background image

21

105500

OWNER’S MANUAL

CLEANING AND
MAINTENANCE

 WARNING: Turn off fireplace

and let cool before cleaning.

 CAUTION: You must keep con-

trol areas, burners, and circulat-
ing air passageways of fireplace
clean. Inspect these areas of fire-
place before each use. Have fire-
place inspected yearly by a quali-
fied service person. Fireplace may
need more frequent cleaning due
to excessive lint from carpeting,
bedding material, pet hair, etc.

 WARNING: Do not use abra-

sive cleaners as this may damage
glass. Use a non-abrasive house-
hold glass cleaner to clean glass.
Do not clean glass when hot.

  WARNING: Handle glass door

panel with care. Do not strike,
slam or otherwise abuse glass.
Do not operate fireplace with the
glass door removed, cracked, or
broken.

GLASS DOOR

Glass must be cleaned periodically. During
start-up it is normal for condensation to
form on the inside of the glass causing lint,
dust, and other airborne particles to cling to
the glass surface. During initial start-up a
slight film may form on the glass due to
paint curing. The glass should be cleaned
several times with a non-amonia, non-abra-
sive household cleaner and warm water
after the first two weeks of operation. There-
after, clean the glass two or three times
during each heating season, depending on
the usage and circumstances present. Refer
to Removing/Replacing Glass Door on page
16 of this manual when removing glass door
for cleaning.

PILOT AND BURNERS

• Remove ember material before cleaning

burners and replace when cleaning is
complete.

• Burner and controls should be cleaned

with compressed air to remove dust, dirt,
or lint.

• Use a vacuum cleaner or small, soft

bristled brush to remove excess dust, dirt,
or lint.

 WARNING: Only parts sup-

plied by the manufacturer should
be used when replacing broken
or damaged glass door panel (see
Replacement Parts, page 25). This
glass door panel is a complete
unit. No substitute materials may
be used.

If glass has been broken, carefully remove
glass door (see Removing/Replacing Glass
Door,  
page 16). Vacuum all glass pieces
with a shop vac.

 CAUTION: Wear gloves and

safety glasses while handling or
removing broken glass. Do not
remove if glass is hot. Keep chil-
dren and pets away from glass.

 WARNING: Do not operate

fireplace with the glass door re-
moved, cracked, or broken.

Use only the ceramic glass door replace-
ment intended for this fireplace (see Re-
placement Parts
, page 25 for details on
ordering). No substitutions may be made.
See Removing/Replacing Glass Door, page
16 for instructions for replacing glass door.

 CAUTION: Do not vacuum if

pieces are hot.

LOGS

• If you remove logs for cleaning, refer to

Installing Logs, Lava Rock, and Glowing
Embers
, page 17, to properly replace logs.

• Use a vacuum cleaner to remove any car-

bon build-up on logs.

• Replace log(s) if broken. See Replace-

ment Parts on page 25.

• Replace ember material periodically as

needed. See Replacement Parts on page 25.

VENTING SYSTEM

Conduct annual inspection of the venting
system following these guidelines:

1.

Check areas of venting system that are
exposed to the weather for corrosion (rust
spots or streaks and, in extreme cases,
holes). Have these items replaced imme-
diately by a qualified service person.

2.

Remove the vent cap and shine a flash-
light into the vent. Remove any foreign
material.

3.

Check for evidence of excessive con-
densation. Continuous condensation
can cause corrosion of caps, pipes, and
fittings and can be caused by having
excessive lateral runs, too many el-
bows, or exterior portions of the sys-
tem being exposed to cold weather.

4.

Inspect joints to verify that no pipe sec-
tion or fitting has been disturbed and
loosened. Check mechanical supports
such as wall straps for rigidity.

Содержание SBVBN(A)

Страница 1: ...res Forassistance or additional information consultaqualifiedinstaller service agency or the gas supplier This appliance may be installed in an aftermarket manufactured mobile home where not prohibite...

Страница 2: ...qualified service person with glass door properly seated and sealed gas leakage can occur Carbon Monoxide Poisoning Early signsofcarbonmonoxidepoisoningresemble theflu withheadaches dizziness ornause...

Страница 3: ...d vents vertically Heat is gener ated by both realistic flames and glowing embers When used without the blower ac cessory the fireplace requires no electricity making it ideal for emergency backup hea...

Страница 4: ...igure 4 on page 5 4 This stove is a freestanding unit de signed to set directly on the floor If your fireplace is to be installed directly on carpeting vinyl tile or any combus tible material other th...

Страница 5: ...ing Down Stove On Side Figure 8 Removing Pallet Wood From The Bottom of The Stove Figure 6 Removing Back Panel Bolt Product Identification Label Back Stove Panel Pallet Wood Bolt Pallet Wood Bottom Of...

Страница 6: ...p nut is a bolt stop and the bot tom nut is for door leveling adjustment 12 Check general catch bolt alignment with door claw Make final adjustment and door leveling after stove is in nor mal standing...

Страница 7: ...jects in blower wheel Turn blower on and check for operation Turn blower off by rotating knob fully counterclock wise before continuing NOTICE If installing blower in an existing fireplace with gas c...

Страница 8: ...nearby combustibles This appli ance is equipped with a safety control sys tem designed to protect against improper venting of combustion products It is very important that the venting system maintain...

