022-12-16
45/55
www.vareximaging.com
9.
Specifications and accessories
This chapter gives specifications (technical and product label information) and information about available
accessories.
9.1.
Technical specifications
Classifications
See section §2.7
Application
Stationary cooling equipment (see §2.1)
Materials – hydraulic circuit
Copper, brass, tin (brazing material), stainless steel, VMQ, NBR,
PPE+PS
Power source
230 [VAC] ± 10% / 3.4 [A] 50/60 [Hz]
Overvoltage category
II
Pollution degree
2
Power supply (internally only,
unregulated)
24 [VDC] ± 15% / 100 [mA] / 1 [VA]
Fuse Mains
Littlefuse 0234005.MXBP
230 [VAC], 5 [A], medium acting, 5x20 [mm]
Monitoring circuit (external)
24 [VDC] / 100 [mA]
Fuse Polyswitch
(controller, transformer)
240 [VAC], I
hold
= 0.25 [mA], I
trip
= 0.56 [mA]
Flow switch
Normally open; reed switch; 24 [VDC] / 100 [mA]
Level switch
Normally open; reed switch; 24 [VDC] / 100 [mA]
Dimensions (L x H x W]
423 x 448 x 447 [mm]
Dry weight
33 kg
Coolant filter
160 µm
Interface – hydraulic
3/8-inch female thread BSPP
Interface – electrical
Binder 3 pins + PE
Binder 12 pins
Operation environment
Ambient temperature: +5 – +40 [°C]
Relative humidity:
20 – 90 % RH, non-condensing
Atm. Pressure:
altitude <2000 [m]
Environment:
industrial
Transport and storage
Ambient temperature: -20 – +70 [°C]
Relative humidity:
30 – 95 % RH, non-condensing
Withstand normal means of transport (no damage or
performance lost)
Ingress protection
Cooler – IP21
Controller front – IP65
Pump motor – IP55
Fan – IP54
Level switch – IP65
Flow switch – IP65