CT-6500 Series 2 Operating Instructions
58
9.15 Check Cable Hookup
The following steps allow the user to check the CT-6500 contact cable connections to the circuit
breaker.
Table 20.0 Checking the Cable Hookup
STEP
OPERATION
ACTION
DISPLAY
1
SELECT DIAGNOSTIC.
PRESS # 4 KEY.
1. SLOW-CLOSE TEST
2. CHECK HOOKUP
3. TEST TRANSDUCER
4. NEXT PAGE
2
SELECT CHECK HOOK UP.
PRESS # 2 KEY.
MAKE SURE BREAKER
IS IN CLOSE POSITION,
THEN PRESS "START"
3
INITIATE TEST.
PRESS THE "START"
KEY.
1 2 3
C - - -
“START” to RETEST
“STOP” to EXIT
4
RETURN TO MAIN MENU.
PRESS THE "STOP"
KEY.
1.RUN TEST 06/10/07
2.GET RESULTS 20:10:01
3.SETUP
4.DIAGNOSTIC
NOTES
1. The CT-6500 will also print a test report with the thermal printer.
2. A contact closure is shown as "C" on the LCD and printout.
3. An open contact is shown as "-" on the LCD and printout.