CT-6500 Series 2 Operating Instructions
64
9.20 Print Test Record Data
Print data command allows the user to print the hexadecimal timing data collected by the CT-
6500. This feature is mainly for factory testing. The CT-6500 collects 20,000 data points in the
one-second timing window. As a results, each data sample is 0.05 ms apart. By looking at the
time marker and the data point, the user can actually find the channel activities vs time in the
timing record.
The following steps allow the user to print CT-6500 timing data from memory.
Table 25.0 Print Test Record Data
STEP
OPERATION
ACTION
DISPLAY
1
SELECT DIAGNOSTIC.
PRESS # 4 KEY.
1. SLOW-CLOSE TEST
2. CHECK HOOKUP
3. TEST TRANSDUCER
4. NEXT PAGE
2
SELECT NEXT PAGE.
PRESS # 4 KEY.
1. PRINT DATA
2. ENCODER FILTER
3. CONTACT FILTER
3
SELCT PRINT DATA.
PRESS # 1 KEY.
STARTING ADDRESS?:
4
ENTER ADDRESS BOUNDARY
(See note below)
PRESS KEY # 1 to 9
1. EVERY POINT
2. EVERY 5 POINTS
5
CT-6500 PRINTS DATA.
NONE.
1. EVERY POINT
2. EVERY 5 POINTS
6
RETURN TO MAIN MENU.
PRESS THE "STOP"
KEY.
1.RUN TEST 06/10/07
2.GET RESULTS 20:10:01
3.SETUP
4.DIAGNOSTIC
As sample of the CT-6500 timing data print out is shown in Figure 21.0.
Note
Pressing key #0 will start printing the data at address location 0 (or the first data point)
Pressing key #1 will start printing the data at address location .10000 second.
Figure 21.0 CT-6500 Timing Data
Time marker 0.10010 ms
Timer marker 0.100000 ms
Содержание CT-6500 2 Series
Страница 22: ...CT 6500 Series 2 Operating Instructions 21 Figure 4 0 Series Contact Cable Connection...
Страница 77: ...CT 6500 Series 2 Operating Instructions 76 APPENDIX F SIEMENS TCP Breaker Velocity Calculation...
Страница 78: ...CT 6500 Series 2 Operating Instructions 77 APPENDIX G SIEMENS SPS2 Breaker Velocity Calculation...
Страница 79: ...CT 6500 Series 2 Operating Instructions 78 APPENDIX H CT 6500 SIEMENS SPS2 Test Plan...
Страница 82: ...www vanguard instruments com...