                                                                          Installation 

 

ITC-Series

 Inverter 

Page 6 

 

 

 

 

 

 

 

 

 

 8/05/17 

 

System Features 

 

Inverter 

 

The inverter consists of a sine wave inverter that supplies power when AC loads are applied. Depending on 
your  model,  the  inverter  develops  2100,  3200  or  3600  watts  of  continuous  power.  Using  TruSine

®

 

technology,  a  very  high  quality  sine  wave  is  produced.  Total  harmonic  distortion  (THD)  is  less  than  4.0 
percent. 

 

Battery Charger with Automatic Power Management

 

The high efficiency, multi-stage battery charger allows automatic charging of flooded lead acid and gel type 
batteries.  The  efficient  0.85  power  factor  or  PF,  compared  to  typical  0.59PF  on  triac  pulse  type  chargers, 
allows full charger output from a 30-

amp AC source. The system’s Bulk, Absorption, and Float charge cycle 

quickly  charges  and  maintains  the  battery  bank.  An  Equalization  charge  cycle is available for flooded lead 
acid battery maintenance. In addition, there is an optional battery temperature sensor to reduce battery float 
voltage as temperature increases above 25° Celsius.  

Automatic  Power  Management  (APM)  monitors  the  AC  Input  current  and  will  reduce  the  battery  charger 
output as needed to keep the AC input current below the preset APM Limit.  

 

GenStart Contact 

The  GenStart  feature  provides  a  start/stop  signal  to  control  an  automatic  generator.  The  start/stop  signal 
consists  of  a  contact  closure  to  start  the  Gen.  Start  based  on  battery  voltage  of  12.3  (24.6)  VDC.    The 
GenStart turns off when the battery charging current falling below 10 amps. 

 

Low Battery or Fan On Contact 

The  Low  Battery  contact  allows  remote  monitoring  of  the  Inverter’s  battery  status.  The  contact  will  close 
when  battery  voltage  falls  below  11.0  (22.0) volts.  This will alert the user to take appropriate measures to 
avoid shutdown of the Inverter at 10.5 (21.0) VDC. The SP00172 offers a Fan On contact instead of the Low 
Battery contact fo

r turning on an external fan or blower when the ITC’s fan is on. 

 

Remote Power Switch 

This  loop  between  Options  Terminal  7  and  8  (left  side  of  Options  Terminal)  allow  remote  control  of  the 
system  On/Off.  Tying  these  two  terminals  together  or  optionally,  tying  the  terminal  7  (

Remote  Switch)

  to 

battery ground applies power to the unit.  

Note:

 The Front Panel switch will always overrule the remote switch in terms of disabling the unit. 

 

System Control

 

The ITC contains a System ON/OFF Switch located in the front  of the ITC.  This switch is used to turn the 
control  power  ON  and  OFF.    This  power  switch  also  has  a  break  out  loop  for  a  series  switch  that can be 
placed  in  a  remote  location  from  the  unit  (See 

Remote  Power  Switch

  above).  A  control  microprocessor 

provides a variety of protection interlocks, system fault detection/reporting/recovery, storage of system data 
parameters, and high-speed data communications to the ITC Control/Display Unit. This Control/Display Unit 
also has individual on/off switches for independent Inverter and Charger control. The ITC will protect itself in 
the event of any overload, over temperature, high or low battery voltage condition.  

 

ITC Control/Display Unit 

 

The ITC Control/Display Unit is a user interface that is connected to the ITC Control Board via a 6-wire 
modular cable.  This Control/Display unit can be an integral part of the Inverter or can be removed and 
mounted in a remote area to allowing remote system operation.  Two of these units can talk to the System 
Control Board one display would be configured as a Master, and the other as Slave.  The configuration 
switches on top of the Master allow programming of the Charger current, Automatic Power Management and 

Содержание SP00175

Страница 1: ...Manual 8 5 17 ITC Series Inverter Charger System Models SP00175 SP00176 ITC12 2100 ITC12 3200 and SP00172 Vanner Incorporated 4282 Reynolds Drive Hilliard Ohio 43026 614 771 2718 1 800 ACPOWER www van...

Страница 2: ...INCORPORATED ITC Series ITC Series Inverter Page 2 8 05 17 Notes...

Страница 3: ...WIRING IDENTIFICATION 18 AC INPUT OUTPUT WIRING 18 DC BATTERY WIRING 18 FRONT PANEL CONTROL DISPLAY OUTLET 19 SYSTEM ON OFF SWITCH 19 REMOTE SIGNAL CONTACTS 19 INSTALLATION 19 BASIC GUIDELINES 19 DC W...

Страница 4: ...7 Figure 1 4 6 Suspended Dimensions in Inches 11 F 8 Figure 1 4 7 Bottom Mount Dimensions in Inches 11 F 9 Figure 1 4 8 Control Display Unit Dimensions in Inches 11 F 10 Figure 1 4 9 Customer Terminat...

Страница 5: ...e cover of this manual System Features and Specifications General Description The ITC Series system consists of a DC to AC true sine wave inverter a battery charger an automatic AC transfer switch and...

Страница 6: ...lts This will alert the user to take appropriate measures to avoid shutdown of the Inverter at 10 5 21 0 VDC The SP00172 offers a Fan On contact instead of the Low Battery contact for turning on an ex...

Страница 7: ...Surge Capacity 25 C 3 sec 6400 watts DC INPUT Operating Range 10 5 to 17 Volts 21 0 to 31 Volts No Load Inverter ON 4 amps 3 amps No Load Inverter OFF 0 30 amps 0 30 amps Full power 208 amps 350 amps...