Страница 9: ...osure walls should have a fire rating equal to or greater than the floors through which the gas vent passes except in single or two family dwellings Situate the gas vent in the structure so that it ca...

Страница 10: ...should be relined with appropriate listed relining systems Cleanout access may be required NOTICE Consult the authority having jurisdiction in your area regarding listed chimney liner venting applicat...

Страница 11: ...c gas A simple spillage test can be con ducted if spillage is suspected See Checking Gas Connection pages 13 and 14 CAUSES OF SPILLAGE AND CORRECTIVE ACTION Incorrect Vent Sizing If the vent is too sm...

Страница 12: ...ector if allowed by local codes not provided AnA G A design certifiedmanualshutoff valve with 1 8 NPT tap is an acceptable alternative to test gauge connection Pur chase the A G A design certified man...

Страница 13: ...ation Items Needed 5 16 hex socket wrench or nut driver sealant resistant to propane LP gas not provided 1 Open lower door panel 2 Route flexible gas line provided by installer from manual shutoff val...

Страница 14: ...Open propane LP supply tank valve for propane LP fireplace or main gas valve located on or near gas meter for natu ral gas fireplace 3 Make sure control knob of fireplace is in the OFF position 4 Chec...

Страница 15: ...at sources such as lamps direct sun light fireplace or heat and air condi tioning ducts WARNING Do not connect this thermostat to a power source Electrical shock and or fire hazard will occur 5 Gently...

Страница 16: ...s seeFigure35 5 Place receiver into valve bracket and align holes see Figure 36 6 Use push in fasteners included with receiver to secure to bracket 7 Connect the wires from the receiver to the valve a...

Страница 17: ...Figure 41 Installing Log No 2 Figure 42 Installing Log No 3 Figure 43 Installing Log No 4 WARNING The glass door must be securely in place before running this fireplace Do not run this fireplace if g...

Страница 18: ...turn the gas control knob Never use tools If the knob will not push in or turn by hand don t try to repair it call a qualified service technician Force or attempted repair may result in a fire or expl...

Страница 19: ...on the hand held remote control unit Figure 47 Setting the GHRCT Selector Switch control Knob and Flame Adjustment Knob for Remote Operation TEMP STATUS HI LO MAN ON AUTO OFF Figure 48 Hand Held Ther...

Страница 20: ...Blower controls are located on the left side of the switch bracket to the left just inside the louver panel Both the GA3700 manual blower and the DA3610T thermostatically controlled blower have an ON...

Страница 21: ...e used when replacing broken ordamagedglassdoorpanel see ReplacementParts page25 This glass door panel is a complete unit No substitute materials may be used If glass has been broken carefully remove...

Страница 22: ...pen 4 Control valve damaged REMEDY 1 Reconnect ignitor cable 2 Free ignitor cable if pinched by any metal or tubing Keep ignitor cable dry 3 Tighten nut holding piezo ignitor Nut is located behind the...

Страница 23: ...from line Have gas line checked by local pro pane LP or natural gas company 3 Clean burner see Cleaning and Maintenance page 21 or replace burner orifice 1 Adjust the log set so that the flame does n...

Страница 24: ...Control valve defective 1 Gas leak See Warning statement above 1 Improper log placement 2 Air holes at burner inlet blocked 3 Burner flame holes blocked OBSERVED PROBLEM Fireplace produces unwanted o...

Страница 25: ...ng controls Wiringerrorscancause improper and dangerous opera tion Verify proper operation af ter servicing Note Use only original replacement parts Thiswillprotectyourwarrantycoveragefor parts replac...

Страница 26: ...Pressure 4 5 w c 11 0 w c Thermal Efficiency 70 70 Dimension Inches mm HxWxD Fireplace 27 x 26 x 25 27 x 26 x 25 685 8 x 660 4 x 635mm 685 8 x 660 4 x 635mm Carton Insert Only 23 x 33 x 23 23 x 33 x...

Страница 27: ...ireplaces THERMOSTATICALLY CONTROLLED BLOWER KIT DA3610T Provides better heat distribution Blower turns off and on automatically as needed Completeinstallationandoperationinstruc tions included in thi...

Страница 28: ...ENT FREESTANDING FIREPLACE 105500 ILLUSTRATED PARTS BREAKDOWN SBVBN A SBVBP A LO H I P I L O T OFF ON 24 17 18 19 21 23 1 23 4 23 2 23 3 26 27 4 22 9 4 1 10 11 8 2 4 4 7 28 13 14 15 16 20 20 25 5 29 3...

Страница 29: ...urner Propane LP 1 18 104506 03 Orifice Natural 1 104506 04 Orifice Propane LP 1 19 104507 01 Brass Elbow 1 20 104508 01 Brass Fitting 2 21 105493 01 Aluminum Tubing Assy 1 22 105325 01 Air Deflector...

Страница 30: ...repairing a defective heater will be the responsibility of the owner TOTHEFULLEXTENTALLOWEDBYTHELAWOFTHEJURISDICTIONTHATGOVERNSTHESALEOFTHEPRODUCT THIS EXPRESS WARRANTY EXCLUDES ANY AND ALL OTHER EXP...

Отзывы: