background image

13

105500

OWNER’S MANUAL

Pressure Testing Gas Supply
Piping System

Test Pressures In Excess Of 1/2 PSIG
(3.5 kPa)

1.

Disconnect fireplace and its individual
manual shutoff valve from gas supply
piping system. Pressures in excess of 1/2
psig (3.5 kPa) will damage fireplace gas
regulator.

2.

Cap off open end of gas pipe where
manual shutoff valve was connected.

3.

Pressurize supply piping system by ei-
ther opening propane/LP supply tank
valve for propane/LP gas fireplace or
opening main gas valve located on or near
gas meter for natural gas fireplace, or
using compressed air.

4.

Check all joints of gas supply piping
system. Apply commercial leak test
solution to all gas joints. Bubbles form-
ing show a leak. Correct all leaks at
once.

5.

Reconnect fireplace and manual shutoff
valve to gas supply. Check reconnected
fittings for leaks.

CHECKING GAS
CONNECTIONS

 WARNING: Test all gas pip-

ing and connections for leaks
after installing or servicing. Cor-
rect all leaks at once.

  WARNING: Never use an open

flame to check for a leak. Apply
commercial leak test solution to
all gas joints. Bubbles forming
show a leak. Correct all leaks at
once.

Installation Items Needed

• 5/16" hex socket wrench or nut-driver

• sealant (resistant to propane/LP gas, not

provided)

1.

Open lower door panel.

2.

Route flexible gas line (provided by
installer) from manual shutoff valve to
fireplace. Route flexible gas supply line
through slot in stove bottom and attach
to valve.

CONNECTING FIREPLACE
TO GAS SUPPLY

FIREPLACE
INSTALLATION

Continued

Flare Union

To Fireplace
Gas Valve

Flexible Gas Line from
Fireplace Gas Valve
Provided with Fireplace

Flexible Gas Line from
Manual Shutoff Valve
Provided by Installer

Manual Shutoff Valve

To Gas Supply
(Natural)

To External
Regulator
(Propane/LP)

Figure 27 - Attaching Flexible Gas Lines Together

Continued

Figure 26 - Gas Connection

* The A.G.A. design-certified manual shutoff valve may be supplied with the appliance or
you can purchase it from your dealer.

A.G.A. Design-
Certified Manual
Shutoff Valve with
1/8" NPT Tap*

3" Minimum

LP - From External
Regulator (11" W.C. to
14" W.C. Pressure)

Approved Flexible
Gas Line

Cap    Pipe Nipple    Tee Joint

Sediment Trap/Drip Leg

Natural - From Gas
Meter (5" W.C. to 10.5"
W.C. Pressure )

3.

Attach a 45

°

 flare union gas connector

to flexible gas line from gas supply (see
Figure 27). Connect flare union to flex-
ible gas line attached to gas regulator
of fireplace (see Figure 27).

4.

Check all gas connections for leaks. See
Checking Gas Connections.

Содержание SBVBN(A)

Страница 1: ...res Forassistance or additional information consultaqualifiedinstaller service agency or the gas supplier This appliance may be installed in an aftermarket manufactured mobile home where not prohibite...

Страница 2: ...qualified service person with glass door properly seated and sealed gas leakage can occur Carbon Monoxide Poisoning Early signsofcarbonmonoxidepoisoningresemble theflu withheadaches dizziness ornause...

Страница 3: ...d vents vertically Heat is gener ated by both realistic flames and glowing embers When used without the blower ac cessory the fireplace requires no electricity making it ideal for emergency backup hea...

Страница 4: ...igure 4 on page 5 4 This stove is a freestanding unit de signed to set directly on the floor If your fireplace is to be installed directly on carpeting vinyl tile or any combus tible material other th...

Страница 5: ...ing Down Stove On Side Figure 8 Removing Pallet Wood From The Bottom of The Stove Figure 6 Removing Back Panel Bolt Product Identification Label Back Stove Panel Pallet Wood Bolt Pallet Wood Bottom Of...

Страница 6: ...p nut is a bolt stop and the bot tom nut is for door leveling adjustment 12 Check general catch bolt alignment with door claw Make final adjustment and door leveling after stove is in nor mal standing...

Страница 7: ...jects in blower wheel Turn blower on and check for operation Turn blower off by rotating knob fully counterclock wise before continuing NOTICE If installing blower in an existing fireplace with gas c...

Страница 8: ...nearby combustibles This appli ance is equipped with a safety control sys tem designed to protect against improper venting of combustion products It is very important that the venting system maintain...

Страница 9: ...osure walls should have a fire rating equal to or greater than the floors through which the gas vent passes except in single or two family dwellings Situate the gas vent in the structure so that it ca...

Страница 10: ...should be relined with appropriate listed relining systems Cleanout access may be required NOTICE Consult the authority having jurisdiction in your area regarding listed chimney liner venting applicat...

Страница 11: ...c gas A simple spillage test can be con ducted if spillage is suspected See Checking Gas Connection pages 13 and 14 CAUSES OF SPILLAGE AND CORRECTIVE ACTION Incorrect Vent Sizing If the vent is too sm...

Страница 12: ...ector if allowed by local codes not provided AnA G A design certifiedmanualshutoff valve with 1 8 NPT tap is an acceptable alternative to test gauge connection Pur chase the A G A design certified man...

Страница 13: ...ation Items Needed 5 16 hex socket wrench or nut driver sealant resistant to propane LP gas not provided 1 Open lower door panel 2 Route flexible gas line provided by installer from manual shutoff val...

Страница 14: ...Open propane LP supply tank valve for propane LP fireplace or main gas valve located on or near gas meter for natu ral gas fireplace 3 Make sure control knob of fireplace is in the OFF position 4 Chec...

Страница 15: ...at sources such as lamps direct sun light fireplace or heat and air condi tioning ducts WARNING Do not connect this thermostat to a power source Electrical shock and or fire hazard will occur 5 Gently...

Страница 16: ...s seeFigure35 5 Place receiver into valve bracket and align holes see Figure 36 6 Use push in fasteners included with receiver to secure to bracket 7 Connect the wires from the receiver to the valve a...

Страница 17: ...Figure 41 Installing Log No 2 Figure 42 Installing Log No 3 Figure 43 Installing Log No 4 WARNING The glass door must be securely in place before running this fireplace Do not run this fireplace if g...

Страница 18: ...turn the gas control knob Never use tools If the knob will not push in or turn by hand don t try to repair it call a qualified service technician Force or attempted repair may result in a fire or expl...

Страница 19: ...on the hand held remote control unit Figure 47 Setting the GHRCT Selector Switch control Knob and Flame Adjustment Knob for Remote Operation TEMP STATUS HI LO MAN ON AUTO OFF Figure 48 Hand Held Ther...

Страница 20: ...Blower controls are located on the left side of the switch bracket to the left just inside the louver panel Both the GA3700 manual blower and the DA3610T thermostatically controlled blower have an ON...

Страница 21: ...e used when replacing broken ordamagedglassdoorpanel see ReplacementParts page25 This glass door panel is a complete unit No substitute materials may be used If glass has been broken carefully remove...

Страница 22: ...pen 4 Control valve damaged REMEDY 1 Reconnect ignitor cable 2 Free ignitor cable if pinched by any metal or tubing Keep ignitor cable dry 3 Tighten nut holding piezo ignitor Nut is located behind the...

Страница 23: ...from line Have gas line checked by local pro pane LP or natural gas company 3 Clean burner see Cleaning and Maintenance page 21 or replace burner orifice 1 Adjust the log set so that the flame does n...

Страница 24: ...Control valve defective 1 Gas leak See Warning statement above 1 Improper log placement 2 Air holes at burner inlet blocked 3 Burner flame holes blocked OBSERVED PROBLEM Fireplace produces unwanted o...

Страница 25: ...ng controls Wiringerrorscancause improper and dangerous opera tion Verify proper operation af ter servicing Note Use only original replacement parts Thiswillprotectyourwarrantycoveragefor parts replac...

Страница 26: ...Pressure 4 5 w c 11 0 w c Thermal Efficiency 70 70 Dimension Inches mm HxWxD Fireplace 27 x 26 x 25 27 x 26 x 25 685 8 x 660 4 x 635mm 685 8 x 660 4 x 635mm Carton Insert Only 23 x 33 x 23 23 x 33 x...

Страница 27: ...ireplaces THERMOSTATICALLY CONTROLLED BLOWER KIT DA3610T Provides better heat distribution Blower turns off and on automatically as needed Completeinstallationandoperationinstruc tions included in thi...

Страница 28: ...ENT FREESTANDING FIREPLACE 105500 ILLUSTRATED PARTS BREAKDOWN SBVBN A SBVBP A LO H I P I L O T OFF ON 24 17 18 19 21 23 1 23 4 23 2 23 3 26 27 4 22 9 4 1 10 11 8 2 4 4 7 28 13 14 15 16 20 20 25 5 29 3...

Страница 29: ...urner Propane LP 1 18 104506 03 Orifice Natural 1 104506 04 Orifice Propane LP 1 19 104507 01 Brass Elbow 1 20 104508 01 Brass Fitting 2 21 105493 01 Aluminum Tubing Assy 1 22 105325 01 Air Deflector...

Страница 30: ...repairing a defective heater will be the responsibility of the owner TOTHEFULLEXTENTALLOWEDBYTHELAWOFTHEJURISDICTIONTHATGOVERNSTHESALEOFTHEPRODUCT THIS EXPRESS WARRANTY EXCLUDES ANY AND ALL OTHER EXP...

Отзывы: