I N S T A L L A T I O N

 

 

©Vantage, 11/6/2014 / IS-0602-A 

InFusion Controller II — MODEL: IC-36-II & IC-24-II 

page 7 of 7 

InFusion Controller and Main Enclosure Terminal Board 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Possible Ground Loop Issues 
All RS-232/RS-485 connections between 

third party

 equipment and RS-232/RS-485 connections on the Main Enclosure Terminal 

Board, 

may

 produce a ground loop. Often the third party connected RS-232/RS-485 device is not using the same power source or is far 

away from the Vantage enclosure resulting in a possible ground loop or data noise condition. If this condition is suspected, Vantage 
recommends a third party RS-232/RS-485 Opto (optical) Isolation connection. Opto Isolation provides a communications link and is an 
important consideration if a system uses different power sources, has noisy signals or must operate at different ground potentials. 

Содержание InFusion Controller II

Страница 1: ...hernet 15 Controllers maximum on each Controller to Controller Bus run InFusion Controller Specifications Description Specification Dimensions HWD 6 62 x 7 88 x 3 0 168mm x 200mm x 76mm Description Specification Weight 24V 3 55 lbs or 1 61 kg Weight 36V 4 4 lbs or 2 kg Voltage 120 240V 50 60Hz Lightning Surge Protection Static Shock IO All ports case IEC 61000 4 2 Low Voltage ITU T K 20 Max Length...

Страница 2: ...ler If the IP address is correct change the connection to standard Ethernet and re download the controller firmware This procedure will also require the system to be re programmed after the firmware update Updating all controllers firmware shipped with Design Center 3 3 or higher should clear this error for future SSL connections Remote Programming and Maintenance Remote programming and update cap...

Страница 3: ...in the Design Center project file for future connections through Ethernet SCREEN 7 CONTROLLER INFORMATION This screen shows information about the IC Uptime the amount of time the IC has been operating without losing power reported in days hours minutes RAM Free Memory Total Memory o RAM This is the active memory Random Access Memory and is volatile Flash Free Memory Total Memory o Flash memory is ...

Страница 4: ...I N S T A L L A T I O N Vantage 11 6 2014 IS 0602 A InFusion Controller II MODEL IC 36 II IC 24 II page 4 of 7 ...

Страница 5: ...ecurity Level is set to None and no Users and Devices exist If the security level is changed to Local or Remote at least one Admin user must be added before exiting the dialog box 4 To create a user press Add User The Add New User dialog box opens 5 Enter a Username and Password and select Admin or User to assign a group 6 Press Add to add the new user a Admin have all permissions selected by defa...

Страница 6: ...ect Design Center contains the system s micro SD card Recommendation Install one micro SD card per system Backup and Restore From Design Center 1 In Design Center click on System Backup And Restore and select from a Full System Backup b Full System Restore c Restore Equinox Data From Backup i Option c restores Equinox profile information on controller and opens programming screen 2 If Backup is se...

Страница 7: ...ard may produce a ground loop Often the third party connected RS 232 RS 485 device is not using the same power source or is far away from the Vantage enclosure resulting in a possible ground loop or data noise condition If this condition is suspected Vantage recommends a third party RS 232 RS 485 Opto optical Isolation connection Opto Isolation provides a communications link and is an important co...

Отзывы: