CT-6500 Operating Instructions
14
8.3 Analog Voltage Monitor Hookup
The analog, voltage input, “V1” permits the user to monitor a breaker's DC control voltage
during an operation.
The analog, voltage input will record the nominal DC voltage at no load and
the minimum DC voltage while the Trip or Close coil is energized.
The nominal and minimal voltage readings will be printed on a tabulated report. Analog
waveforms will also be plotted in a graphical format. Thus, the user is able to see the breaker's
DC control voltage "dip" under load conditions. Problems, such as a poor connection or an
excessive voltage drop, during operation can be easily detected.
A typical voltage monitoring hook up scheme is shown on Figure 6.0.
NOTE
The maximum voltage that can be recorded is set at 255 Vdc.
Figure 6.0 Voltage Monitoring Cable Hook-Up
8.4 Digital Voltage Monitor Hookup
The digital, voltage input channel, “V2” permits the user to monitor the voltage status as “ON”
or “OFF” states. The voltage “ON” or “OFF” states will be plotted on the graphical report. A typical
hook up is shown in Figure 6.0.
Содержание CT-6500
Страница 19: ...CT 6500 Operating Instructions 12 Figure 3 0 Series Contact Cable Connection...
Страница 41: ...CT 6500 Operating Instructions 34 Figure 16 0 Printout of the Timing Shot Directory From the Thermal Printer...
Страница 63: ...CT 6500 Operating Instructions 56 APPENDIX B CLOSE OPEN Timing Chart for ITE Circuit Breaker Model 14 4K...
Страница 64: ...CT 6500 Operating Instructions 57 APPENDIX C CLOSE OPEN Tabulated Report for ITE Circuit Breaker Model 14 4K...
Страница 65: ...CT 6500 Operating Instructions 58 APPENDIX D OPEN CLOSE Timing Chart for ITE Circuit Breaker Model 14 4K...
Страница 66: ...CT 6500 Operating Instructions 59 APPENDIX E OPEN CLOSE Tabulated Report for ITE Circuit Breaker Model 14 4K...
Страница 69: ...www vanguard instruments com...