Страница 8: ...6 7 8 9 4 5 FRONT VIEW 13 2 14 15 16 10 LEFT SIDE VIEW RIGHT SIDE VIEW 11 12 15 16 OPTIONS CABLE ENTRY CHASSIS GROUND ITEM 1 2 3 4 5 6 7 8 9 10 11 12 13 14 DESCRIPTION BATTERY TERMINAL ACCESS REMOTE...

Страница 9: ...when enabled but not on 2 Inverter On Off Button Enables Disables Inverter Function 3 Charger Indicator Light Solid when on flashes when enabled but not on 4 Charger On Off Button Enables Disables Cha...

Страница 10: ...allowing access to user AC and control terminals through a removable front cover ACCESS PANEL REMOVABLE FROM FRONT WHEN UNDER TABLE MOUNTED DOCKED DISPLAY CONTROL PANEL DC TERMINATIONS POWER ON OFF SW...

Страница 11: ...8 5 17 18 10 7 8 19 1 4 13 5 8 16 3 4 8 1 8 7 5 16 8 3 4 ITC DIMENSIONS FOR SUSPENDED MOUNTING F 7 Figure 1 4 6 Suspended Dimensions in Inches 19 1 4 18 10 7 8 16 3 4 13 5 8 7 5 16 8 ITC DIMENSIONS F...

Страница 12: ...ITC Series Inverter Page 12 8 05 17 F 9 Figure 1 4 8 Control Display Unit Dimensions in Inches Overload Overload LowBattery Bulk Fault Fault INCOR PORATED Inverter On Off Charger On Off 3 78 3 50 3 3...

Страница 13: ...l be steadily on when the unit is in the Inverter or Charger mode These Inverter and Charger lights will blink if the mode is not currently on but are enabled Example The Inverter light will blink whe...

Страница 14: ...temperature will shut down system Overheat The SCR plate or power brick overheating will cause the system to shutdown If the unit has faulted there are the two following options 1 Auto restart After...

Страница 15: ...uring the Equalize Cycle the battery is charged at the Absorption Charge Amps setpoint and the Equalize Voltage 15 5 30 0 VDC setpoint The Equalize Charge Cycle provides a deliberate overcharging of t...

Страница 16: ...ally the temperature sensor part number is D012684 and the cable part number is D012638 Automatic Power Management APM A key feature of the battery charger operation is Automatic Power Management APM...

Страница 17: ...le Control Display Units Note The figure below is also available on the Rear of the Control Display Unit on 12V units ON O OFF 0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 5 O O O O O O O O 6 O O O O O...

Страница 18: ...rtment is a terminal strip for making AC input and AC output connections P14 and P15 NOTE The AC output voltage and the required AC input voltage of the ITC is 120 VAC 60Hz DC Battery Wiring A DC wiri...

Страница 19: ...is provided terminal 6 with a current limiting resistor integral to the circuit INSTALLATION Unpacking the Inverter Inspect the shipping container and equipment for loose or damaged parts If any damag...

Страница 20: ...allations do not use the vehicle chassis as the DC negative conductor Use a cable the same size as the DC positive to go directly from the inverter to the battery negative 4 Route the AC and DC power...

Страница 21: ...nd negative cables enter the compartment through separate strain reliefs located at the right front of the unit WARNING Never make electrical connections live Make the connections to the inverter firs...

Страница 22: ...vided by others to comply with the National Electric Code NFPA 70 2 AC Wire Size To properly size the AC input and output wiring the installer must consider the inverter output capability the inverter...

Страница 23: ...ield wires to the proper AC input terminals and tighten to 9 lb in max Replace the front cover Warning Do not attempt to use a stranded wire Stranded wire has a tendency to break off some of the stran...

Страница 24: ...attery Note the keyed BTS cable has same connector on both ends so cable connector orientation does not matter Make sure cable does not come into contact with sharp edges and is secured with nylon tie...

Страница 25: ...nces that contain electronic power supplies e g computers TVs and VCRs The square wave is appropriate when operating AC loads such as resistive heating devices Inverter Sizing Output Power Rating Powe...

Страница 26: ...parated into two categories according to their use engine cranking batteries and deep cycle batteries The engine cranking battery is specifically designed to supply hundreds of amps for a short period...

Страница 27: ...cases this may be true but in general the battery may be made up of several individual batteries electrically connected together to form a Bank of batteries Batteries can be connected in series parall...

Страница 28: ...installation The Battery System is responsible for supplying all of the DC power required by the inverter The system normally consists of the primary charger engine alternator or photovoltaic array a...

Страница 29: ...the type and model of battery you are using This is because battery charging parameters such as bulk absorption float and equalize voltages vary from one manufacturer to another and that gel cell batt...

Страница 30: ...corrosion free 2 Check air ventilation openings for dust and other obstructions 3 Examine receptacle indicators and switches for cracks and breaks in insulation material Trouble Shooting The Unit does...

Страница 31: ...quasiwave inverters with load demand active you will need to turn off the inverter and then turn the inverter back on to reset the GFCI receptacle within 5 seconds before the inverter goes back into l...

Страница 32: ...nverter Page 32 8 05 17 Vanner Incorporated 4282 Reynolds Drive Hilliard Ohio 43026 1 800 AC POWER 1 800 227 6937 Tel 614 771 2718 Fax 614 771 4904 www vanner com e mail pwrsales vanner com Manual Num...

Отзывы: