1.0 Introduction
The CT-6500 is a microprocessor-based, digital time travel, circuit breaker analyzer. The CT-
6500 can fully analyze a utility circuit breaker’s performance by measuring: the contact time,
stroke, velocity, over-travel, bounce-back and contact wipe.
The contact motion analysis includes: Open, Close, Open-Close, Close-Open and Open-
Close-Open operations. A timing window is selectable between one second, ten second and
twenty second periods. The ten and twenty second windows allow timing of long events such as
circuit switcher contacts.
The CT-6500 is available with the following configurations:
CT-6500-3:
n
Three Contact-Input channels
n
Three Digital Travel Transducer Input channels
n
One Analog Voltage Monitor Input channel
n
One Digital Voltage Monitor Input channel
n
One Trip/Close Current Monitor channel
CT-6500-6:
n
Six Contact-Input channels
n
Three Digital Travel Transducer Input channels
n
One Analog Voltage Monitor Input channel
n
One Digital Voltage Monitor Input channel
n
One Trip/Close Current Monitor channel
CT-6500-12:
n
Twelve Contact-Input channels
n
Three Digital Travel Transducer Input channels
n
One Analog Voltage Monitor Input channel
n
One Digital Voltage Monitor Input channel
n
One Trip/Close Current Monitor channel
There are two different modes of operation for the CT-6500 which are Stand Alone Mode and
Computer Control Mode. The manual will focus on the Stand Alone Mode. The Computer Control
Mode is covered under the CT-6500/7000/7500/DIGITMR PC software manual.
2.0 CT-6500 Description
The CT-6500 applies a test voltage of 35 Vdc to each of the contact channels thus allowing an
analog to digital converter (A/D) to determine if a close, an open or an insertion resistor was the
state of contact. The CT-6500 records into the memory 10,000 readings from the A/Ds and the
transducer position counters. The contact time, circuit breaker stroke and velocity is then derived
from the data that was stored in the memory.
The CT-6500 uses an up-down counter to sense the breaker’s transducer reading. The CT-
6500 travel transducer employs optical encoders to send quadrature signals to the CT-6500’s
counters. With the use of digital transducers and counters, the need to set up or calibrate the
transducers is eliminated.
A built-in, initiate circuit allows the user to operate the circuit breakers. Since the solid-state
circuit is controlled by a microprocessor, the CT-6500 can perform multiple contact operations
with ease. The initiate circuit is fuse protected for trip and close operations. The user is required
to hold the “ARM” switch during a test to complete the initiate circuit as a safety feature.
Содержание CT-6500
Страница 19: ...CT 6500 Operating Instructions 12 Figure 3 0 Series Contact Cable Connection...
Страница 41: ...CT 6500 Operating Instructions 34 Figure 16 0 Printout of the Timing Shot Directory From the Thermal Printer...
Страница 63: ...CT 6500 Operating Instructions 56 APPENDIX B CLOSE OPEN Timing Chart for ITE Circuit Breaker Model 14 4K...
Страница 64: ...CT 6500 Operating Instructions 57 APPENDIX C CLOSE OPEN Tabulated Report for ITE Circuit Breaker Model 14 4K...
Страница 65: ...CT 6500 Operating Instructions 58 APPENDIX D OPEN CLOSE Timing Chart for ITE Circuit Breaker Model 14 4K...
Страница 66: ...CT 6500 Operating Instructions 59 APPENDIX E OPEN CLOSE Tabulated Report for ITE Circuit Breaker Model 14 4K...
Страница 69: ...www vanguard instruments com...